Plan Review Details - Permit 17010227
Plan Review Stops For Permit 17010227
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-15 Cont ID  
Sent By jwitmer Date 2017-02-15 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2017-02-15 Time 15:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-03 Cont ID  
Sent By jwitmer Date 2017-02-03 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2017-02-03 Time 07:31 Sent To  
Notes
2017-02-03 08:02:32BUILDING PLAN REVIEW
 W. P. B. REVISION: 17010227
 W. P. B. PERMIT: 16080368
 ADD: 5800 CORPORATE WAY
 CONT: GEN-X CONSTRUCTION
 TEL: 561-963-4490
 E-MAIL: ????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 03/2017
 ACTION: DENIED
  
 1) SHEET M3 SHOWS A ROOF TOP UNIT, RCL STRUCTURAL
 ENGINEERING SUBMITTED STRUCTURAL CALCULATION FOR THE
 SECURING THE ROOF TOP RTU TO THE STRUCTURE BELOW. THE
 REPORT IS 8 OF 8 PAGES. WITHIN THE REPORT THE
 COVERSHEET AND PAGE 5 ARE SEALED. THIS REPORT DOES NOT
 COMPLY WITH:
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET. .
  
 2) SHEET 5 IS A DETAIL FOR THE RTU REINFORCING DETAIL
 AND TIE DOWN OF THE CURB TO THE ROOF DECK AND ANCHORING
 OF THE RTU TO THE CURB.
  
 2A) THE ANCHORING OF THE CURB TO THE ROOF TOP FRAMING
 MEMBERS IS A GENERIC DETAIL NOT A SITE SPECIFIC DETAIL
 SHOWING THE INSTALLATION TO A SPECIFIC TYPE OF DECK AND
 ROOF FRAMING MEMBER. THE TERM OR IS USED FOR VARIOUS
 TYPE OF ROOF FRAMING.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON THE CONSTRUCTION
 DRAWINGS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 2B) THE RTU REINFORCING DETAIL, L4X45/16 INCH ANGLES
 DOES NOT PROVIDE ANY TYPE OF INFORMATION HOW THE ENDS
 OF THE ANGLE IRON WERE TO BE CUT OR THE TYPE OF WELDS,
 AGAIN IT IS ASSUMED THE JOIST ARE BAR JOIST, THE PLANS
 INDICATE EXISTING JOIST, AGAIN THESE COULD BE WOOD
 JOIST? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. ,
 ADMINISTRATION 107.2.1 INFORMATION ON THE CONSTRUCTION
 DRAWINGS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC?
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-01-20 Cont ID  
Sent By jwitmer Date 2017-01-20 Time 17:26 Rev Time 0.00
Received By jwitmer Date 2017-01-20 Time 16:55 Sent To  
Notes
2017-01-20 16:59:29BUILDING PROVISO: RED LINED/ MISSING VERTICAL
 DIMENSION.
 SHEET # 10, COORIDOR SINK AND EMPLOYEES LOUNGE SINK:
 2014 FBC-ACCESSIBILITY CODE SECTION 606.3
 THE RIM OF A SINK OR COUNTER SURFACE TO BE A MAXIMUM OF
 34 INCHES ABOVE FINISH FLOOR.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-14 Cont ID  
Sent By rlecky Date 2017-02-14 Time 12:17 Rev Time 0.00
Received By rlecky Date 2017-02-14 Time 12:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-02-07 Cont ID  
Sent By rlecky Date 2017-02-07 Time 13:02 Rev Time 0.00
Received By rlecky Date 2017-02-07 Time 12:23 Sent To  
Notes
2017-02-07 13:07:12PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENT.
  
 FEEDER TO PANEL C IS UNDER SIZED BASED ON THE
 OVERCURRENT PROTECTION PROVIDED. NEC 240.4
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-17 Cont ID  
Sent By vperez Date 2017-01-17 Time 12:11 Rev Time 0.00
Received By rlecky Date 2017-01-17 Time 12:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-02-15 Cont ID  
Sent By wjolin Date 2017-02-15 Time 16:44 Rev Time 0.00
Received By wjolin Date 2017-02-15 Time 16:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-18 Cont ID  
Sent By pleduc Date 2017-01-18 Time   Rev Time 0.00
Received By pleduc Date 2017-01-18 Time 12:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-15 Cont ID  
Sent By ccole Date 2017-02-15 Time 16:41 Rev Time 0.00
Received By ccole Date 2017-02-10 Time 14:24 Sent To  
Notes
2017-02-13 14:24:13C20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-07 Cont ID  
Sent By rlecky Date 2017-02-07 Time 13:03 Rev Time 0.00
Received By rlecky Date 2017-02-02 Time 14:44 Sent To  
Notes
2017-02-02 14:44:52RESUB ROUTED TO RLECKY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-25 Cont ID  
Sent By ccole Date 2017-01-25 Time 11:07 Rev Time 0.00
Received By ccole Date 2017-01-09 Time 14:42 Sent To  
Notes
2017-01-09 14:42:18C17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-02-15 Cont ID  
Sent By ccole Date 2017-02-15 Time 16:34 Rev Time 0.00
Received By ccole Date 2017-02-15 Time 16:34 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-03 Cont ID  
Sent By ccole Date 2017-02-03 Time 08:32 Rev Time 0.00
Received By ccole Date 2017-02-03 Time 08:32 Sent To E
Notes
2017-02-03 08:35:242ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010227
 2/3/17
  
 1) THE REQUESTED WIND LOAD ENGINEERING FOR THE RTU
 INSTALLATIONS IS INCOMPLETE AND DEFICIENT. PLEASE
 REVIEW BUILDING COMMENTS AND RESUBMIT CORRECTED DETAILS
 AND SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By ccole Date 2017-01-25 Time 11:00 Rev Time 0.00
Received By ccole Date 2017-01-25 Time 10:27 Sent To  
Notes
2017-01-25 11:07:141ST REVIEW FBC-2014 MECHANICAL
 REVISION #17010227
 MASTER #16080368
 1/25/17
  
 1) ENGINEERING DETAILS ARE REQUIRED FOR THE NEW ROOF
 OPENINGS AND REINFORCEMENTS, AND FOR ATTACHMENT OF THE
 RTU'S AND CURBS- SECTION 301.15 FBC-14 MECHANICAL, AND
 SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  