Plan Review Details - Permit 17010010
Plan Review Stops For Permit 17010010
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-01-06 Cont ID  
Sent By jwitmer Date 2017-01-06 Time 09:04 Rev Time 0.00
Received By jwitmer Date 2017-01-06 Time 06:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-17 Cont ID  
Sent By mvaldes Date 2017-01-17 Time 10:45 Rev Time 0.00
Received By rlecky Date 2017-01-10 Time 10:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-09 Cont ID  
Sent By pleduc Date 2017-01-09 Time   Rev Time 0.00
Received By pleduc Date 2017-01-09 Time 11:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-25 Cont ID  
Sent By gjohnson Date 2017-01-25 Time 11:33 Rev Time 0.00
Received By gjohnson Date 2017-01-03 Time 14:28 Sent To  
Notes
2017-01-04 14:29:08B04

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-06-27 Cont ID  
Sent By ccole Date 2017-06-27 Time 17:31 Rev Time 0.00
Received By ccole Date 2017-01-13 Time 17:31 Sent To  
Notes
2017-01-13 17:34:29MECHANICAL SCOPE OF WORK REVIEWED AND APPROVED UNDER
 PERMIT REVISION #17061079
 CCOLE- 6/27/17

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-06-30 Cont ID  
Sent By gjohnson Date 2017-06-30 Time 16:32 Rev Time 0.00
Received By gjohnson Date 2017-06-30 Time 16:32 Sent To  
Notes
2017-06-30 16:34:36APPPROVED UNDER REV# 16100880 GPJ

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By gjohnson Date 2017-01-25 Time 11:31 Rev Time 0.00
Received By gjohnson Date 2017-01-25 Time 08:43 Sent To  
Notes
2017-01-25 11:31:341ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
 1. BATH # 1 ELEVATIONS BATH#2 MIRRORED PER FBC ACC
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
  
  
 1. THE 3 COMPARTMENT SINK , FLOOR DRAIN AND TABLE SINK
 AND SLOPE SINK ARE REQUIRED TO CONNECT TO A GREASE
 INTERCEPTOR. PER FBC PL 1003.1
  
 2. THE FLOOR DRAIN SHALL BE EQUIPPED WITH A TRAP
 PRIMER. FBC PL 1002.4
  
 3. THE WASHING MACHINE IS REQUIRED TO DRAIN THROUGH A
 LENT INTERCEPTOR. PER FBC PL 1003.6 LAUNDRIES.
 LAUNDRY FACILITIES NOT INSTALLED WITHIN AN INDIVIDUAL
 DWELLING UNIT OR INTENDED FOR INDIVIDUAL FAMILY USE
 SHALL BE EQUIPPED WITH AN INTERCEPTOR WITH A WIRE
 BASKET OR SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT
 PREVENTS PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2
 INCH (12.7 MM) OR LARGER IN SIZE, STRING, RAGS, BUTTONS
 OR OTHER MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE
 SYSTEM.