| 2017-01-12 12:27:03 | 2001 SOUTH DIXIE HIGHWAY |
| | TRACKING #17010266 |
| | PERMIT #16041215 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FIRE RESCUE HAS NO OBJECTIONS TO THE PRODUCT (DC315 |
| | INTUMESCENT PAINT) UTILIZED TO PROTECT THE EXISTING |
| | SPRAY POLYURETHANE FOAM (SPF). NOTE THE MANUFACTURER'S |
| | APPLICATION REQUIREMENTS ARE VERY SPECIFIC AND REQUIRE |
| | DOCUMENTATION. REFERENCE PAINTTOPROTECT.COM DC315. THE |
| | PLAN REVIEW HAS BEEN APPROVED FOR THIS PRODUCT; |
| | HOWEVER, IN ORDER TO PASS INSPECTION THE MANUFACTURER'S |
| | REQUIREMENTS FOR APPLICATION DOCUMENTATION MUST BE |
| | PROVIDED. |
| | |
| | PRODUCT SPECIFICATIONS INDICATE: |
| | |
| | APPLICATOR SHALL PERFORM CONTINUOUS WET FILM THICKNESS |
| | CHECKS, MINIMUM 1 PER 100 SQUARE FEET. MEDALLIONS SHALL |
| | BE INSTALLED AT MINIMUM OF 1 PER 400 SQUARE FEET AND |
| | SHALL BE MAINTAINED WITH CONTRACT DOCUMENTS FOR |
| | VERIFICATION OF DRY FILM THICKNESS. APPLICATOR SHALL |
| | COMPLETE A JOB WORK REPORT THAT INCLUDES AMBIENT |
| | CONDITIONS, APPLICATION THICKNESS AND RESULTS OF |
| | ADHESION TESTING. UPON COMPLETION, A JOB SITE LABEL |
| | SHALL BE AFFIXED IN AN AREA SUCH AS THE ELECTRICAL |
| | PANEL AND SHALL INCLUDE APPLICATOR NAME AND CONTACT |
| | INFORMATION, COMPANY INFORMATION, PRODUCTS USED, |
| | MEASURED APPLICATION THICKNESS. JOB WORK REPORTS MUST |
| | BE SUBMITTED TO IFRM MANUFACTURER WITHIN 7 DAYS OF |
| | COMPLETION OF PROJECT. |
| | |
| | REQUIRED SURFACES SHALL BE PRIMED WITH A COMPATIBLE |
| | PRIMER APPROVED BY THE THIN-FILM FIRE RESISTIVE |
| | MATERIALMANUFACTURER. |
| | |
| | THE THIN-FILM FIRE RESISTIVE MATERIAL SHALL BE APPLIED |
| | AT THE REQUIRED DRY FILM THICKNESS PER THE APPROPRIATE |
| | SPF TEST REPORT AND MANUFACTURERS WRITTEN APPLICATION |
| | INSTRUCTIONS. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |