| Plan Review Stops For Permit 17010157 |
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2017-02-20 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2017-02-20 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2017-02-20 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-03-14 |
|
|
Cont ID |
|
| Sent By |
fstal |
Date |
2017-03-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
fstal |
Date |
2017-03-14 |
Time |
|
Sent To |
M |
|
| Notes |
| 2017-03-14 09:31:46 | NFPA 14-6.4, 2012 FIRE DEPARTMENT CONNECTIONS. SHALL BE | | | LOCATED NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST | | | FIRE HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. | | | 6.4.5.4.1 THE LOCATION OF THE FIRE DEPARTMENT | | | CONNECTION SHALL BE PERMITTED TO EXCEED 100 FT (30.5 M) | | | SUBJECT TO THE APPROVAL OF THE AUTHORITY HAVING | | | JURISDICTION. | | | | | | FIRE PUMP INTALLATION SHALL COME IN COMPLIANCE WITH | | | NFPA 20. | | | | | | NFPA 72-5.15 SUPERVISORY SIGNAL-INITIATING DEVICES: | | | 5.15.1 CONTROL VALVE SUPERVISORY SIGNAL-INITIATING | | | DEVICE. 5.15.1.1 TWO SEPARATE AND DISTINCT SIGNALS | | | SHALL BE INITIATED: ONE INDICATING MOVEMENT OF THE | | | VALVE FROM ITS NORMAL POSITION (OFF-NORMAL) AND THE | | | OTHER INDICATING RESTORATION OF THE VALVE TO ITS NORMAL | | | POSITION. | | | | | | 5.15.1.2 THE OFF-NORMAL SIGNAL SHALL BE INITIATED | | | DURING THE FIRST TWO REVOLUTIONS OF THE HAND WHEEL OR | | | DURING ONE-FIFTH OF THE TRAVEL DISTANCE OF THE VALVE | | | CONTROL APPARATUS FROM ITS NORMAL POSITION. 5.15.1.3 | | | THE OFF-NORMAL SIGNAL SHALL NOT BE RESTORED AT ANY | | | VALVE POSITION EXCEPT NORMAL. 5.15.1.4 AN INITIATING | | | DEVICE FOR SUPERVISING THE POSITION OF A CONTROL VALVE | | | SHALL NOT INTERFERE WITH THE OPERATION OF THE VALVE, | | | OBSTRUCT THE VIEW OF ITS INDICATOR, OR PREVENT ACCESS | | | FOR VALVE MAINTENANCE. | | | | | | FRANK STALLWORTH, FIRE INSPECTOR I | | | WEST PALM BEACH FIRE PREVENTION BUREAU | | | 500 N. DIXIE HWY | | | WEST PALM BEACH, FLORIDA 33401 | | | OFFFICE: 561-840-4780 | | | FAX: 561-840-4774 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2017-03-06 |
|
|
Cont ID |
|
| Sent By |
fstal |
Date |
2017-03-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
fstal |
Date |
2017-03-06 |
Time |
09:01 |
Sent To |
M |
|
| Notes |
| 2017-03-06 08:59:08 | 03/06/2017: PROVIDE FIRE SPRINKLER PROTECTION IN | | | KITCHENS. NOTE: SEE HIGHLIGHTED SECTION ON PAGE 3,4. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-01-12 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-02-21 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
fstal |
Date |
2017-01-09 |
Time |
12:48 |
Sent To |
M |
|
| Notes |
| 2017-01-12 08:52:18 | PROVIDE FIRE SPRINKLER PROTECTION IN KITCHENS. PAGE | | | 3,4. | | | | | | FRANK STALLWORTH, FIRE INSPECTOR I | | | WEST PALM BEACH FIRE PREVENTION BUREAU | | | 500 N. DIXIE HWY | | | WEST PALM BEACH, FLORIDA 33401 | | | OFFFICE: 561-840-4780 | | | FAX: 561-840-4774 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-03-23 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-03-23 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-03-09 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2017-03-09 15:36:24 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-03-09 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-03-09 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-02-28 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2017-03-01 15:04:44 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-02-21 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-02-21 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-01-06 |
Time |
11:40 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-03-23 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-03-23 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-03-23 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-03-08 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2017-03-08 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2017-03-08 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2017-03-08 16:22:10 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | (1) SPRINKLER HEADS MISSING IN KITCHENS (AS WAS POINTED | | | OUT ON LAST REVIEW) | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-01-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-01-24 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-01-24 |
Time |
13:40 |
Sent To |
ENG |
|
| Notes |
| 2017-01-24 13:50:38 | PLAN DENIED | | | 1) MISSING SPRINKLER IN KITCHENS | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|