Plan Review Details - Permit 17010099
Plan Review Stops For Permit 17010099
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-17 Cont ID  
Sent By jwitmer Date 2017-04-17 Time 12:05 Rev Time 0.00
Received By jwitmer Date 2017-04-17 Time 07:57 Sent To  
Notes
2017-04-17 12:29:40BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010099
 ADD: 1111 S. FLAGLER DR.
 CONT: MYRICK GUROSKY & ASS.
 TEL: 205-313-3027
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. APRIL 17/ 2017
  
 ACTION: BUILDING PROVISO:
  
 1A) BUILDING PROVISO- 107.3.4.2 DEFERRED SUBMITTALS:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 1B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-18 Cont ID  
Sent By jwitmer Date 2017-01-18 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2017-01-13 Time 11:17 Sent To  
Notes
2017-01-18 13:41:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010099
 ADD: 1111 S. FLAGLER DR.
 CONT: MYRICK GUROSKY & ASS.
 TEL: 205-313-3027
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 13/ 2017
 ACTION: DENIED
  
 1) SHEET T101:
 1A) THE TITLESHEET T101 UNDER THE HEADING OF ADOPTED
 CODES WILL NEED TO UPDATE THE DESIGN OF THE PLANS TO
 THE CURRENT ADOPTED FAMILY OF CODES. STATEWIDE ON JUNE
 30/2015 THE 5TH EDITION OF THE FLORIDA BUILDING CODE
 (2014) WAS ADOPTED. JULY 1/2016 THE 2016 SUPPLEMENTS OF
 THE FLORIDA BUILDING CODE WERE ALSO ADOPTED STATEWIDE.
 PLEASE CORRECT THE CODE ANALYSIS AND PLANS ACCORDINGLY.
  
 1B) THE ARCHITECTURAL, (IN) INTERIOR SECTIONS NOR THE
 STRUCTURAL SHEETS PROVIDE THE ADDRESS WITHIN THE
 TITLEBLOCK. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS . CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROPOSED WORK.
  
 2) IN THIS PERMIT SUBMITTAL THERE ARE NO LIFE SAFETY
 PLANS FOR THE 1ST NOR 2ND FLOOR. SHEET A101 AND A102
 THE 1ST AND 2ND STORY FLOOR PLANS SHOW A FLOOR LAYOUT
 BUT NO LIFE SAFETY INFORMATION.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING (7) OCCUPANCY LOAD/EGRESS
 REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DEAD END CORRIDORS
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 2A) ROOMS # 1,2 & 3 ALL ARE ASSEMBLY USE ROOMS WITH
 OCCUPANT LOADS 50 OR MORE OCCUPANTS. TO THE NORTH OF
 THESE ROOMS THERE IS A SERVICE HALL. NOTE THERE ARE
 DOORWAYS THAT LEAD OUT OF THESE ROOMS INTO THE SERVICE
 HALL AND THEN TO THE EXTERIOR OF THE BUILDING. THERE IS
 NO INFORMATION AS TO WHERE THE EXIT DISCHARGE LEADS YOU
 IF THE DOOR OPENINGS ON THE NORTH SIDE OF THE 3
 ASSEMBLY ROOMS ARE TO BE CONSIDERED THE 2ND MEANS OF
 EGRESS. SEE FBC-B TABLE 1015.1. THE NAMING OF THIS
 SPACE A SERVICE HALL LEADS ONE TO THINK THIS MAY END UP
 AS A STORAGE ROOM FOR TABLES AND CHAIRS SEE FBC-B
 1014.2.(4) EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
  
 2B)(1) SHEET A101 DETAIL # 2 INDICATES A PLATFORM PLAN.
 PLEASE INDICATE THE USAGE OF THIS AREA. PLATFORMS ARE
 ASSOCIATED WITH EQUIPMENT AND OR MACHINERY SUCH AS AIR
 CONDITIONING UNITS? 2014 FBC-B 505.3 EQUIPMENT
 PLATFORMS.
  
 2B)(2) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF
 THE PLATFORM OVER THE PANTRY. WITHIN THIS DETAIL THE
 LIVE LOAD DESIGN IS 125 LBS./ PSF WHICH IS THE DESIGN
 LOADS USED FOR STORAGE FOR LIGHT LOADS SEE FBC-B TABLE
 1607.1. IT WOULD APPEAR THE FLOOR LOADING IS BEING
 DESIGNED FOR A MEZZANINE USAGE LIGHT STORAGE WHEREAS
 THE LOADING INDICATED IN TABLE 1607.1 FOR ELEVATED
 PLATFORMS IS 60LBS./ PSF. ADDITIONAL INFORMATION IS
 REQUIRED 107.2.1.3.
  
 2C) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF THE
 PLATFORM OVER THE PANTRY. THE PLANS DO NOT INDICATE IF
 THE OTHER SIDE OF THE PLATFORM WILL HAVE THE SAME
 VERTICAL FRAMING & FASTENING PATTERN. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2D) SHEET S-102 DETAIL # 2 SHOWS THE FLOOR FRAMING
 MEMBERS TO BE 10 INCH STEEL STUD FRAMING AT 16 INCHES
 ON CENTER. PLEASE REVIEW SHEET S-101 UNDER THE HEADING
 5.0 STEEL DECK SEE NOTES 5.2 THE FLOOR FRAMING IS TO BE
 LIGHT GAGE STEEL STUD FLOOR JOIST @ 1 FOOT O/C AT ALL
 SUPPORTS. DISCREPANCY IN PLANS 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THE VERTICAL WALL STEEL STUDS
 ARE AT 16 INCHES ON CENTER, THE COMMENT ABOVE (2C) THE
 ATTACHMENT METHOD OF THE HORIZONTAL TO VERTICAL STUDS
 WILL NOT LINE UP, NEW DETAIL WOULD BE REQUIRED. ALSO
 SEE SHEET S201 SHOWS THE FLOOR FRAMING @ 16 INCHES ON
 CENTER?
  
 2E) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF THE
 PLATFORM OVER THE PANTRY. NOTE ON THIS DETAIL INDICATES
 THE FINAL DESIGN IS TO BE PROVIDED BY THE COLD STEEL
 FRAMING MANUFACTURER. IF THE DESIGN BY THE COLD STEEL
 FRAMING MANUFACTURER IS COMPLETED BY A DELEGATE
 ENGINEER THEN SHOW COMPLIANCE WITH:
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 2F) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF THE
 PLATFORM OVER THE PANTRY. IF THE PLATFORM IS ACTUALLY A
 STORAGE MEZZANINE THEN SHOW COMPLIANCE WITH 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION:
  
 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH
 EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH
 DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE
 OWNER IN THAT PART OF EACH STORY IN WHICH THEY
 APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO
 REMOVE OR DEFACE SUCH NOTICES.
  
 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111
 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS,
 REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO
 PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON
 ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION
 THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS
 CODE.
  
 2G) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF THE
 PLATFORM OVER THE PANTRY AND FOR ACCESS THE USE OF A
 SHIPS LADDER. PLEASE PROVIDE WHERE THE CODE ALLOWS FOR
 THE USE OF A SHIPS LADDER. 2014 FBC-B 1009.14 SHIPS
 LADDERS.
  
 3) SHEET D101 SHOWS THE DEMOLITION OF PORTIONS OF
 EXTERIOR CMU WALLS FOR NEW DOUBLE DOOR OPENINGS. ON
 SHEET S102 THERE IS A LINTEL SCHEDULE BUT NO SECTIONS
 SHOWING HOW THE NEW COLUMNS/ REBAR AND LINTELS ARE TO
 ATTACH TO THE FOOTERS NOR THE BEAM ABOVE TO CREATE A
 CONTINUOUS LOAD PATH AND BE PART OF THE MWFRS (MAIN
 WIND FORCE RESISTING SYSTEM). SHEET S102 SHOWS A SERIES
 OF DETAILS WITH ANGLES ACTING AS SUPPORT AT THE NEW
 DOOR OPENING BUT NO MENTION OF COLUMNS BEING ELIMINATED
 OR NOT. NO MENTION OF HOW THE BRICK VENEER ARE TO BE
 SUPPORTED BY STEEL ANGLE IRON SEE A201.
 IF MASONRY: 2104.1 MASONRY CONSTRUCTION. MASONRY
 CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTIONS 2104.1.1 THROUGH 2104.4 AND WITH TMS 602/ACI
 530.1/ASCE 6.
 IF COLUMNS ARE CONCRETE THEN: FBC-B 1901.2 REINFORCED
 CONCRETE.
  
 4) SHEETS A101, A201 & A301 ALL SHOW NEW EXTERIOR OR
 REPLACED WINDOWS AND DOORS. NEITHER THE ARCHITECTURAL
 SHEETS NOR THE STRUCTURAL SHEETS SHOW THE WIND DESIGN
 CRITERIA AND ASSOCIATED PRESSURES.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) PLEASE PROVIDE DOCUMENTS INDICATING COMPLIANCE WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) PLEASE SHOW COMPLIANCE WITH : 2014 FBC-ENERGY CODE
 C401.2.1 APPLICATION TO EXISTING BUILDINGS.
 ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. SECTIONS C402, C403, C404 AND C405; OR
 2. ANSI/ASHRAE/IESNA 90.1.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-20 Cont ID  
Sent By vperez Date 2017-04-20 Time 09:47 Rev Time 0.00
Received By vperez Date 2017-04-20 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-31 Cont ID  
Sent By vperez Date 2017-01-31 Time 09:52 Rev Time 0.00
Received By vperez Date 2017-01-31 Time 09:52 Sent To  
Notes
2017-01-31 09:53:26INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR
 HOOD SYSTEMS AND ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS DUE TO
 MODIFICATION; SEE VERBIAGE IN CODE.
 4. PLEASE ID SHUNT TRIP BREAKER AT THE PANELBOARD
 SCHEDULE K, FOR ALL DEVICES UNDER HOOD IN KITCHEN HOOD
 AREA. FBC 107.3.5
 5. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO
 ELECTRICAL.
 6. PROVIDE A NOTE AT THE RISER TO INDICATE THAT NEW
 400AMP BREAKER IS TO BE LISTED FOR REPLACEMENT WITHIN
 CABINET WHERE EXISTING 600AMP IS LOCATED. NEC 110.3B
 7. PROVIDE A NOTE TO SHEET E201 FOR DIMMING PANEL TO
 INDICATE THAT REQUIRED LIGHTING LEVELS MUST NOT FALL
 UNDER REQUIRED LIFE SAFETY LEVELS. FBC 107.3.5
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-10 Cont ID  
Sent By pleduc Date 2017-04-10 Time   Rev Time 0.00
Received By pleduc Date 2017-04-10 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-01-10 Cont ID  
Sent By pleduc Date 2017-01-10 Time   Rev Time 0.00
Received By pleduc Date 2017-01-09 Time 11:14 Sent To  
Notes
2017-01-10 11:44:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET T 101 - THERE ARE INCORRECT REFERENCES TO THE
 CURRENT FIRE CODES INDICATED.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2011
 EDITION.
  
 PLEASE CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET T 101 - THERE IS NO ADDRESS INDICATED IN THE
 TITLE BLOCK.
  
 FOR SPECIFIC LOCATION PURPOSES, PLEASE PROVIDE THE
 ADDRESS OF THE PROJECT IN THE TITEL BLOCK.
  
  
  
 3) NO SHEET - PLEASE PROVIDE A COMPLETE LIFE SAFETY
 PLAN THAT ILLUSTRATES OCCUPANT LOADS, TRAVEL DISTANCES,
 COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 PLEASE ENSURE, WITH SPECIFIC NARRATIVE OR DESIGN
 DRAWING, IF THE PROJECT PROPOSES TO BE ONGOING WITH
 OCCUPANCY OF THE GENERAL PUBLIC IN ADJACENT AREAS, HOW
 WILL THE PROJECT AREA BE PROTECTED/SEPARATED FROM
 ACCESS.
  
  
  
  
 4) SHEET A 101 - THERE ARE DASH LINES INDICATED AROUND
 THE KITCHEN AND PANTRY. THERE IS ALSO A NOTE INDICATED
 "FRP".
  
 PLEASE CLARIFY FRP AND IF IT IS FIRE RATED PROTECTION
 (OR SIMILAR), PLEASE INDICATE THE NUMERIC VALUE OF THE
 RATING.
  
  
  
 5) SHEET A 101 - A KITCHEN IS INDICATED. ANY KITCHEN
 EQUIPMENT SHALL BE INSTALLED PER THE APPLICABLE CODE
 UNDER SEPARATE SHOP DRAWINGS AND PERMIT.
  
 CHAPTER 9 BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN
 VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE
 IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE
 PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT.
  
 PLEASE ENSURE COMPLIANCE WITH THE ABOVE CODE.
  
  
  
 6) SHEET A 301 - SHOULD THE DASH LINES SHOWN ON SHEET A
 101 (#4 ABOVE) INDICATE A FIRE RATED WALLS THEN THE
 DOORS 117A, 117B, 120A, 118A, SHOULD BE FIRE RATED. THE
 DOOR SCHEULDE ON SHEET A 301 DO NOT INDICATE ANY RATING
 FOR THESE DOORS.
  
 PLEASE REVIEW, CLARFIY AND/OR CORRECT.
  
  
  
 7) SHEET FP 101 - WORK ON THE FIRE SPRINKLER SYSTEM IS
 INDICATED.
  
 PROVIDE A NOTE INDICATING:
  
 THE FIRE SPRINKLER SYSTEM SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE SPRINKLER SYSTEM EXCEEDS 4
 HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED
 UNTIL FULL AND COMPLETE PROTECTION IS RETURNED.
  
  
 8) SHEET E 202 - WORK ON THE FIRE ALARM SYSTEM IS
 INDICATED.
  
 PROVIDE A NOTE INDICATING:
  
 THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE ALARM SYSTEM EXCEEDS 4 HOURS,
 A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL
 FULL AND COMPLETE PROTECTION IS RETURNED.
  
  
  
 9) SHEET 102 - IF THE NOTE ON SHEET A 101 (# 4 ABOVE)
 INDICATES A FIRE RATED PARTITION, THERE IS NO CAL-OUT
 DESIGN OR DRAWING INDICATING THE LISTING FOR THE WALL.
  
 PLEASE CLARIFY AND OR CORRECT.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-05-17 Time 14:44 Sent To  
Notes
2017-05-18 14:44:38RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-04 Cont ID  
Sent By jroach Date 2017-05-04 Time 10:57 Rev Time 0.00
Received By jroach Date 2017-04-04 Time 13:50 Sent To  
Notes
2017-04-05 13:51:27C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-31 Cont ID  
Sent By jroach Date 2017-01-31 Time 15:17 Rev Time 0.00
Received By jroach Date 2017-01-04 Time 13:54 Sent To  
Notes
2017-01-05 13:59:27C06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-18 Cont ID  
Sent By jwitmer Date 2017-01-18 Time 13:42 Rev Time 0.00
Received By jwitmer Date 2017-01-13 Time 11:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-19 Cont ID  
Sent By ccole Date 2017-05-19 Time 15:38 Rev Time 0.00
Received By ccole Date 2017-05-19 Time 15:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-04-11 Cont ID  
Sent By ccole Date 2017-04-11 Time 11:27 Rev Time 0.00
Received By ccole Date 2017-04-11 Time 10:41 Sent To  
Notes
2017-04-11 11:55:502ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010099
 4/11/17
  
 1) SHEET M002: THE O/A CALCULATION FOR AC-9 IS NOT IN
 COMPLIANCE WITH ASHRAE 62.1-2010 WHICH REQUIRES AN
 OCCUPANCY DENSITY OF 150 PERSONS PER 1000 S.F.- PLEASE
 CORRECT BOTH THE O/A CALCULATIONS AND THE AC COOLING
 AND HEATING CALCULATIONS. PLEASE NOTE THAT THE AC
 CACLULATIONS FOR THE NEW SYSTEMS WERE NOT RETURNED WITH
 THE CORRECTED PLANS.
  
 2) THE REQUESTED SPECIFICATIONS FOR THE OVEN AND HOOD
 WERE NOT SUBMITTED. PLEASE NOTE THAT THE WPB
 CONSTRUCTION SERVICES DIVISION REQUIRES KITCHEN HOODS
 TO BE SUBMITTED UNDER A SEPARATE PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By ccole Date 2017-01-25 Time 09:39 Rev Time 0.00
Received By ccole Date 2017-01-25 Time 08:12 Sent To  
Notes
2017-01-25 10:08:561ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010099
 1/25/17
  
 1) PROVIDE FIRE DAMPERS FOR DUCTS PENETRATING THE
 FLOOR/CEILING ASSEMBLIE SBETWEEN THE FIRST AND SECOND
 LEVELS- SECTION 607.6.2.
  
 2) M103: SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE
 DETECTORS IN THE RETURN AIR SYSTEMS OF THE AC UNITS-
 SECTION 606.2.1
  
 3) M104: THERE APPEARS TO BE A ROOM OR SPACE ON THE
 SECOND FLOOR ABOVE THE NEW FIRST FLOOR KITCHEN AND
 MEETING ROOM THAT IS NO LONGER BEING CONDITIONED-
 PLEASE CLARIFY.
  
 4) REFER TO TABLE 403.3 AND PROVIDE AN EXHAUST
 VENTILATION CALCULATION FOR THE KITCHEN.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OVEN
 AND HOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-03 Cont ID  
Sent By gjohnson Date 2017-05-03 Time 14:04 Rev Time 0.00
Received By gjohnson Date 2017-05-03 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By gjohnson Date 2017-01-25 Time 17:25 Rev Time 0.00
Received By gjohnson Date 2017-01-25 Time 13:51 Sent To  
Notes
2017-01-25 17:54:311ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 THE TOP OF GRIPPING SURFACE. PER FBC ACC 609.4
  
 2. THE TOILETPAPER DISPENSER SHALL BE 7"- 9" MEASURED
 FROM THE FRONT OF THE TOILET TO THE CENTER OF THE
 DISPENSER. PER FBC ACC 604.7
  
 3. ONE URINAL SHALL BE ACCESSIBLE WITH THE RIM AT 17"
 MAX OFF FINISHED FLOOR AND HAVE A CLEAR FLOOR SPACE OF
 30" X 48" PER FBC ACC 605
  
 4. SHT. P102 SHOW EXACTLY WHERE THE EXISTING GREASE
 LINES WILL BE CAPPED NO DEAD ARE PERMITTED. PER WPB
 AMEND TO FBC
  
 5. ARE THE BATHROOMS 110 + 111 UNDER THIS PERMIT THE
 COVER SHEETS SHOWS THEM UNDER A DIFFERENT PHASE PLEASE
 CLARIFY. PER WPB AMEND TO FBC
  
 6. THE LAVATORY'S ARE REQUIRED TO HAVE TEMPERED WATER.
 PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 7. SHT S201 SHOWS FD IN BATHROOMS 126+127 THEY ARE NOT
 SHOWN ON THE PLUMBING PLANS PLEASE CLARIFY. PER WPB
 AMEND TO FBC

Review Stop Z ZONING
Rev No 2 Status P Date 2017-05-04 Cont ID  
Sent By jroach Date 2017-05-04 Time 10:56 Rev Time 0.00
Received By jroach Date 2017-05-04 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-01-31 Cont ID  
Sent By jroach Date 2017-01-31 Time 15:17 Rev Time 0.00
Received By jroach Date 2017-01-31 Time 15:17 Sent To  
Notes
2017-01-31 14:41:05ROUTED TO JOHN ROACH