Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-02-23 Cont ID  
Sent By skennedy Date 2017-02-23 Time 13:53 Rev Time 0.00
Received By skennedy Date 2017-02-23 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-02-16 Cont ID  
Sent By shill Date 2017-02-16 Time 16:58 Rev Time 0.00
Received By shill Date 2017-02-16 Time 16:58 Sent To  
Notes
2017-02-16 17:00:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SEE GENERAL LIMITATION #7, THE ASSEMBLY SELECTED IS
 TO MEET THE DESIGN PRESSURES FOR ZONE 1. ENGINEERING
 SPECIFIES FIELD AREA AS -73 PSF, ASSEMBLY IS LIMITED TO
 -52.5 PSF.
  
 2. FBC 5TH EDITION RESIDENTIAL FIGURE 301.2(7), ZONE 3
 TO EQUAL 4' IN ALL CASES. PLEASE REVISE NOTE 1 WHICH
 SPEFICIES "NOT LESS THAN 3'-0"".
  
 3. ZONE 2 SPECIFIES 5.8"; SEE RAS 117 10.4.5, ALL
 FRACTIONS TO BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
  
 3. ZONE 3 SPECIFIES 4.3" SPACING; SEE RAS 117 10.4.5,
 ALL FRACTIONS TO BE ROUNDED DOWN TO THE NEXT WHOLE
 NUMBER.
  
 4. ALL PRODUCT APPROVALS IN THE SUBMITTAL WERE MARKED
 "VOID" BY THE APPLICANT. PROVIDE TWO SETS OF EACH
 PRODUCT APPROVAL (FLAT DECK, SHINGLES).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-02-08 Cont ID  
Sent By shill Date 2017-02-08 Time 15:10 Rev Time 0.00
Received By shill Date 2017-02-08 Time 15:10 Sent To  
Notes
2017-02-08 15:13:00****CORRECTIONS****
 REVISED 2/13/17
 REVISED 2/14/17
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE ASSEMBLY SELECTED REFERS TO GENERAL LIMITATION
 #9. SEE GENERAL LIMITATIONS ON PAGE 16. #7 WAS CIRCLED,
 BUT IS NOT APPLICABLE. #9 DOES NOT ALLOW ENHANCED
 FASTENING.
  
 PLEASE SELECT A DIFFERENT ASSEMBLY AND REVISE
 ENGINEERING. AS DISCUSSED, THIS MAY BE SENT VIA EMAIL
 FOR PRELIMINARY REVIEW WITH ORIGINAL REQUIRED AT TIME
 OF PICKUP.
  
 (NOTE - CONTRACTOR AND ENGINEER ELECTED NOT TO PROVIDE
 VIA EMAIL)
  
 2. REGARDING THE CALCULATIONS, FBC R 301:
  
 FBC 5TH EDITION RESIDENTIAL FIGURE 301.2(7), ZONE 3 TO
 EQUAL 4' IN ALL CASES.
  
 CLARIFY SHEET WIDTH OF 60. SEE THE NOA PROVIDED, THE
 BASE SHEETS FOR THE SELECTED ASSEMBLY ARE ALL 36" IN
 WIDTH.
  
 PROVIDE THE PAGES OF THE NOA WHICH APPLY TO ALL
 ASSEMBLIES; THIS SHOULD INCLUDE THE FIRST PAGES WHICH
 PROVIDE PRODUCT DESCRIPTIONS.
  
 CLARIFY 14" ROW SPACING; THE ATTACHMENT REQUIREMENTS
 SPECIFY FOUR ROWS 14" APART, BUT THE SHEET IS ONLY 36".
 ARE YOU PROPOSING AN ALTERNATE PRODUCT?
  
 CLARIFY SPECIFICATION; 4 ROWS PROPOSED; CONFIRM THAT
 THIS IS FOUR ROWS TOTAL (ONE IN THE 4" LAP AND THREE IN
 THE FIELD), OR REVISE TO CLARIFY.
  
 ZONE 2 SPECIFIES 4.8" OC W/12" SIDELAP SPACING -
 CLARIFY HOW IT IS POSSIBLE FOR THE LAP TO BE 12", A
 DRAWING MAY BE REQUIRED. 4" OR LESS IS TYPICAL. THE
 SPECIFICATION OF A 12" LAP DOES NOT FOLLOW THE RAS117
 REQUIREMENTS, REVISE OR CLARIFY.
  
 ZONE 2 SPECIFIES 4.8"; SEE RAS 117 10.4.5, ALL
 FRACTIONS TO BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
  
 ZONE 3 SPECIFIES 3.2" SPACING; SEE RAS 117 10.4.5, ALL
 FRACTIONS TO BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
  
 ZONE 3 SPECIFIES 3.2" SPACING; SEE RAS 117 8.1, THE
 MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN 4 IN
 OC.
  
 THE CALCULATIONS DO NOT APPEAR CORRECT. HOWEVER, THE
 SPECIFICATION IS WHAT WILL DETERMINE WHETHER OR NOT THE
 CALCULATIONS WILL BE ACCEPTED (PASS PLAN REVIEW). A
 COMPLIANT SPECIFICATION WILL RESULT IN PERMIT ISSUANCE,
 EVEN IF THE CALCULATIONS ARE NOT CORRECT (NOT IN
 ACCORDANCE WITH RAS 117).
  
 NEW COMMENT 2/14/17
  
 KATI FROM JIJ CONSTRUCTION MARKED ALL FOUR PRODUCT
 APPROVALS "VOID" (TWO SHINGLE, TWO FLAT). NO ADDITIONAL
 PRODUCT APPROVALS WERE SUBMITTED. WHEN RESUBMITTING,
 PROVIDE TWO COMPLETE SETS OF PRODUCT APPROVALS TO
 REPLACE THE VOIDED PRODUCT APPROVALS
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-24 Cont ID  
Sent By shill Date 2017-01-24 Time 16:42 Rev Time 0.00
Received By shill Date 2017-01-24 Time 16:42 Sent To  
Notes
2017-01-24 16:43:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FOR THE FLAT DECK, INDICATE THE APPROVED ASSEMBLY
 PROPOSED AND PROVIDE ENGINEERING FOR THE ENHANCED
 FASTENING, FBC RESIDENTIAL 301.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-09 Cont ID  
Sent By shill Date 2017-01-09 Time 18:17 Rev Time 0.00
Received By shill Date 2017-01-09 Time 18:17 Sent To  
Notes
2017-01-09 18:18:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FOR THE FLAT DECK, INDICATE THE APPROVED ASSEMBLY
 PROPOSED AND PROVIDE ENGINEERING FOR THE ENHANCED
 FASTENING, FBC RESIDENTIAL 301.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-08 Cont ID  
Sent By shill Date 2017-02-08 Time 15:13 Rev Time 0.00
Received By shill Date 2017-01-31 Time 11:34 Sent To  
Notes
2017-02-01 11:34:55RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-24 Cont ID  
Sent By shill Date 2017-01-24 Time 16:43 Rev Time 0.00
Received By shill Date 2017-01-18 Time 10:01 Sent To  
Notes
2017-01-19 10:01:10RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-09 Cont ID  
Sent By shill Date 2017-01-09 Time 18:18 Rev Time 0.00
Received By shill Date 2017-01-09 Time 16:33 Sent To  
Notes
2017-01-09 16:33:31SHILL'S DESK


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved