| 2017-01-10 03:31:33 | 1) THE SUBMITTED GAS PLAN NOTES AN "EXISTING " GAS |
| | METER. INDICATE ON THE PLAN IF THE TANKLESS WATER |
| | HEATER IS THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF |
| | NOT, SUBMIT A GAS RISER SHOWING ALL GAS APPLIANCES ON |
| | THE SYSTEM, THE BTU LOAD OF EACH APPLIANCE AND THE |
| | LONGEST LENGTH OF PIPING FROM THE POINT OF DELIVERY TO |
| | THE MOST REMOTE OUTLET AND THEBTU LOAD OF EACH SECTION |
| | OF PIPE. |
| | 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER IN RELATION TO |
| | THE LOCATION OF ANY OPERABLE DOORS OR WINDOWS AND SHOW |
| | THE DISTANCES TO SUCH DOORS AND WINDOWS.THE LOCATION OF |
| | THE WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. SUBMIT TWO COPIES OF THE |
| | PAGE(S) FROM THE INSTALLATION MANUAL THAT SHOWS AND |
| | LIST(S) THE REQUIRED DISTANCES FROM THE WATER HEATER TO |
| | THE DOORS AND WINDOWS. |
| | 3) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| | REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| | REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| | BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| | ON THE APPLICATION IN THE DESCRIPTION OF WORK AND ON |
| | THE PLANS. |
| | 4) IS THIS TANKLESS WATER HEATER BEING ADDED TO AN |
| | EXISTING GAS SYSTEM? IF SO, SUBMIT A COMPLETE GAS RISER |
| | SHOWING ALL GAS APPLIANCES CONNECTED TO THE SYSTEM |
| | ALONG WITH ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED |
| | LENGTH TO THE FURTHEST GAS OUTLET, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PSI OF THE SYSTEM, TYPE OF GAS AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. |
| | 5) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2, |
| | 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| | G2413.3. |
| | 6) A SEPARATE PERMIT IS REQUIRED FOR ANY ELECTRIC WORK |
| | THAT MAY NEED TO BE DONE, |
| | 7) A SEDIMENT TRAP IS REQD. ON THE GAS LINE TO THE |
| | WATER HEATER PER 2014 FBC-FUEL GAS 408.4, 2014 |
| | FBCR-SEC. G2419.4. |
| | 8) A SHUTOFF VALVE FOR THE APPLIANCE SHALL BE INSTALLED |
| | IN ACCORDANCE WITH 2014 FBCR SEC. G2420.5, 2014 |
| | FBC-FUEL GAS SEC.409.5. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |