Plan Review Details - Permit 17010126
Plan Review Stops For Permit 17010126
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-05-31 Cont ID  
Sent By jwitmer Date 2017-05-31 Time 07:55 Rev Time 0.00
Received By jwitmer Date 2017-05-31 Time 07:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-04 Cont ID  
Sent By jwitmer Date 2017-04-04 Time 11:08 Rev Time 0.00
Received By jwitmer Date 2017-04-04 Time 10:32 Sent To  
Notes
2017-04-04 11:08:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010126
 ADD: 3199 CUMBERLAND DRIVE
 CONT: J. COMPTON ELECTRIC, INC.
 TEL: 561-588-6559
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 04/2017
 ACTION: DENIED
  
 1-4) COMPLIED.
  
 5) 2ND REQUEST. SHEET C-2 AND OTHER SHEETS SHOWING AN
 ELEVATION. THROUGHOUT THE SET OF PLANS ELEVATION IS
 GIVEN IN THE TERMS NAVD 88. THE CITY AND ALL FLOOD MAPS
 ADOPTED ARE STILL USING NGVD 29 PLEASE CORRECT
 ELEVATIONS, OR SHOW THE EQUIVALENCY IN NGVD. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6-7) COMPLIED.
  
 8) SEMI- COMPLIED. THIS REVIEW A SOILS REPORT WAS
 SUBMITTED. IN BOTH SETS OF THE SOILS REPORTS ON PAGE 03
 THE SIGNATURES ARE COPIES (SIGNATURES ARE PIXILATED,
 NOT AN ORIGINAL INK SIGNATURE)AND THE PAGE IS NOT
 SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002 ENGINEERS.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-23 Cont ID  
Sent By jwitmer Date 2017-01-23 Time 09:33 Rev Time  
Received By jwitmer Date 2017-01-23 Time 07:28 Sent To  
Notes
2017-01-23 09:33:02BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010126
 ADD: 3199 CUMBERLAND DRIVE
 CONT: J. COMPTON ELECTRIC, INC.
 TEL: 561-588-6559
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 23/2017
 ACTION: DENIED
  
 1) COMPLIED. CONCRETE PAD AND TELELECTRONIC EQUIPMENT
 RACKS.
  
 2) THE WIND DESIGN CRITERIA SHOWS THIS BUILDING IS 160
 MPH. PLEASE REFER TO TABLE 1604.5 RISK CATEGORY OF
 BUILDINGS AND OTHER STRUCTURES. THE BUILDING RISK
 CATEGORY INDICATED ON THE PLANS IS RISK CATEGORY II
 WITH A 170 VULT WIND DESIGN, THIS STRUCTURE IS NOT
 AGRICULTURAL OUT BUILDING NOT A TEMPORARY FACILITY,
 MINOR STORAGE FACILITY NOR SCREEN ENCLOSURE. AFTER THE
 2004 & 2005 HURRICANES WE WERE REQUIRING THE CELL
 TOWERS TO BE CLASSIFIED AS A RISK CATEGORY III. THROUGH
 THE APPLICANT A LETTER CAME BACK FROM THE STATE THAT
 THE CELL TOWERS AND ASSOCIATED EQUIPMENT WAS TO BE
 INTERPRETED AS A RISK CATEGORY II NOT AN III. PLEASE
 CORRECT THE WIND SPEED.
  
 3) SHEET C-6 SHOWS AN ANCHORING DETAIL. THIS DETAIL
 WILL NEED TO BE RE-EVALUATED FOR A 170 VULT MPH WIND
 SPEED. TABLE 1604.5 AND FIGURE 1609 A RISK CATEGORY II
 BUILDINGS.
  
 4) SHEET C-5 THE ATTENDANT UTILITIES PROPANE GAS TANK
 AND METAL GENERATOR ENCLOSURE SHOW ANCHORING DETAILS
 BUT THERE IS NO WIND DESIGN AS TO WHAT WIND SPEED. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 5) SHEET C-2 AND OTHER SHEETS SHOWING AN ELEVATION.
 THROUGHOUT THE SET OF PLANS ELEVATION IS GIVEN IN THE
 TERMS NAVD 88. THE CITY AND ALL FLOOD MAPS ADOPTED ARE
 STILL USING NGVD 29 PLEASE CORRECT ELEVATIONS, OR SHOW
 THE EQUIVALENCY IN NGVD. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 6) REPORT TRANSMISSION LINE PROJECT T00000016270 BY
 JASON TRUCKENBROD, P. E. IS A COPY OF SIGNATURE AND
 SEAL.
 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS
 MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1,
 2006.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS
 AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY
 THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 7) REPORT TRANSMISSION LINE PROJECT T00000016270
 INDICATES ATTACHED FOUNDATION REPORT FOR CALCULATIONS
 OF THE REQUIRED SET DEPTH AND BACKFILL. NO SUCH
 CALCULATIONS ARE FOUND IN REPORT, NOTE TO BE SIGNED AND
 SEALED BY THE ENGINEER OF CALCULATIONS. 61G15-23.002(2)
 FL. ADMIN. CODE. A COVER SHEET OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION
 & PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
 8) PLEASE INDICATE HOW THE FOUNDATION DESIGN WAS
 DERIVED WITHOUT A SOILS REPORT? 1803.5.2 QUESTIONABLE
 SOIL.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-19 Cont ID  
Sent By rlecky Date 2017-01-19 Time 11:22 Rev Time 0.00
Received By rlecky Date 2017-01-17 Time 14:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-06-13 Cont ID  
Sent By tklarge Date 2017-06-13 Time 10:55 Rev Time 0.00
Received By tklarge Date 2017-06-13 Time 10:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 18:17 Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 18:17 Sent To  
Notes
2017-05-24 18:16:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: HAS NOT COMPLIED 2ND REQUEST
  
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 58, AND FBC-2014 FUEL
 GAS CODE SEC. 402.2, AND 301.3. GAS APPLIANCES SHALL BE
 LISTED AND LABELED. THE INSTALLATION MANUALS FOR ALL
 GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME
 OF INSPECTION. FGC SEC.305.1,
  
 3) SHOW THE METHOD OF REQUIRED PROTECTION FOR THE LP
 TANK AND APPURTENANCES PER NFPA 58.
  
 5) STATIONARY ENGINE GENERATOR ASSEMBLIES SHALL MEET
 THE REQUIREMENTS OF UL 2200 AND NFPA 37.. SUBMIT MANUF.
 SPECIFICATIONS FOR REVIEW. 2014 FGC SEC.616.1.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-09 Cont ID  
Sent By tklarge Date 2017-05-09 Time 12:15 Rev Time 0.00
Received By tklarge Date 2017-05-09 Time 12:15 Sent To  
Notes
2017-05-09 10:24:331) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 58, AND FBC-2014 FUEL
 GAS CODE SEC. 402.2, AND 301.3. GAS APPLIANCES SHALL BE
 LISTED AND LABELED. THE INSTALLATION MANUALS FOR ALL
 GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME
 OF INSPECTION. FGC SEC.305.1,
 2) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
 3) SHOW THE METHOD OF REQUIRED PROTECTION FOR THE LP
 TANK AND APPURTENANCES PER NFPA 58.
 4) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3.
 5) STATIONARY ENGINE GENERATOR ASSEMBLIES SHALL MEET
 THE REQUIREMENTS OF UL 2200 AND NFPA 37.. SUBMIT MANUF.
 SPECIFICATIONS FOR REVIEW. 2014 FGC SEC.616.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-06-13 Cont ID  
Sent By tklarge Date 2017-06-13 Time 10:55 Rev Time 0.00
Received By tklarge Date 2017-06-13 Time 10:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-05-31 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-19 Time 14:02 Sent To  
Notes
2017-05-22 14:02:17C17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-09 Cont ID  
Sent By tklarge Date 2017-05-09 Time 12:16 Rev Time 0.00
Received By tklarge Date 2017-03-29 Time 09:55 Sent To  
Notes
2017-03-31 09:55:42C13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-20 Cont ID  
Sent By skennedy Date 2017-03-20 Time 13:20 Rev Time 0.00
Received By skennedy Date 2017-01-06 Time 11:31 Sent To  
Notes
2017-01-09 11:33:06C13

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2017-03-20 Cont ID  
Sent By skennedy Date 2017-03-20 Time 13:19 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2017-03-20 13:20:18SEPARATE PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-13 Cont ID  
Sent By tklarge Date 2017-06-13 Time 10:20 Rev Time 0.00
Received By tklarge Date 2017-06-13 Time 10:20 Sent To  
Notes
2017-06-13 10:22:27CONNECTION TO EXISTING IRRIGATION SYSTEM. BFP DEVICE
 NOT REQD.

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 18:13 Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 18:13 Sent To  
Notes
2017-05-24 18:14:151ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: NOT COMPLIED 2ND REQUEST.
  
 A RAIN SENSOR AND CONTROLLER IS REQUIRED ON THE
 IRRIGATION SYSTEM PER FL. STATUTE 373.62.
 2) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 WATER SUPPLY TO THE IRRIGATION SYSTEM PER THE CITY OF
 WPB CROSS- CONNECTION CONTROL MANUAL & 2014
 FBC-PLUMBING SEC.608.16.5.
 3) THE BACKFLOW DEVICE SHALL BE LEAD FREE AND A
 SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW DEVICE.
 2014 FBC-PLUMBING SEC.605.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-09 Cont ID  
Sent By tklarge Date 2017-05-09 Time 12:32 Rev Time 0.00
Received By tklarge Date 2017-05-09 Time 12:27 Sent To  
Notes
2017-05-09 12:32:02A RAIN SENSOR AND CONTROLLER IS REQUIRED ON THE
 IRRIGATION SYSTEM PER FL. STATUTE 373.62.
 2) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 WATER SUPPLY TO THE IRRIGATION SYSTEM PER THE CITY OF
 WPB CROSS- CONNECTION CONTROL MANUAL & 2014
 FBC-PLUMBING SEC.608.16.5.
 3) THE BACKFLOW DEVICE SHALL BE LEAD FREE AND A
 SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW DEVICE.
 2014 FBC-PLUMBING SEC.605.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-05-30 Cont ID  
Sent By awooten Date 2017-05-30 Time 10:26 Rev Time 0.00
Received By awooten Date 2017-05-30 Time   Sent To  
Notes
2017-05-30 10:26:06************************ZONING*************************
 ******
  
 THE FOLLOWING CONDITIONS, APPLY TO THIS APPROVAL:
  
 1.) ALL EQUIPMENT/MOUNTING BRACKETS EXPOSED TO VIEW AT
 GROUND LEVEL SHALL BE COLOR MATCHED TO THE EXISTING
 BUILDING/FACADE. NO EQUIPMENT LOGOS SHALL BE VISIBLE.
  
 2.) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 COMPLETION FOR THE ANTENNA AND ENCLOSURE, LANDSCAPING
 ADJACENT TO THE ENCLOSURE WALL SHALL BE PERMITTED AND
 INSTALLED PER THE LANDSCAPE PLAN APPROVED FOR THE SITE.
  
 PLEASE CONTACT ME WITH ANY QUESTIONS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT
 PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1449 | F: 561.822.1449 | E: [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-04-06 Time   Rev Time 0.00
Received By   Date 2017-04-06 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-01-13 Cont ID  
Sent By awooten Date 2017-01-13 Time 16:15 Rev Time 0.00
Received By awooten Date 2017-01-13 Time 15:54 Sent To  
Notes
2017-01-13 16:14:57************************ZONING*************************
 ******
  
 THE FOLLOWING CONDITIONS, APPLY TO THIS APPROVAL:
  
 1.) ALL EQUIPMENT/MOUNTING BRACKETS EXPOSED TO VIEW AT
 GROUND LEVEL SHALL BE COLOR MATCHED TO THE EXISTING
 BUILDING/FA?ADE. NO EQUIPMENT LOGOS SHALL BE VISIBLE.
  
 2.) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 COMPLETION FOR THE ANTENNA AND ENCLOSURE, LANDSCAPING
 ADJACENT TO THE ENCLOSURE WALL SHALL BE PERMITTED AND
 INSTALLED PER THE LANDSCAPE PLAN APPROVED FOR THE SITE.
  
 PLEASE CONTACT ME WITH ANY QUESTIONS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT
 PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1449 | F: 561.822.1449 | E: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved