Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-13 Cont ID  
Sent By vperez Date 2017-04-13 Time 10:22 Rev Time 0.00
Received By vperez Date 2017-04-13 Time 10:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-19 Cont ID  
Sent By vperez Date 2017-01-19 Time 15:20 Rev Time 0.00
Received By vperez Date 2017-01-19 Time 15:20 Sent To  
Notes
2017-01-19 15:21:28PLEASE PROVIDE SOME TYPE OF DRAWING SHOWING THE
 ELECTRICAL FEED TO NEW GAS IGNITOR. LOCATION, SIZE OF
 WIRE, DISCONNECT WITHIN SIGHT OF EQUIPMENT ETC.
  
 ADDRESS GAS COMMENTS
  
 V. PEREZ
 *6717

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2017-12-19 Cont ID  
Sent By tklarge Date 2017-12-19 Time 13:37 Rev Time 0.00
Received By tklarge Date 2017-12-19 Time 13:37 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2017-11-21 Cont ID  
Sent By tklarge Date 2017-11-21 Time 09:50 Rev Time 0.00
Received By tklarge Date 2017-11-21 Time 06:27 Sent To I
Notes
2017-11-21 06:57:361) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THIS
 SUBMITTAL. I COULD NOT PERFORM A COMPREHENSIVE PLAN
 REVIEW DUE TO THE FACT IT IS UNCLEAR AS TO WHAT IS
 BEING INSTALLED AND WHICH DRAWING IS THE CORRECT
 DRAWING TO REVIEW. ONE PLAN SHOWS A GAS DRYER AND THE
 OTHER PLAN DOES NOT. THE CONTRACTOR SHALL REVIEW ALL
 THE SUBMIITED PLANS AND DISCARD ALL UNEEDED PLANS AND
 COMBINE THE APPLICABLE DRAWINGS INTO TWO COMPLETE SETS
 FOR SUBMITTAL AND REVIEW. WPB AMEND. TO FBC SEC. 107.1.
 2) THE GAS DRYER IN THE GARAGE SHALL BE PROTECTED FROM
 PHYSICAL DAMAGE PER 2014 FBC-FUEL GAS SEC. 305.5.SHOW
 ON THE PLAN HOW THIS BEING ACCOMPLISHED. 4TH REQUEST
 3) THE INSTALLATION OF THE DRYER SHALL COMPLY WITH THE
 FUEL GAS CODE SEC. 305.3.4TH REQUEST.
 4) THE PLAN NOTES THAT PE PIPE WILL BE USED TO SUPPLY
 GAS TO THE POOL HEATER BUT THE SIZING TABLE THAT WAS
 SUBMITTED IS FOR COPPER TUBING. SUBMIT 2 COPIES OF THE
 SIZING TABLE FOR PE PIPE THAT IS BEING USED. 4TH
 REQUEST.
 5) SUBMIT TWO COMPLETE COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL HEATER. THE POOL HEATER
 SHALL BE LISTED AND LABELED PER 2014 FBC SEC. 301.3.
 THE DOCUMENT THAT HAS BEEN SUBMITTED IS A SHEET FROM
 THE INTERNET AND DOES NOT SUPPLY THE REQUESTED
 INFORMATION. 4TH REQUEST.
 6) THE POOL HEATER SHALL COMPLY WITH 2014 FBC-ENERGY
 SEC. R403.9.1.1.4TH REQUEST.
 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER.
 YOU HAVE SUPPLIED A NUMBER OF 2496 CUBIC FEET BUT ALSO
 REFERENCED SEC.614.5 OF THE FUEL GAS CODE WHICH
 REQUIRES INSTALLATIONS EXHAUSTING MMORE THAN 200 CFM'S
 TO BE PROVIDED WITH MAKEUP AIR. THIS IS CONFUSING AS TO
 HOW YOU ARE COMPLYING. CLARIFY HOW YOU ARE COMPLYING
 WITH THE GAS CODE FOR COMBUSTION AIR. 4TH REQUEST.
 8) SUBMIT TWO COPIES OF THE INSTALLATION MANUAL FOR THE
 TANKLESS WATER HEATER FOR REVIEW. THE LOCATION OF THE
 TANKLESS WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION MANUAL.WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1.
 9) A SET OF PLANS HAS BEEN SUBMITTED THAT IS DRAWN IN
 PENCIL. PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THE
 DRAWING CAN BE MODIFIED/CHANGED.
 10) SHOW THE LOCATION OF THE GAS METERS ON THE PLAN
 DRAWING. ONE SET OF PLANS HAS THE LOCATION OF THE GAS
 METERS AND THE OTHER DOES NOT. I HAVE NO IDEA AS TO
 WHICH PLAN IS THE ONE TO BE REVIEWED. WPB AMEND. TO FBC
 SEC. 107.2.1.
 11) SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS DRYER. THE SPECIFICATION THAT HAS BEEN
 SUBMITTED IS FROM THE INTERNET AND DOES NOT SUPPLY THE
 REQUIRED INFORMATION. THE GAS DRYER SHALL BE LISTED AND
 LABELED PER THE 2014 FBC-FUEL GAS SEC.301.3. THE
 MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT
 ARE BEING EXHAUSTED BY THE DRYER.
 12) ONE SUBMITTED GAS DRAWING SHOWS THE BTU VALUE OF
 THE TANKLESS WATER HEATER AS 199,000 AND ANOTHER
 DRAWING SHOWS 180,000. THE SUBMITTED SPECIFICATIONS
 SHOW A MAXIMUM BTU LOAD OF THE SPECIFIED MODEL AS
 180,000. WHAT MODEL IS BEING INSTALLED? CLARIFY.
 ***NOTE: THE NEXT PLAN REVIEW SUBMITTAL SHALL BE
 SUBJECT TO FOUR TIMES THE PLAN REVIEW FEE IN ACCORDANCE
 WITH FL. STATUTE 553.80 (2) (B).
 NO FURTHER PLAN REVIEW WILL BE DONE ON THIS PERMIT
 APPLICATION UNTIL THE QUALIFIER OF THE COMPANY CONTACTS
 THE CHIEF PLUMBING INSPECTOR AND MEETS WITH THE CHIEF
 PLUMBING INSPECTOR TO REVIEW AND DISCUSS THESE PLAN
 REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-10-04 Cont ID  
Sent By thunt Date 2017-10-04 Time 07:11 Rev Time 0.00
Received By thunt Date 2017-10-04 Time 07:11 Sent To  
Notes
2017-10-04 07:14:2410/4/17 3RD PLUMBING REVIEW*DENIED*
  
 FURTHER PLAN REVIEW COULD RESULT IN A 4X PLAN REVIEW
 FEE PER F.S.553.7.9 (B) (2)
  
 ONLY 1 OF THE 7 COMMENTS HAVE BEEN ADDRESS FROM 2ND
 PLAN REVIEW REGRADING THE CORRECT SIZING TABLE. PLEASE
 REVIEW PLAN REVIEW 2ND COMMENTS AND CALL REVIEWER
 BEFORE SUBMITTING CORRECTIONS
  
 1) THE GAS DRYER IN THE GARAGE SHALL BE PROTECTED FROM
 PHYSICAL DAMAGE PER 2014 FBC-FUEL GAS SEC. 305.5.
 2) THE INSTALLATION OF THE DRYER SHALL COMPLY WITH THE
 FUEL GAS CODE SEC. 305.3.
 3) SUBMIT MANUF. SPECIFICATIONS FOR THE POOL HEATER.
 THE POOL HEATER SHALL BE LISTED AND LABELED PER 2014
 FBC SEC. 301.3.
 4) THE POOL HEATER SHALL COMPLY WITH 2014 FBC-ENERGY
 SEC. R403.9.1.1.
 5) THE INSTALLATION SHEET I PRINTED FROM THE DESIGN
 MANUAL SHOWS A REQUIRED DISTANCE OF 4 FEET FROM
 OPERABLE DOORS OR WINDOWS AND YOU HAVE STATED ON THE
 PLANS A DISTANCE OF ONE FOOT IS REQUIRED. CLARIFY.
 REFER TO THE MANUF. SHEET. I PLACED IN YOUR PLANS.
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER.
 YOU HAVE SUPPLIED A NUMBER OF 2496 CUBIC FEET BUT ALSO
 REFERENCED SEC.614.5 OF THE FUEL GAS CODE WHICH
 REQUIRES INSTALLATIONS EXHAUSTING MMORE THAN 200 CFM'S
 TO BE PROVIDED WITH MAKEUP AIR. THIS IS CONFUSING AS TO
 HOW YOU ARE COMPLYING. CLARIFY HOW YOU ARE COMPLYING
 WITH THE GAS CODE FOR COMBUSTION AIR.
  
  
 NOTE: IT MAY BE BENEFICIAL FOR THE CONTRACTOR TO CALL
 AND SET UP AN APPOINTMENT TO GO OVER THESE COMMENTS.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-04-14 Cont ID  
Sent By tklarge Date 2017-04-14 Time 06:48 Rev Time 0.00
Received By tklarge Date 2017-04-14 Time 05:58 Sent To  
Notes
2017-04-14 06:05:571) THE GAS DRYER IN THE GARAGE SHALL BE PROTECTED FROM
 PHYSICAL DAMAGE PER 2014 FBC-FUEL GAS SEC. 305.5.
 2) THE INSTALLATION OF THE DRYER SHALL COMPLY WITH THE
 FUEL GAS CODE SEC. 305.3.
 3) THE PLAN NOTES THAT PE PIPE WILL BE USED TO SUPPLY
 GAS TO THE POOL HEATER BUT THE SIZING TABLE THAT WAS
 SUBMITTED IS FOR COPPER TUBING. SUBMIT 2 COPIES OF THE
 SIZING TABLE FOR PE PIPE THAT IS BEING USED.
 4) SUBMIT MANUF. SPECIFICATIONS FOR THE POOL HEATER.
 THE POOL HEATER SHALL BE LISTED AND LABELED PER 2014
 FBC SEC. 301.3.
 5) THE POOL HEATER SHALL COMPLY WITH 2014 FBC-ENERGY
 SEC. R403.9.1.1.
 6) THE INSTALLATION SHEET I PRINTED FROM THE DESIGN
 MANUAL SHOWS A REQUIRED DISTANCE OF 4 FEET FROM
 OPERABLE DOORS OR WINDOWS AND YOU HAVE STATED ON THE
 PLANS A DISTANCE OF ONE FOOT IS REQUIRED. CLARIFY.
 REFER TO THE MANUF. SHEET. I PLACED IN YOUR PLANS.
 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER.
 YOU HAVE SUPPLIED A NUMBER OF 2496 CUBIC FEET BUT ALSO
 REFERENCED SEC.614.5 OF THE FUEL GAS CODE WHICH
 REQUIRES INSTALLATIONS EXHAUSTING MMORE THAN 200 CFM'S
 TO BE PROVIDED WITH MAKEUP AIR. THIS IS CONFUSING AS TO
 HOW YOU ARE COMPLYING. CLARIFY HOW YOU ARE COMPLYING
 WITH THE GAS CODE FOR COMBUSTION AIR.
  
  
 NOTE: IT MAY BE BENEFICIAL FOR THE CONTRACTOR TO CALL
 AND SET UP AN APPOINTMENT TO GO OVER THESE COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-01-17 Cont ID  
Sent By tklarge Date 2017-01-17 Time 05:46 Rev Time 0.00
Received By tklarge Date 2017-01-17 Time 05:20 Sent To E
Notes
2017-01-17 05:46:011. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413. THE SPEC SHEETS FOR THE DRYER
 SHOW THE HEATING ELEMENT IS 22,000 BTU FOR THE
 ELECTRICAL RATING, THIS IS NOT THE GAS RATING. ALSO,
 THE SPEC SHEETS DO NOT SHOW THAT THE DEVICE IS LISTED
 AND LABELED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 9. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. SPEC
 SHEETS DO NOT SHOW THE DRYER IS LISTED AND LABELED.
  
 10) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
  
 11) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER APPROVED / RECOGNIZED STANDARD USED IN THE DESIGN
 OF THIS SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
 NOTE: THIS SUBMITTAL WAS LACKING SO MUCH BASIC
 INFORMATION THAT ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON FUTURE REVIEW WHEN THE REQUIRED
 INFORMATION IS SUBMITTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-12-19 Cont ID  
Sent By tklarge Date 2017-12-19 Time 13:38 Rev Time 0.00
Received By tklarge Date 2017-12-19 Time 13:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-11-21 Cont ID  
Sent By tklarge Date 2017-11-21 Time 09:50 Rev Time 0.00
Received By tklarge Date 2017-11-17 Time 11:43 Sent To  
Notes
2017-11-20 11:43:24RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-04 Cont ID  
Sent By cpuell Date 2017-10-04 Time 13:42 Rev Time 0.00
Received By cpuell Date 2017-09-29 Time 11:45 Sent To  
Notes
2017-10-02 11:45:46RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-14 Cont ID  
Sent By tklarge Date 2017-04-14 Time 06:48 Rev Time 0.00
Received By tklarge Date 2017-04-12 Time 08:14 Sent To  
Notes
2017-04-12 08:15:01RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-19 Cont ID  
Sent By vperez Date 2017-01-19 Time 15:21 Rev Time 0.00
Received By vperez Date 2017-01-19 Time 15:21 Sent To  
Notes
2017-01-10 12:55:24PLEASE PLACE IN PLUMBING < 5K

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-17 Cont ID  
Sent By tklarge Date 2017-01-17 Time 05:49 Rev Time 0.00
Received By tklarge Date 2017-01-17 Time 05:46 Sent To  
Notes
***NONE***