Plan Review Details - Permit 17010057
Plan Review Stops For Permit 17010057
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-12 Cont ID  
Sent By mvaldes Date 2017-01-12 Time 14:08 Rev Time 0.00
Received By mvaldes Date 2017-01-12 Time 11:14 Sent To  
Notes
2017-01-12 14:12:26PROVISO 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] SEPERATE STRUCTURE SHALL HAVE A SINGLE BRANCH
 CIRCUIT THEREFORE MEETING THE EXCEPTION REQUIREMENTS
 NEC 250.32 (GROUNDING SEPERATE STRUCTURE). AN EGC WILL
 BE ROUTED ALONG THE CIRCUIT CONDUCTORS FOR FAULT
 PROTECTION.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-05 Cont ID  
Sent By mvaldes Date 2017-01-05 Time 17:58 Rev Time 0.00
Received By mvaldes Date 2017-01-05 Time 17:40 Sent To  
Notes
2017-01-05 18:05:521ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] CLARIFY SCOPE OF WORK, THE APPLICATION CALLS OUT FOR
 INTERIOR WIRING? THIS REQUIRES AN ELECTRICAL FLOOR PLAN
 MEETING MINIMUM PROVISIONS SUCH AS RECEPTACLE OUTLET
 SPACING, LIGHTING OUTLET IN HABITABLE ROOMS, SMOKE
 ALARMS, TAMPER-RESISTANT RECEPTACLES, & AFCI, GFCI
 PROTECTION. FBC 107 (SHOW COMPLIANCE).
  
 2] ADD AN INTERSYSTEM BONDING TERMINAL TO THE GROUNDING
 DETAIL ON RISER DIAGRAM. NEC 250.94
  
 3] THE LOAD CALCULATION ARE INADEQUATE, PLEASE REFRENCE
 NEC 220.82 (OPTIONAL) AND PROVIDE THE MINIMUM 3VA FOR
 GENERAL LIGHTING PLUS THE 2 SMALL APPLIANCE CIRCUITS
 1500VA EACH. IN ADDITION THE DEMAND PERCENTAGE IS 40%
 NOT 45% PLEASE CORRECT ACCORDINGLY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-12 Cont ID  
Sent By mvaldes Date 2017-01-12 Time 14:08 Rev Time 0.00
Received By mvaldes Date 2017-01-10 Time 13:51 Sent To  
Notes
2017-01-11 13:52:06RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-05 Cont ID  
Sent By mvaldes Date 2017-01-05 Time 18:07 Rev Time 0.00
Received By mvaldes Date 2017-01-04 Time 14:43 Sent To  
Notes
2017-01-04 14:43:15ROUTED TO ELECTRICAL INBOX