Plan Review Details - Permit 17010063
Plan Review Stops For Permit 17010063
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-03-21 Cont ID  
Sent By wjolin Date 2017-03-21 Time 17:26 Rev Time 0.00
Received By wjolin Date 2017-03-21 Time 16:01 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2017-03-09 Cont ID  
Sent By wjolin Date 2017-03-09 Time 12:28 Rev Time 0.00
Received By wjolin Date 2017-03-09 Time 12:04 Sent To M
Notes
2017-03-09 12:28:085011 BROADWAY - CITY MARKET
 PERMIT #17010063
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT X3
 REVISE PERMIT VALUE: UNDERGROUND FIRELINE AND BACKFLOW
 PREVENTER VALUE NEEDS TO BE ADDED TO THE FIRE SPRINKLER
 PERMIT SO THE PROPER FEES CAN BE ASSESSED. ORIGINAL
 COMMENT - SHEET FP1: PLANS INDICATE 4-INCH UNDERGROUND
 FIRE MAIN IS TO BE INSTALLED BY OTHERS. IS THIS
 CORRECT? IF YES, A SEPARATE UNDERGROUND FIRE LINE
 PERMIT WILL BE NEEDED.
  
 REPEAT COMMENT X2
 PART OF THE ROOFING STRUCTURE IS CONSTRUCTED OF
 COMBUSTIBLE CONSTRUCTION; HOWEVER, NO SPRINKLERS HAVE
 BEEN PROVIDED IN THE COMBUSTIBLE CONCEALED SPACE PER
 NFPA 13.
  
 REPEAT COMMENT X2
 THE HYDRAULIC AREA UTILIZES A SPRINKLER AREA OF 120
 SQUARE FEET PER SPRINKLER. PROVIDE HYDRAULIC
 CALCULATIONS UTILIZING THE NORTHEAST COOLER AS THE
 REMOTE SPRINKLER BECAUSE THIS SPRINKLER APPEARS TO BE
 PROTECTING AN AREA OF 182 SQUARE FEET, THEREBY
 REQUIRING A STARTING FLOW OF +36 GALLONS (182 X 0.2
 DENSITY).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By skennedy Date 2017-02-24 Time 08:30 Rev Time 0.00
Received By wjolin Date 2017-02-15 Time 14:52 Sent To M
Notes
2017-02-15 15:25:355011 BROADWAY - CITY MARKET
 PERMIT #17010063
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVISE PERMIT VALUE: UNDERGROUND FIRELINE AND BACKFLOW
 PREVENTER VALUE NEEDS TO BE ADDED TO THE FIRE SPRINKLER
 PERMIT SO THE PROPER FEES CAN BE ASSESSED. ORIGINAL
 COMMENT - SHEET FP1: PLANS INDICATE 4-INCH UNDERGROUND
 FIRE MAIN IS TO BE INSTALLED BY OTHERS. IS THIS
 CORRECT? IF YES, A SEPARATE UNDERGROUND FIRE LINE
 PERMIT WILL BE NEEDED.
  
 REPEAT COMMENT: NO EQUIPMENT CUTSHEETS SUBMITTED FOR
 BACKFLOW PREVENTER, FIRE SPRINKLERS, PIPING, HANGERS,
 ETC.
  
 NEW COMMENT: PART OF THE ROOFING STRUCTURE IS
 CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION; HOWEVER, NO
 SPRINKLERS HAVE BEEN PROVIDED IN THE COMBUSTIBLE
 CONCEALED SPACE PER NFPA 13.
  
 NEW COMMENT: THE HYDRAULIC AREA UTILIZES A SPRINKLER
 AREA OF 120 SQUARE FEET PER SPRINKLER. PROVIDE
 HYDRAULIC CALCULATIONS UTILIZING THE NORTHEAST COOLER
 AS THE REMOTE SPRINKLER BECAUSE THIS SPRINKLER APPEARS
 TO BE PROTECTING AN AREA OF 182 SQUARE FEET, THEREBY
 REQUIRING A STARTING FLOW OF +36 GALLONS (182 X 0.2
 DENSITY).
  
 NEW COMMENT: THE HYDRAULIC AREA SUPPORTS THE USE OF 4
 SPRINKLERS SUPPLIED FROM AN 1-1/4" BRANCHLINE; HOWEVER,
 A COUPLE OTHER BRANCHLINES HAVE MORE THAN FOUR
 SPRINKLERS ON THE BRANCHLINE IN THE SAME SIZE REMOTE
 AREA. PROVIDE A HYDRAULIC CALCULATION FOR THE SOUTHWEST
 KITCHEN AREA.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-01-05 Cont ID  
Sent By wjolin Date 2017-01-05 Time 13:18 Rev Time 0.00
Received By wjolin Date 2017-01-05 Time 13:11 Sent To M
Notes
2017-01-05 13:18:135011 BROADWAY - CITY MARKET
 PERMIT #17010063
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN SHEET 2 OF 2 NOT SUBMITTED FOR REVIEW.
  
 SHEET FP1: PLANS INDICATE 4-INCH UNDERGROUND FIRE MAIN
 IS TO BE INSTALLED BY OTHERS. IS THIS CORRECT? IF YES,
 A SEPARATE UNDERGROUND FIRE LINE PERMIT WILL BE NEEDED.
  
 NO EQUIPMENT CUTSHEETS SUBMITTED FOR BACKFLOW
 PREVENTER, FIRE SPRINKLERS, PIPING, HANGERS, ETC.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE
 FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE
 ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO
 THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
  
 NOTE:
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE
 INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS
 OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER,
 AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-27 Cont ID  
Sent By hmoser Date 2017-03-27 Time 11:34 Rev Time 0.00
Received By hmoser Date 2017-03-14 Time 12:49 Sent To  
Notes
2017-03-15 12:49:14RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-10 Cont ID  
Sent By skennedy Date 2017-03-10 Time 09:49 Rev Time 0.00
Received By skennedy Date 2017-03-01 Time 16:02 Sent To  
Notes
2017-03-02 16:02:19RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-24 Cont ID  
Sent By skennedy Date 2017-02-24 Time 08:30 Rev Time 0.00
Received By skennedy Date 2017-02-09 Time 08:29 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-24 Cont ID  
Sent By hmoser Date 2017-01-24 Time 13:32 Rev Time 0.00
Received By hmoser Date 2017-01-04 Time 15:42 Sent To  
Notes
2017-01-04 15:42:56ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-03-27 Cont ID  
Sent By hmoser Date 2017-03-27 Time 11:34 Rev Time 0.00
Received By hmoser Date 2017-03-27 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-03-10 Cont ID  
Sent By skennedy Date 2017-03-10 Time 09:48 Rev Time 0.00
Received By skennedy Date 2017-03-10 Time 09:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-24 Cont ID  
Sent By skennedy Date 2017-02-24 Time 08:29 Rev Time 0.00
Received By skennedy Date 2017-02-24 Time 08:29 Sent To  
Notes
2017-03-10 09:48:463RD REVIEW: FBC 2014 5TH ED.
 3RD REVIEW FBC 2014 EXISTING BUILDING
  
 SEE FIRE DEPARTMENT COMMENTS.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
2017-02-24 08:35:222ND REVIEW: FBC 2014 5TH ED.
 2ND REVIEW FBC 2014 EXISTING BUILDING
  
 SEE FIRE DEPARTMENT COMMENTS.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-24 Cont ID  
Sent By hmoser Date 2017-01-24 Time 13:26 Rev Time 0.00
Received By hmoser Date 2017-01-24 Time 13:26 Sent To  
Notes
2017-01-24 13:32:03SEE FIRE COMMENTS HM.