Plan Review Details - Permit 17010175
Plan Review Stops For Permit 17010175
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-03-03 Cont ID  
Sent By jwitmer Date 2017-03-03 Time 16:04 Rev Time 0.00
Received By jwitmer Date 2017-03-03 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-22 Cont ID  
Sent By jwitmer Date 2017-02-22 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2017-02-22 Time 07:16 Sent To  
Notes
2017-02-22 08:59:30BUILDING PLAN REVIEW
 W. P. B. REVISION: 17010175
 W. P. B. PERMIT: 15100991/ WAWA CONVENIENCE STORE
 ADD: 1520 BELVEDERE RD.
 CONT: COMPREHENSIVE ENERGY SERVICES
 TEL: 407-682-1313
 E-MAIL: [email protected] /
 [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. FEB. 22/ 2017
 ACTION: DENIED
  
 NOTICE!!!!!! **** 4X FEE NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)****
  
  
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 2ND REQUEST! SUBMIT PLANS COLLATED INTO (2) PERMIT
 READY SETS OF PLANS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES.
 107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 PERMIT APPLICATION.
  
 2) DEFERRED SUBMITTAL. 107 3.4.2. COMPREHENSIVE ENERGY
 SERVICES HAS REQUESTED THAT THE PRE-ENGINEERED STAND TO
 BE SUBMITTED BY THE GENERAL CONTRACTOR UNDER SEPARATE
 COVER (A DIFFERENT SUBMITTAL TRACKING NUMBER) IT IS NOT
 PART OF THEIR PERMIT PACKAGE.
 THE FLORIDA APPROVAL FL#16921.1-R2 IS MISSING THE
 FLORIDA APPROVAL COVERSHEETS AND ONLY ONE APPROVAL WAS
 SUBMITTED. 107.1 GENERAL. SUBMITTAL DOCUMENTS
 CONSISTING OF CONSTRUCTION DOCUMENTS, STATEMENT OF
 SPECIAL INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 3) DEFERRED SUBMITTAL. 107 3.4.2. COMPREHENSIVE ENERGY
 SERVICES HAS REQUESTED THAT THE PRE-ENGINEERED STAND TO
 BE SUBMITTED BY THE GENERAL CONTRACTOR UNDER SEPARATE
 COVER (A DIFFERENT SUBMITTAL TRACKING NUMBER) IT IS NOT
 PART OF THEIR PERMIT PACKAGE.
 THE FLORIDA APPROVAL FL#16921.1-R2 HAS NOT BEEN
 REVIEWED, NEITHER THE CONTRACTOR NOR THE DESIGNER OF
 RECORD HAVE FOLLOWED THE PRODUCT APPROVAL IN
 CALCULATING THE AREA OF THE ROOF TOP COMPRESSORS, THE
 MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES , ANCHORS
 AND UPLIFT VERSES MOMENT.
  
 4) DEFERRED SUBMITTAL. 107 3.4.2. COMPREHENSIVE ENERGY
 SERVICES HAS REQUESTED THAT THE PRE-ENGINEERED STAND TO
 BE SUBMITTED BY THE GENERAL CONTRACTOR UNDER SEPARATE
 COVER (A DIFFERENT SUBMITTAL TRACKING NUMBER) IT IS NOT
 PART OF THEIR PERMIT PACKAGE.
 THE FLORIDA APPROVAL FL#16921.1-R2 HAS NOT BEEN
 REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD, NOR
 THEIR SHOP DRAWING STAMP OF APPROVAL APPLIED.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 5) COMPLIED. 2SETS OF PLANS SUBMITTED. NOTE (1) SET OF
 MASTER BUILT PLAN FOR ROOFTOP UNITS WAS SUPPLIED, (2)
 REQUIRED ADMINISTRATIVE CODE 107.1.
  
 6) 2ND REQUEST. THE ISSUE WITH THE DESIGN IS THE RISK
 CATEGORY ASSIGNED FOR THE BUILDING. THE PLANS INDICATE
 A RISK CATEGORY FOR THE BUILDING I WHICH IS FOR THE
 LOCATION 156 VULT CORRECT. IN THE 2014 FBC-B TABLE
 1604.5 CATEGORY I BUILDINGS ARE MINOR STORAGE
 FACILITIES, AGRICULTURAL FACILITIES, BARNS SILOS, ETC.
 OR SCREEN ENCLOSURES. THE RISK CATEGORY FOR THIS
 STRUCTURE IS A II PER 2014 FBC-B TABLE 1604.5 AND THE
 WIND SPEED IS 170 VULT (FIGURE 1609A). YOU ARE ALLOWED
 TO INTERPOLATE BETWEEN THE WIND SPEED LINES, BUT THE
 BUILDING IS A RISK CATEGORY II , TABLE 1604.5 2014
 FBC-B.
  
 1ST ROUND OF COMMENTS. MATER BUILT PLAN SUBMITTED
 INDICATES THE DESIGN IS FOR 165 VULT FOR THE ROOF TOP
 UNIT. SHEET S1 SHOWS AN VULT WIND SPEED OF 168, 3
 SECOND GUST FOR THE WIND SPEED AT THIS LOCATION.
  
 7) COMPLIED. FLORIDA P.E. SIGNED THE PLANS WITH FLORIDA
 SEAL
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLATE AND STAPLE INTO SETS OF PLANS . A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By jwitmer Date 2017-02-14 Time 07:48 Rev Time 0.00
Received By jwitmer Date 2017-02-14 Time 07:02 Sent To  
Notes
2017-02-14 07:48:49BUILDING PLAN REVIEW
 W. P. B. REVISION: 17020175
 W. P. B. PERMIT: 15100991/ WAWA CONVENIENCE STORE
 ADD: 1520 BELVEDERE RD.
 CONT: COMPREHENSIVE ENERGY SERVICES
 TEL: 407-682-1313
 E-MAIL: NO E-MAIL GIVEN/ [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. FEB. 14/ 2017
 ACTION: DENIED
  
 1) SUBMIT PLANS COLLATED INTO (2) PERMIT READY SETS OF
 PLANS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES.
 107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 PERMIT APPLICATION.
  
 2) THE FLORIDA APPROVAL FL#16921.1-R2 IS MISSING THE
 FLORIDA APPROVAL COVERSHEETS AND ONLY ONE APPROVAL WAS
 SUBMITTED. 107.1 GENERAL. SUBMITTAL DOCUMENTS
 CONSISTING OF CONSTRUCTION DOCUMENTS, STATEMENT OF
 SPECIAL INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 3) THE FLORIDA APPROVAL FL#16921.1-R2 HAS NOT BEEN
 REVIEWED, NEITHER THE CONTRACTOR NOR THE DESIGNER OF
 RECORD HAVE FOLLOWED THE PRODUCT APPROVAL IN
 CALCULATING THE AREA OF THE ROOF TOP COMPRESSORS, THE
 MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES , ANCHORS
 AND UPLIFT VERSES MOMENT.
  
 4) THE FLORIDA APPROVAL FL#16921.1-R2 HAS NOT BEEN
 REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD, NOR
 THEIR SHOP DRAWING STAMP OF APPROVAL APPLIED.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 5) NOTE (1) SET OF MASTER BUILT PLAN FOR ROOFTOP UNITS
 WAS SUPPLIED, (2) REQUIRED ADMINISTRATIVE CODE 107.1.
  
 6) MATER BUILT PLAN SUBMITTED INDICATES THE DESIGN IS
 FOR 165 VULT FOR THE ROOF TOP UNIT. SHEET 1 0F 1 SHOWS
 AN VULT WIND SPEED OF 168, 3 SECOND GUST FOR THE WIND
 SPEED AT THIS LOCATION.
  
  
  
  
  
  
  
  
 7) THE ENGINEER SHOWN ON THIS PLAN VIPIN TOLAT SHOWS
 WORK BEING COMPLETED UNDER A TEXAS P.E. NUMBER NOT A
 REGISTERED ENGINEER UNDER THE STATE OF FLORIDA. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002/ FLORIDA STATUTE
 471.003.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By skennedy Date 2017-03-01 Time 11:28 Sent To  
Notes
2017-03-01 11:28:26SENT TO CCOLE DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-22 Cont ID  
Sent By jwitmer Date 2017-02-22 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2017-02-17 Time 13:38 Sent To  
Notes
2017-02-21 13:38:17RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-13 Cont ID  
Sent By ccole Date 2017-02-13 Time 11:25 Rev Time 0.00
Received By ccole Date 2017-02-10 Time 08:27 Sent To  
Notes
2017-02-13 08:27:47CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-01 Cont ID  
Sent By ccole Date 2017-02-01 Time 09:09 Rev Time 0.00
Received By ccole Date 2017-01-06 Time 14:04 Sent To  
Notes
2017-01-06 14:05:09APP ONLY ROUTED TO HMOSER

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-03-02 Cont ID  
Sent By ccole Date 2017-03-02 Time 09:26 Rev Time 0.00
Received By ccole Date 2017-03-02 Time 09:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-02-21 Cont ID  
Sent By ccole Date 2017-02-21 Time 16:30 Rev Time 0.00
Received By ccole Date 2017-02-21 Time 16:30 Sent To B
Notes
2017-02-21 16:47:583RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17010175
 2/21/17
  
 1) AS PREVIOUSLY NOTED IN THE SECOND REVIEW, TWO COPIES
 OF THE PLANS AND SUBMITTALS ARE REQUIRED PER SECTION
 107.2.1 WPB AMENDMENTS. MISSING ARE DUPLICATE COPIES OF
 THE MASTERBILT POWER PLAN DRAWING #5687- REV- 002, AND
 THE SUBMITTAL FOR THE GLASS DOOR MERCHANDISERS.
  
 2) 2ND REQUEST FOR PLANS TO BE BOUND NEATLY TOGETHER IN
 TWO SEPARATE SETS.
  
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010175
 2/13/17
  
 1) THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT REQUIRES THAT ALL PLANS AND SPECIFICATIONS
 FOR PERMITING PURPOSES BE SUBMITTED IN DUPLICATE. THE
 CURRENT SUBMITTAL IS MISSING DUPLICATE COPIES OF THE
 MASTERBILT PLANS, THE ROOF STAND PLANS, AND THE FREEZER
 DOOR DETAILS. A) PLEASE SEPARATE THE PLANS AND
 SUBMITTALS INTO TWO DUPLICATE SETS AND PERMANENTLY BIND
 THE
  
 INDIVIDUAL PAGES OF THE MAIN PLAN FROM CTA, AND THE
 MASTERBILT PLAN.
  
 2) THE STRUCTURAL ENGINEERING PLAN FOR INSTALLATION OF
 THE ROOFTOP MASTERBILT UNIT SHALL BEAR THE SIGNATURE
 AND SEAL OF A FL. LICENSED PE.- SEE SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND FL.
 STATUTES 471.003.
  
 3) THE ENGINEER OF RECORD MUST CIRCLE, HIGHLIGHT, OR
 OTHWERWISE MARK ALL APPLICABLE DETAILS, ASSEMBLIES, AND
 DESIGN PRESSURES ETC. ON THE PRECISION ROOF STAND
 PRODUCT APPROVAL. AS NOTED IN COMMENT #1 TWO COMPLETE
 COPIES ARE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-13 Cont ID  
Sent By ccole Date 2017-02-13 Time 10:36 Rev Time 0.00
Received By ccole Date 2017-02-13 Time 10:36 Sent To  
Notes
2017-02-13 11:24:532ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010175
 2/13/17
  
 1) THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT REQUIRES THAT ALL PLANS AND SPECIFICATIONS
 FOR PERMITING PURPOSES BE SUBMITTED IN DUPLICATE. THE
 CURRENT SUBMITTAL IS MISSING DUPLICATE COPIES OF THE
 MASTERBILT PLANS, THE ROOF STAND PLANS, AND THE FREEZER
 DOOR DETAILS. A) PLEASE SEPARATE THE PLANS AND
 SUBMITTALS INTO TWO DUPLICATE SETS AND PERMANENTLY BIND
 THE
  
 INDIVIDUAL PAGES OF THE MAIN PLAN FROM CTA, AND THE
 MASTERBILT PLAN.
  
 2) THE STRUCTURAL ENGINEERING PLAN FOR INSTALLATION OF
 THE ROOFTOP MASTERBILT UNIT SHALL BEAR THE SIGNATURE
 AND SEAL OF A FL. LICENSED PE.- SEE SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND FL.
 STATUTES 471.003.
  
 3) THE ENGINEER OF RECORD MUST CIRCLE, HIGHLIGHT, OR
 OTHWERWISE MARK ALL APPLICABLE DETAILS, ASSEMBLIES, AND
 DESIGN PRESSURES ETC. ON THE PRECISION ROOF STAND
 PRODUCT APPROVAL. AS NOTED IN COMMENT #1 TWO COMPLETE
 COPIES ARE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By ccole Date 2017-02-01 Time 09:09 Rev Time 0.00
Received By ccole Date 2017-02-01 Time 09:09 Sent To  
Notes
2017-02-01 09:12:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010175
 2/1/17
  
 1) NO PLANS OR SPECIFICATIONS SUBMITTED. PLEASE PROVIDE
 COMPLETE REFIREGRATION PLANS AND SPECIFICATIONS.
 INCLUDE EQUIPMENT SCHEDULES, FLOOR PLAN LAYOUT,
 REFRIGERATION PIPING CIRCUIT RUNS AND DETAILS, ROOFTOP
 EQUIPMENT TIE DOWN ENGINEERING ETC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  