Plan Review Details - Permit 16120999
Plan Review Stops For Permit 16120999
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-03 Cont ID  
Sent By rmcdouga Date 2017-01-03 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2017-01-03 Time 08:21 Sent To  
Notes
2017-01-03 08:23:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FROM THE PRODUCT APPROVAL (NOA NO. 14-1030.02) FOR
 THE GAF RUBEROID MODIFIED BITUMEN ROOF SYSTEM THAT WAS
 SUBMITTED, SPECIFY THE SYSTEM TYPE, THE FASTENING
 OPTION AND THE MAXIMUM DESIGN PRESSURE. THE MAXIMUM
 DESIGN PRESSURES LISTED IN THIS NOA DO NOT MEET THE
 REQUIRED UPLIFT PRESSURES FOR THE PERIMETER AND CORNER
 AREAS. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING FROM A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT
 OR REGISTERED ROOF CONSULTANT AS REQUIRED BY LIMITATION
 NUMBER 7 ON PAGE 30 OF THE PRODUCT APPROVAL. FBC
 107.2.1.3
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-03 Cont ID  
Sent By rmcdouga Date 2017-01-03 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2016-12-30 Time 15:32 Sent To  
Notes
2016-12-30 15:32:41RMCDOUGAL