Plan Review Details - Permit 16120953
Plan Review Stops For Permit 16120953
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-20 Cont ID  
Sent By cthroop Date 2017-07-20 Time 10:02 Rev Time 0.00
Received By cthroop Date 2017-07-20 Time 10:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-24 Cont ID  
Sent By cthroop Date 2017-04-24 Time 11:17 Rev Time 0.00
Received By cthroop Date 2017-04-24 Time 10:17 Sent To  
Notes
2017-04-24 11:17:56BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT MAY BE REQUIRED. STATE PERCENTAGE OF
 EXISTING ROOF OR SQUARE FOOTAGE OF EXISTING ROOF
 REPAIRS.
 2. SEE PLAN PAGE A-4, CHANGE CODE REFERENCE FROM FBC
 2010 TO FBC 2014 5TH ED.
 3. PROVIDE WINDOW SCHEDULE.
 4. PROVIDE WINDOW AND DOOR PRODUCT APPROVALS.
 4A. IF NON-IMPACT DOORS OR WINDOWS ARE INSTALLED,
 PROVIDE SHUTTER SCHEDULE AND PRODUCT APPROVALS.
 5. SEE PLAN PAGE A-1, EXISTING BLDG. LEVEL III
 ALTERATION SECTION 401.4 DOES NOT EXIST. CHANGE CODE
 REFERENCE TO FBC2014 5TH ED. EXISTING BUILDING
 ALTERATION LEVEL III SECTION 505.1.
 6. PROVIDE DETAIL OF EXTERIOR WALL ASSEMBLY. SHOW
 TYPICAL FRAMING AT DOOR AND WINDOW OPENINGS, DRAINAGE
 PLANE AND FASTENER SCHEDULE FOR EXTERIOR SIDING.
 7. PROVIDE REPAIR DETAIL FOR ANY STRUCTURAL CONCRETE
 REPAIRS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, AND DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-13 Cont ID  
Sent By CThroop Date 2017-01-13 Time 11:08 Rev Time 0.00
Received By cthroop Date 2017-01-13 Time 09:35 Sent To  
Notes
2017-01-13 11:11:42BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT IDENTIFY WHICH PERMIT APPLICATION APPLIES TO
 WHICH STRUCTURE.
 2. PROVIDE SITE PLAN WITH PROPERTY LINE SETBACKS AND
 DEMENSIONS BETWEEN STRUCTURES. INDICATE ADDRESS AND
 UNIT NUMBER ON EACH STRUCTURE.
 3. NO REVIEW PERFORMED AT THIS TIME.
  
 COMPLY WITH COMMENTS AND RE-SUBMIT.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-17 Cont ID  
Sent By vperez Date 2017-04-17 Time 08:31 Rev Time 0.00
Received By vperez Date 2017-04-17 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By vperez Date 2017-01-25 Time 11:54 Rev Time 0.00
Received By vperez Date 2017-01-25 Time 11:54 Sent To Z
Notes
2017-01-25 11:55:052ND REVIEW-
  
 ORIGINAL COMMENTS 4 AND 5 ADDRESSED
  
 PENDING 1,2, 3,6,7 AND 8 PLEASE ADDRESS
 ZONING HAS DISSAPROVED MULTIPLE UNITS, PLEASE CLARIFY
 BEFORE RESUBMITTING
  
 V. PEREZ
 *6717

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-21 Cont ID  
Sent By gjohnson Date 2017-07-21 Time 10:37 Rev Time 0.00
Received By gjohnson Date 2017-07-07 Time 14:06 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-04 Cont ID  
Sent By ccole Date 2017-05-04 Time 17:34 Rev Time 0.00
Received By ccole Date 2017-03-29 Time 10:17 Sent To  
Notes
2017-03-31 10:17:32B28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-27 Cont ID  
Sent By njwira Date 2017-01-27 Time 16:01 Rev Time 0.00
Received By njwira Date 2016-12-29 Time 11:40 Sent To  
Notes
2016-12-30 11:40:44B28
 **TRAVELLING WITH 16080345**

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-13 Cont ID  
Sent By gjohnson Date 2017-07-21 Time 10:37 Rev Time 0.00
Received By ccole Date 2017-07-13 Time 07:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-04 Cont ID  
Sent By ccole Date 2017-05-04 Time 17:21 Rev Time 0.00
Received By ccole Date 2017-05-04 Time 17:21 Sent To  
Notes
2017-05-04 17:34:372ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16120953
 5/4/17
  
 1) THE ENERGYGAUGE FORM R405-2014 AND AC CALCULATIONS
 ARE BOTH INDICATING A THOUGH-THE WALL 1-TON AC SYSTEM
 AT 15 SEER, HOWEVER THE PLANS ARE INDICATING A 2-TON
 SPLIT SYSTEM.
  
 2) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 GOODMAN AIR HANDLER TO VERIFY IT CAN PRODUCE 1000 CFMS
 OF SUPPLY AIR AS INDICATED ON THE PLAN.
  
 3) PROVIDE THE DIMENSIONS OF THE AC DUCT DROP FROM THE
 2ND TO THE 1ST FLOOR.
  
 4) CLARIFY HOW AIR IS BEING RETURNED TO THE AIR HANDLER
 ON THE 2ND FLOOR. THERE IS NO RETURN GRILL SHOWN AND
 THE DOOR IS INDICATED TO BE SOLID IN THE DOOR SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-05 Cont ID  
Sent By ccole Date 2017-01-05 Time 07:54 Rev Time 0.00
Received By ccole Date 2017-01-05 Time 07:54 Sent To  
Notes
2017-01-05 07:55:231ST REVIEW FBC-2014 RESIDIENTIAL MECHANICAL
 PERMIT #16120953
 1/5/17
  
 1) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS
 INDICATING MAKES, MODELS, COOLING AND HEATING
 CAPACITIES, AND EFFICIENCY RATINGS. THE SUBMIITTED AC
 AND ENERGY CALCULATIONS CANNOT BE REVIEWED IN ENTIRETY
 WITHOUT SYSTEMS' INFORMATION. PLEASE NOTE THAT THE
 SYSTEM IS LISTED AS "GENERIC" UNDER THE EQUIPMENT
 SUMMARY ON THE AC CALCULATIONS.
  
 2) THE COOLING AND HEATING SYSTEM COMPLIANCE DATA ON
 THE SUBMITTED ENERGYGAUGE FORM R405-2014 DOES NOT MATCH
 THE PLANS: A) THE THROUGH THE WALL SYSTEMS SHOWN ON THE
 PLAN ARE LISTED AS ONE "CENTRAL UNIT" ON THE FORM. B)
 THE REVERSE CYCLE HEATING SYSTEMS SHOWN ON THE PLAN ARE
 LISTED AS HEAT STRIPS ON THE FORM.
  
 3) THE ENERGYGAUGE FORM MUST BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 4) THE PLANS MUST BE REVISED TO SHOW THE INSULATION
 R-VALUES IN THE WALLS AND CEILING IN ORDER TO VERIFY
 THE VALUES LISTED ON THE ENERGY FORM R405-2014 ARE
 ACCURATE.
  
 5) THE ENERGY FORM R405 IS LISTING EITHER NEW OR
 EXISTING DOUBLE-PANED WINDOWS AT 0.29 U-FACTOR/0.23
 SHGC. PLEASE PROVIDE A WINDOW SCHEDULE ON THE PLAN AND
 SUBMIT MANUFACTURER'S DATA SHEET FOR REVIEW.
  
 6) PROVIDE A DRYER VENTING PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-07-21 Cont ID  
Sent By gjohnson Date 2017-07-21 Time 10:36 Rev Time 0.00
Received By gjohnson Date 2017-07-21 Time 10:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-04-20 Cont ID  
Sent By gjohnson Date 2017-04-20 Time 09:21 Rev Time 0.00
Received By gjohnson Date 2017-04-19 Time 14:12 Sent To  
Notes
2017-04-20 09:34:251ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A-4 WATER HEATER ON SECOND FLOOR IS NOT SHOWN
 ON EXISTING PLAN IS THIS A NEW LOCATION, ON PREVIOUS
 PLANS THE WATER HEATER IS SHOWN ON FIRST FLOOR IN A
 LAUNDRY ROOM THAT IS NOT SHOWN ON THIS PLAN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. A-4 A DRYER VENT IS SHOWN IN BREAKFAST AREA IS
 THIS A STACKABLE WASHER DRYER UNIT. PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 3. SHT. A-4 IF THAT IS A STACKABLE UNIT IN BREAKFAST
 AREA IT IS NOT SHOWN ON EXISTING IS IT A NEW LOCATION,
 ON PREVIOUS PLANS IT IS SHOWN IN A SEPARATE LAUNDRY
 ROOM THAT IS NOT SHOWN ON THIS PLAN PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-23 Cont ID  
Sent By gjohnson Date 2017-01-23 Time 14:52 Rev Time 0.00
Received By gjohnson Date 2017-01-23 Time 14:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-07-20 Cont ID  
Sent By cthroop Date 2017-07-20 Time 10:02 Rev Time 0.00
Received By cthroop Date 2017-07-20 Time 10:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-04-18 Cont ID  
Sent By njwira Date 2017-04-18 Time 15:55 Rev Time 0.00
Received By njwira Date 2017-04-18 Time 14:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-01-27 Cont ID  
Sent By llouie Date 2017-01-27 Time 16:01 Rev Time 0.00
Received By njwira Date 2017-01-25 Time 15:13 Sent To I
Notes
***NONE***