Plan Review Details - Permit 17010048
Plan Review Stops For Permit 17010048
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 10:15 Rev Time 0.00
Received By shill Date 2018-05-27 Time 10:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 16:22 Rev Time 0.00
Received By shill Date 2017-08-29 Time 16:22 Sent To  
Notes
2017-08-29 16:39:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. DESIGNER OF RECORD TO REVIEW PRODUCTS FOR COMPLIANCE
 WITH THE DESIGN DOCUMENTS PRIOR TO SUBMITTAL.
 SUPERIMPOSED LOADS, DESIGN PRESSURES SHOULD BE REVIEWED
 PRIOR TO SUBMISSION TO THE BUILDING DIVISION.
  
 3RD REVIEW, UPDATED ENGINEERING WAS NOT REVIEWED.
 PLEASE DO SO AT THIS TIME.
  
 3. THREE SETS REQUIRED FBC 107.
  
 3RD REVIEW, THREE SETS ARE STILL REQUIRED, TWO
 SUBMITTED.
  
 4-5. OK
  
 NEW COMMENTS:
  
 6. THE ORIGINAL PACKAGE HAD CALCULATIONS WHICH WERE NOT
 INCLUDED IN THIS RESUBMITTAL. PLEASE PROVIDE.
  
 7. ONLY PYRAMID DRAWINGS SHOULD BE IN THIS SUBMITTAL.
 THE GRAND STAIR WAS SUBMITTED UNDER A DIFFERENT
 TRACKING NUMBER. PLEASE REMOVE AND RESUBMIT UNDER THE
 CORRECT NUMBER.
  
 8. CONTRACTOR IS TO PROVIDE THREE IDENTICAL, ORIGINAL,
 COLLATED SETS OF DRAWINGS FOR SUBMITTAL ISSUANCE. OLD
 DENIED DOCUMENTS SHOULD BE RETAINED IN THE PACKAGE AND
 MARKED "VOID".
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-15 Cont ID  
Sent By shill Date 2017-06-15 Time 07:40 Rev Time 0.00
Received By shill Date 2017-06-15 Time 07:04 Sent To  
Notes
2017-06-15 07:40:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE SKYLIGHT WAS DESIGNED TO FBC 2010, GOVERNING
 CODE IS FBC 2014, REVISE.
  
 SEE SHEET 1 OF 13 PREPARED BY DUANE D. BOICE, PE, OTHER
 LOCATIONS - ONE IS MARKED UP BY SEOR TO BE REVISED.
  
 2. DESIGNER OF RECORD TO REVIEW PRODUCTS FOR COMPLIANCE
 WITH THE DESIGN DOCUMENTS PRIOR TO SUBMITTAL.
 SUPERIMPOSED LOADS, DESIGN PRESSURES SHOULD BE REVIEWED
 PRIOR TO SUBMISSION TO THE BUILDING DIVISION.
  
 3. THREE SETS REQUIRED FBC 107.
  
 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.
  
 5. THE SHEET REFERENCED, S102, IS PART OF A REVISION
 THAT HAS NOT YET BEEN ISSUED. UNTIL THAT SHEET IS
 ISSUED, IT IS NOT A PART OF THE PERMIT RECORD SET.
  
 IT WAS SUGGESTED (MONTHS AGO) THAT APPLICANT SUBMIT
 THAT ONE SHEET AS A REVISION.
  
 OR, GET REVISION 17020076 (MODIFICATION OF KITCHEN
 LAYOUT)ISSUED. THE REVISION HAS PASSED ALL REVIEWS
 EXCEPT FOR IMPACT FEES. BE ADVISED THAT ***NO WORK***
 UNDER THAT REVISION CAN BE INSTALLED UNTIL THE REVISION
 IS ISSUED. EITHER REQUEST TO HAVE THE REVISION REVOKED
 AND ALL INSTALLATION IS TO CONFORM TO THE PERMIT
 DOCUMENTS ISSUED TO DATE, OR ADDRESS THE IMPACT FEE
 COMMENT AND HAVE THIS REVISION ISSUED.
  
 IT IS NOT CLEAR WHY THIS HAS NOT BEEN ADDRESSED AS THE
 IMPACT FEES DUE WILL LIKELY BE MINIMAL. IT IS MY
 UNDERSTANDING THAT THE SQUARE FOOT AREA ADDED WAS LESS
 THAN 200 FEET.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-24 Cont ID  
Sent By shill Date 2017-01-24 Time 11:19 Rev Time 0.00
Received By shill Date 2017-01-24 Time 11:19 Sent To  
Notes
2017-01-24 11:20:08****CORRECTIONS****
 REVISED 1/27/17
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE CALCULATIONS SHOW A DP OF +30.2 / -83.6. SEE
 SHEET S102, THIS DOES NOT MEET THE MINIMUM DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER OF RECORD.
  
 2. THE SKYLIGHT WAS DESIGNED TO FBC 2010, GOVERNING
 CODE IS FBC 2014, REVISE.
  
 3. DESIGNER OF RECORD TO REVIEW PRODUCTS FOR COMPLIANCE
 WITH THE DESIGN DOCUMENTS PRIOR TO SUBMITTAL.
 SUPERIMPOSED LOADS, DESIGN PRESSURES SHOULD BE REVIEWED
 PRIOR TO SUBMISSION TO THE BUILDING DIVISION.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 10:15 Rev Time 0.00
Received By shill Date 2018-05-14 Time 16:14 Sent To  
Notes
2018-05-15 16:14:25RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 16:41 Rev Time 0.00
Received By shill Date 2017-08-24 Time 10:34 Sent To  
Notes
2017-08-28 10:34:53SIGNATURES ROUTED TO SHILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-15 Cont ID  
Sent By shill Date 2017-06-15 Time 07:40 Rev Time 0.00
Received By shill Date 2017-05-26 Time 10:22 Sent To  
Notes
2017-05-30 10:22:34RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-24 Cont ID  
Sent By shill Date 2017-01-24 Time 11:20 Rev Time 0.00
Received By shill Date 2017-01-03 Time 11:30 Sent To  
Notes
2017-01-04 11:30:16SUBMITTAL ROUTED TO SHILL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 16:40 Rev Time 0.00
Received By shill Date 2017-08-29 Time 16:40 Sent To  
Notes
2017-08-29 16:41:43THIS IS NOT A DIGITAL SUBMITTAL. THIS WAS GIVEN A
 "DIGITAL" DESIGNATION AT TIME OF INTAKE AS THE MASTER
 WAS DIGITAL, AND WAS NOT CORRECTED UNTIL 8/29/17.
  
  