| 2017-01-05 14:39:09 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17010071 |
| | W. P. B. PERMIT: 16120520 |
| | ADD: 1517 CAMERON SAMUEL LANE |
| | CONT: MAC ENTERPRISES |
| | TEL: 561-236-3627 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JAN. 05/ 2017 |
| | ACTION: PROVISO |
| | 1) CARPET CLASSIFICATION TO BE CLASS I, 0.45 WATTS/CM2 |
| | OR GREATER; CLASS II, 0.22 WATTS/CM2 OR GREATER 2014 |
| | FBC-B 804.2 CLASSIFICATION. |
| | |
| | THE 804.4.2 MINIMUM CRITICAL RADIANT FLUX. EXCEPTION: |
| | WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE |
| | PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE |
| | REQUIRED, AND MATERIALS COMPLYING WITH DOC FF-1 ?PILL |
| | TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D 2859 ARE |
| | PERMITTED IN ANY AREA WHERE CLASS II MATERIALS ARE |
| | REQUIRED. |
| | |
| | 804.4.1 TEST REQUIREMENT. IN ALL OCCUPANCIES, INTERIOR |
| | FLOOR COVERING MATERIALS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR |
| | PART 1630) OR WITH ASTM D 2859. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |