Plan Review Details - Permit 17010106
Plan Review Stops For Permit 17010106
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-28 Cont ID  
Sent By jwitmer Date 2017-02-28 Time 13:58 Rev Time 0.00
Received By jwitmer Date 2017-02-28 Time 13:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-11 Cont ID  
Sent By jwitmer Date 2017-01-11 Time 10:11 Rev Time  
Received By jwitmer Date 2017-01-11 Time 07:54 Sent To  
Notes
2017-01-11 10:11:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010106
 ADD: 901 45TH ST. / X-RAY ROOM- T1093
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 11/ 2017
 ACTION: DENIED
  
 1) THE ARCHITECTURAL SHEETS IN ALL (3) SETS HAVE BEEN
 SEALED WITH AN IMPRESSION TYPE SEAL SO LIGHT THAT MANY
 OF THE SHEETS THE AUTHENTICITY OF THE SEAL CANNOT BE
 DETERMINED BY NAME OR REGISTRATION NUMBER.
 FLORIDA STATUTE 481.221?SEALS; DISPLAY OF CERTIFICATE
 NUMBER. THE SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE
 OF THE AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED.
  
 2) THE STRUCTURAL SHEETS S1 & S2 ARE CREATED BY GE
 HEALTHCARE IMPLEMENTATION ? DESIGN CENTER. WHILE THE
 NAME OF THE COMPANY DOES NOT STATE ?ENGINEERING? USING
 THE NAMING CONVENTION DESIGN CENTER AND THE NOTES ON
 THE SHEET IT SUGGEST THERE IS OR WAS ENGINEERING
 COMPLETED TO KNOW WHAT POUNDAGE EACH OF THE ANCHORS HAS
 TO HOLD (NOTE # 2). THE SHEET S1 NOR S2 SHOW HOW THE
 LOADS WERE CALCULATED AS EITHER 1607.3 UNIFORM LIVE
 LOADS, OR 1607.4 CONCENTRATED LIVE LOADS. 1607.2 LOADS
 NOT SPECIFIED. FOR OCCUPANCIES OR USES NOT DESIGNATED
 IN TABLE 1607.1, THE LIVE LOAD SHALL BE DETERMINED IN
 ACCORDANCE WITH A METHOD APPROVED BY THE BUILDING
 OFFICIAL.
 1607.9.2 MACHINERY. FOR THE PURPOSE OF DESIGN, THE
 WEIGHT OF MACHINERY AND MOVING LOADS SHALL BE INCREASED
 AS FOLLOWS TO ALLOW FOR IMPACT: (1) LIGHT MACHINERY,
 SHAFT OR MOTOR-DRIVEN, 20 PERCENT; AND (2)
 RECIPROCATING MACHINERY OR POWER-DRIVEN UNITS, 50
 PERCENT. PERCENTAGES SHALL BE INCREASED WHERE SPECIFIED
 BY THE MANUFACTURER.
  
 NOTE # 2 GOES ON TO STATE NOT TO USE SCREW ANCHORS IN
 DIRECT TENSION.
  
 THE STRUCTURAL SHEETS S1 & S2 WHO IS TAKING THE
 RESPONSIBILITY THE DESIGN, THERE IS NO DESIGN
 PROFESSIONAL WHO TAKES THE RESPONSIBILITY FOR THE
 DESIGN, THERE IS NO ENGINEERING SHOWING HOW THE DESIGN
 OF 350 LBS. EVERY 2 FOOT 2 INCHES? FLORIDA STATUTES 471
 ENGINEERING & 481 ARCHITECTURE.
  
 IN THE ANCHORS BEING CAPABLE OF WITHSTANDING 350 LBS.
 THERE IS A SAFETY FACTOR THAT IS NOT KNOWN NOR IS THERE
 ANY REFERENCES TO STANDARDS, CODE SECTIONS TO EITHER
 THE
  
 THIS SHEET SHOULD EITHER BE DESIGNED BY AN ENGINEER, OR
 A DELEGATE ENGINEER AND REVIEWED BY THE FLORIDA
 ENGINEER OF RECORD OR BE BROUGHT IN AS A SHOP DRAWING
 TO BE REVIEWED BY THE ARCHITECT OF RECORD AND THEIR
 SHOP DRAWING STAMP OF APPROVAL AFFIXED TO THE PLAN. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-28 Cont ID  
Sent By vperez Date 2017-02-28 Time 08:30 Rev Time 0.00
Received By vperez Date 2017-02-28 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-17 Cont ID  
Sent By rlecky Date 2017-01-17 Time 11:32 Rev Time 0.00
Received By rlecky Date 2017-01-17 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-01 Cont ID  
Sent By pleduc Date 2017-03-01 Time   Rev Time 0.00
Received By pleduc Date 2017-03-01 Time 13:51 Sent To PC
Notes
2017-03-01 14:38:41THE PREVIOUS PROVISO COMMENTS REMAIN APPLICABLE TO THIS
 REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-09 Cont ID  
Sent By pleduc Date 2017-01-09 Time   Rev Time 0.00
Received By pleduc Date 2017-01-09 Time 11:12 Sent To  
Notes
2017-01-09 11:54:45THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET LS 1 - THERE IS AN INCORRECT REFERENCE TO THE
 APPLICABLE EDITION OF THE CURRENT FIRE CODE. IN NOTE
 BOX "CLASSIFICATION OF HAZARDOUS CONTENTS" IT IS
 INDICATED FFPC 2010 AND NFPA 101 2009.
  
 THE CURRENT EDITION OF THE FFPC INCLUDING NFPA 1 & 101
 IS 2012. THIS DOES APPEAR TO NEGATIVELY AFFECT YOUR
 SUBMITTAL.
  
 PLEASE ENSURE COMPLIANCE AND UPDATE YOUR RECORDS FOR
 FUTURE SUBMITTALS.
  
  
  
 2) SHEET LS 1 & E 2.01 - THE LIFE SAFETY SYSTEMS, FIRE
 ALARM AND/OR FIRE SPRINKLER SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2017-03-01 Cont ID  
Sent By pleduc Date 2017-03-01 Time   Rev Time 0.00
Received By pleduc Date 2017-02-21 Time 15:09 Sent To  
Notes
2017-02-22 15:09:35B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-25 Cont ID  
Sent By ccole Date 2017-01-25 Time 07:54 Rev Time 0.00
Received By ccole Date 2017-01-05 Time 15:10 Sent To  
Notes
2017-01-06 15:10:17B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-11 Cont ID  
Sent By jwitmer Date 2017-01-11 Time 07:55 Rev Time  
Received By jwitmer Date 2017-01-11 Time 07:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-02-28 Cont ID  
Sent By ccole Date 2017-02-28 Time 17:21 Rev Time 0.00
Received By ccole Date 2017-02-28 Time 17:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By ccole Date 2017-01-25 Time 07:54 Rev Time 0.00
Received By ccole Date 2017-01-25 Time 07:54 Sent To  
Notes
2017-01-25 08:00:051ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010106
 1/25/17
  
 1) SHEET M0.00: THE PROJECT DESIGN CRITERIA IS
 SPECIFIYING MIAMI, FL.: PLEASE CORRECT.
  
 2) REFER TO TABLE 7-1 ASHRAE 170 AND PROVIDE THE AIR
 DESIGN PARAMETERS FOR THE RADIOLOGY ROOM AND ADJOINING
 ROOMS AND SPACES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  