Plan Review Details - Permit 16120942
Plan Review Stops For Permit 16120942
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2017-06-23 Cont ID  
Sent By jgomez Date 2017-06-23 Time 15:08 Rev Time 0.00
Received By jgomez Date 2017-06-23 Time 11:55 Sent To  
Notes
2017-06-23 12:01:35 
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2017-06-09 Cont ID  
Sent By jgomez Date 2017-06-09 Time 15:24 Rev Time 0.00
Received By jgomez Date 2017-06-09 Time 13:43 Sent To  
Notes
2017-06-09 13:46:45RESIDENTIAL (R3) ALTERATION, FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ARCHITECT TO PAY FOUR TIMES THE PLAN REVIEW FEE AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR MULTIPLE
 PLAN REVIEW REJECTIONS.
  
 ORIGINAL COMMENT:
 1- SIZE OF WINDOWS SPECIFIED FOR BEDROOM #3 DON'T SEEM
 TO COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE SIZE OF
 WINDOWS OR PROVIDE PROOF THAT SPECIFIED SIZE WILL
 COMPLY WITH THE EGRESS REQUIREMENTS.
 RESPONSE: REPEAT COMMENT. 4'-5" X 4'-6" WINDOWS DON'T
 COMPLY WITH THE EGRESS REQUIREMENTS. THEY DON'T MEET
 THE MIN. 24" CLEAR OPENING HEIGHT. REVISE AS REQUIRED.
 NOTE: CALLED PGT WINDOWS. THEY SAID THE MINIMUM WINDOW
 HEIGHT REQUIRED IS 61.750" (59.5") AND IS FOR A SPECIAL
 WINDOW WITH THE EGRESS HEIGHT SPECIFICATION. FOR
 EXAMPLE SH25"EH".
  
 ORIGINAL COMMENT:
 2- PLANS WERE REVISED AND NOW THEY SHOW REPLACEMENT OF
 ALL EXISTING WINDOWS AND DOORS. CLEARLY SPECIFY TYPE
 AND SIZE OF EXISTING BEDROOM WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 704
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. 4'-5" X 4'-6" WINDOWS DON'T
 COMPLY WITH THE EGRESS REQUIREMENTS. THEY DON'T MEET
 THE MIN. 24" CLEAR OPENING HEIGHT. REVISE AS REQUIRED.
 NOTE: CALLED PGT WINDOWS. THEY SAID THE MINIMUM WINDOW
 HEIGHT REQUIRED IS 61.750" (59.5") AND IS FOR A SPECIAL
 WINDOW WITH THE EGRESS HEIGHT SPECIFICATION. FOR
 EXAMPLE SH25"EH".
  
  
 NOTE:
 PLANS WILL NEED TO BE SEND FOR HISTORIC REVIEW ONCE THE
 EGRESS WINDOWS ARE REVISED ON PLANS AND ELEVATIONS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-05-18 Cont ID  
Sent By jgomez Date 2017-05-18 Time 14:19 Rev Time 0.00
Received By jgomez Date 2017-05-17 Time 18:43 Sent To  
Notes
2017-05-17 18:47:17RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 I TRY TO APPROVE PLANS WITH PROVISO WHEN THERE ARE
 PENDING ITEMS THAT CAN BE SUBMITTED LATER AFTER THE
 PERMIT IS ISSUED BUT IN THIS CASE I CAN NOT ISSUE THE
 PERMIT WITH THE PROVISO BECAUSE THE EGRESS REQUIREMENTS
 NEED TO BE MET.
  
 NOTE:
 ARCHITECT TO PAY FOUR TIMES THE PLAN REVIEW FEE AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR MULTIPLE
 PLAN REVIEW REJECTIONS.
  
 ORIGINAL COMMENT:
 1- SIZE OF WINDOWS SPECIFIED FOR BEDROOM #3 DON'T SEEM
 TO COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE SIZE OF
 WINDOWS OR PROVIDE PROOF THAT SPECIFIED SIZE WILL
 COMPLY WITH THE EGRESS REQUIREMENTS.
 RESPONSE: REPEAT COMMENT. ARCHITECT'S RESPONSE LETTER
 STATES "EGRESS REQUIREMENTS ARE 20"X24" MINIMUM +
 MINIMUM 5.7 SF. THE OPENING SIZE IS 23 1/2" X 48"
 OPENING (WITH 7.6 SF OPENING) ALL SIZES LABELED ON THE
 WINDOW SCHEDULE (NO CHANGE TO DRAWINGS).
 NONE OF THE SINGLE HUNG WINDOWS SPECIFIED ON THE WINDOW
 SCHEDULE COMPLY WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 FBC-RESIDENTIAL, 5TH EDITION (2014). SEC. R310.1.2
 REQUIRES A MIN. OPENING HEIGHT OF 24 INCHES. REVISE AS
 REQUIRED TO COMPLY.
 ARCHITECT TO PAY FOUR TIMES THE PLAN REVIEW FEE AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR MULTIPLE
 PLAN REVIEW REJECTIONS.
  
 ORIGINAL COMMENT:
 2- PLANS WERE REVISED AND NOW THEY SHOW REPLACEMENT OF
 ALL EXISTING WINDOWS AND DOORS. CLEARLY SPECIFY TYPE
 AND SIZE OF EXISTING BEDROOM WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 704
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ARCHITECT'S RESPONSE LETTER
 STATES THAT " ALL EGRESS WINDOWS ARE LABELED AS SUCH ON
 THE SCHEDULE & THE ELEVATIONS (NO CHANGE TO DRAWINGS).
 EGRESS WINDOWS INDICATED ON THE WINDOW SCHEDULE DON'T
 COMPLY WITH EGRESS REQUIREMENTS. NEED WINDOWS THAT
 COMPLY WITH THE EGRESS REQUIREMENTS (COORDINATE WITH
 ITEM #1 ABOVE) OR NEED TO PROVIDE COMPLETE INFORMATION
 SHOWING THAT THE PROPOSED WINDOWS FOR EXISTING BEDROOMS
 WILL COMPLY AT LEAST WITH WITH THE EXCEPTION OF SEC 704
 OF THE EXISTING BUILDING CODE.
 ARCHITECT TO PAY FOUR TIMES THE PLAN REVIEW FEE AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR MULTIPLE
 PLAN REVIEW REJECTIONS.
  
 ORIGINAL COMMENT:
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 EXISTING GARAGE EXTERIOR WALLS AND CEILING SHOWING
 COMPLIANCE WITH THE INSULATION REQUIREMENTS SHOWN ON
 THE ENERGY CALCULATIONS. SEC. R103.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: REPEAT COMMENT. ARCHITECT'S RESPONSE LETTER
 STATES THAT "INSULATION CALLED OUT ON THE
 SPECIFICATIONS COVER SHEET (NEW 9" FIBERGLASS R=30).
 SPECIFICATIONS ON THE COVER SHEET ARE MISSING THE
 SPECIFICATIONS FOR THE INSULATION ON THE GARAGE DOORS.
 PROVIDE INFORMATION. COORDINATE WITH THE THE ENERGY
 CALCULATIONS SUBMITTED.
 ARCHITECT TO PAY FOUR TIMES THE PLAN REVIEW FEE AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR MULTIPLE
 PLAN REVIEW REJECTIONS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) NEW COMMENT BASED ON ENERGY CALCULATIONS AND
 ARCHITECT'S REVISIONS FOR ROOF VENTILATION. NEED
 PRODUCT APPROVAL FOR NEW ROOF VENTS AS SPECIFIED ON
 PLANS. NOTE: MAKE SURE VENTS ARE DESIGNED FOR CONCRETE
 ROOF TILE.
  
 B) ORIGINAL COMMENT: CONCRETE ROOF TILE. ONLY ONE COPY
 WAS SUBMITTED. NEED TO PROVIDE 2 COPIES.
 RESPONSE: THE COVER PAGE AND THE REST OF THE PAGES OF
 THE SECOND COPY SUBMITTED DON'T MATCH. OVER PAGE
 SUBMITTED IS FOR NOA 16-0711.05 BUT THE FOLLOWING PAGE
 ARE FOR NOA 12-0222.03. PROVIDE COMPLETE AND CORRECT
 NOA'S (2 COPIES).
  
 C) ORIGINAL COMMENT: ROOF TILE ADHESIVE AS SPECIFIED BY
 THE ARCHITECT OF RECORD ON COVER PAGE OF NOA SUBMITTED.
 SEE NOA FOR LISTED ADHESIVES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 5- ARCHITECT OF RECORD TO REVIEW ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 NOTE:
 PLANS WILL NEED TO BE SEND FOR HISTORIC REVIEW ONCE THE
 EGRESS WINDOWS ARE REVISED ON PLANS AND ELEVATIONS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-01 Cont ID  
Sent By jgomez Date 2017-05-01 Time 10:51 Rev Time 0.00
Received By jgomez Date 2017-05-01 Time 10:17 Sent To  
Notes
2017-05-01 10:18:59RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ARCHITECT TO PAY FOUR TIMES THE PLAN REVIEW FEE AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR MULTIPLE
 PLAN REVIEW REJECTIONS.
  
 1- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM.
 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- A) SIZE OF WINDOWS SPECIFIED FOR BEDROOM #3 DON'T
 SEEM TO COMPLY WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE SIZE
 OF WINDOWS OR PROVIDE PROOF THAT SPECIFIED SIZE WILL
 COMPLY WITH THE EGRESS REQUIREMENTS.
 RESPONSE: REPEAT COMMENT. ARCHITECT TO PAY FOUR TIMES
 THE PLAN REVIEW FEE AS REQUIRED BY FLORIDA STATUTE
 553.80(2)(B) FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 3- PLANS WERE REVISED AND NOW THEY SHOW REPLACEMENT OF
 ALL EXISTING WINDOWS AND DOORS. CLEARLY SPECIFY TYPE
 AND SIZE OF EXISTING BEDROOM WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 704
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
 ARCHITECT DIDN'T SPECIFY TYPE AND SIZE OF EXISTING
 WINDOWS. PROPOSED WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS REQUIREMENTS. UNABLE TO VERIFY THE EGRESS
 REQUIREMENTS.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW WINDOW AND EXTERIOR DOORS FRAMING DETAILS AND THE
 INFILL OF EXTERIOR WALLS BY BEDROOM #3 AND BY THE
 DINING AREA. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 EXISTING GARAGE EXTERIOR WALLS AND CEILING SHOWING
 COMPLIANCE WITH THE INSULATION REQUIREMENTS SHOWN ON
 THE ENERGY CALCULATIONS. SEC. R103.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 6- ENERGY CALCULATIONS SUBMITTED;
 A) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER NAME AND BUILDER NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) ATTIC INFORMATION ON PAGE 3 OF 5 IS CONSIDERING A
 VENT RATIO OF 1/300. TYPICALLY THE VENT RATIO REQUIRED
 BY SEC. R806.2 FBC-RESIDENTIAL IS 1/150. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 EXISTING HOUSE COMPLIES WITH THE CONDITIONS REQUIRED BY
 THE EXCEPTION ON SEC. R806.2 FBC-RESIDENTIAL TO
 CONSIDER THE 1/300 VENTILATION RATIO OR REVISE THE
 VENTILATION RATIO AS REQUIRED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 7- DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE HOUSE COMPLIES WITH THE
 1/300 VENTILATION RATIO AS SPECIFIED ON THE ENERGY
 CALCULATIONS ON PAGE 3 OF 5. COORDINATE WITH THE ENERGY
 CALCULATIONS SUBMITTED. NOTE: TYPICALLY THE VENT RATIO
 REQUIRED BY SEC. R806.2 FBC-RESIDENTIAL IS 1/150.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 THE EXISTING HOUSE COMPLIES WITH THE CONDITIONS
 REQUIRED BY THE EXCEPTION ON SEC. R806.2
 FBC-RESIDENTIAL TO CONSIDER THE 1/300 VENTILATION
 RATIO.
 RESPONSE: ENERGY CALCULATIONS DIDN'T REVISED THE
 VENTILATION RATIO. THAT'S WHY THIS INFORMATION IS
 REQUIRED.
  
 8- SCOPE OF WORK WAS REVISED. UPDATE VALUATION TO
 INCLUDE ALL THE ADDITIONAL WORK INCLUDING WINDOW /DOORS
 REPLACEMENT, NEW ROOF TILE, ETC AND ALL THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CUSTOM ENTRY DOOR AS SPECIFIED ON PLANS. NOTE:
 DRAWING #ET0003 SUBMITTED IS NOT AN APPROVED FLORIDA
 PRODUCT APPROVAL OR MIAMI-DADE NOA. IF THERE IS NO
 OFFICIAL PRODUCT APPROVAL, THEN MANUFACTURER MAY SUBMIT
 COMPLETE ORIGINAL ENGINEERING PACKAGE FOR LOCAL PRODUCT
 APPROVAL. THIS WILL BE REVIEWED AND APPROVE BY THE
 BUILDING OFFICIAL. ONLY ONE COPY WAS SUBMITTED. NEED TO
 PROVIDE 2 COPIES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) FRENCH DOORS. ONLY ONE COPY WAS SUBMITTED. NEED TO
 PROVIDE 2 COPIES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 C) SINGLE HUNG WINDOWS. ONLY ONE COPY WAS SUBMITTED.
 NEED TO PROVIDE 2 COPIES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D) CONCRETE ROOF TILE. ONLY ONE COPY WAS SUBMITTED.
 NEED TO PROVIDE 2 COPIES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 E) ROOF TILE ADHESIVE AS SPECIFIED BY THE ARCHITECT OF
 RECORD ON COVER PAGE OF NOA SUBMITTED. SEE NOA FOR
 LISTED ADHESIVES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 10- ARCHITECT OF RECORD TO REVIEW ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT.
  
 11- ARCHITECT TO CLARIFY WHAT ARE THE THREE ADDITIONAL
 LINES SHOWN IN THE WALL BY THE NEW MASTER BEDROOM
 CLOSET. PROVIDE WALL LEGEND. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-27 Cont ID  
Sent By jgomez Date 2017-03-27 Time 18:06 Rev Time 0.00
Received By jgomez Date 2017-03-27 Time 15:17 Sent To HIST
Notes
2017-03-27 15:17:38RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM.
 AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH COUNTY
 (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- SPECIFY TYPE AND SIZE OF WINDOW FOR BEDROOM #3 TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: NONE OF THE WINDOW SIZES SHOWN ON BEDROOM #3
 COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310
 FBC-RESIDENTIAL, 5TH EDITION (2014). ALSO, WINDOW
 SCHEDULE DOESN'T SPECIFY TYPE OF WINDOW. REVISE AS
 REQUIRED. PROVIDE COMPLETE INFORMATION.
  
 3- NEW COMMENT. PLANS WERE REVISED AND NOW THEY SHOW
 REPLACEMENT OF ALL EXISTING WINDOWS AND DOORS. CLEARLY
 SPECIFY TYPE AND SIZE OF EXISTING BEDROOM WINDOWS TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 704 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW WINDOW AND EXTERIOR DOORS FRAMING DETAILS AND THE
 INFILL OF EXTERIOR WALLS BY BEDROOM #3 AND BY THE
 DINING AREA. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 EXISTING GARAGE EXTERIOR WALLS AND CEILING SHOWING
 COMPLIANCE WITH THE INSULATION REQUIREMENTS SHOWN ON
 THE ENERGY CALCULATIONS. SEC. R103.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 6- ENERGY CALCULATIONS SUBMITTED;
 A) OWNER NEEDS TO CERTIFY AT BOTTOM OF FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: CLARIFY WHY THE SIGNATURE OF THE OWNER IS NOT
 THE SAME AS THE SIGNATURE SHOWN ON THE PERMIT
 APPLICATION.
  
 B) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS TO
 PROVIDE HIS NAME, LICENSE NUMBER, ETC AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 C) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER NAME AND BUILDER NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 D) NEW COMMENT: FLOOR PLANS WERE REVISED. ENERGY
 CALCULATIONS NEED TO BE REVISED REFLECTING THE SQUARE
 FOOTAGE OF REVISED PLANS.
  
 E) ATTIC INFORMATION ON PAGE 3 OF 5 IS CONSIDERING A
 VENT RATIO OF 1/300. TYPICALLY THE VENT RATIO REQUIRED
 BY SEC. R806.2 FBC-RESIDENTIAL IS 1/150. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 EXISTING HOUSE COMPLIES WITH THE CONDITIONS REQUIRED BY
 THE EXCEPTION ON SEC. R806.2 FBC-RESIDENTIAL TO
 CONSIDER THE 1/300 VENTILATION RATIO.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 F) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 7- SCOPE OF WORK WAS REVISED. UPDATE VALUATION TO
 INCLUDE ALL THE ADDITIONAL WORK INCLUDING WINDOW /DOORS
 REPLACEMENT, NEW ROOF TILE, ETC AND ALL THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CUSTOM ENTRY DOOR AS SPECIFIED ON PLANS. NOTE:
 DRAWING #ET0003 SUBMITTED IS NOT AN APPROVED FLORIDA
 PRODUCT APPROVAL OR MIAMI-DADE NOA. IF THERE IS NO
 OFFICIAL PRODUCT APPROVAL, THEN MANUFACTURER MAY SUBMIT
 COMPLETE ORIGINAL ENGINEERING PACKAGE FOR LOCAL PRODUCT
 APPROVAL. THIS WILL BE REVIEWED AND APPROVE BY THE
 BUILDING OFFICIAL. ONLY ONE COPY WAS SUBMITTED. NEED TO
 PROVIDE 2 COPIES.
  
 B) FRENCH DOORS. ONLY ONE COPY WAS SUBMITTED. NEED TO
 PROVIDE 2 COPIES.
  
 C) SINGLE HUNG WINDOWS. ONLY ONE COPY WAS SUBMITTED.
 NEED TO PROVIDE 2 COPIES.
  
 D) CONCRETE ROOF TILE. ONLY ONE COPY WAS SUBMITTED.
 NEED TO PROVIDE 2 COPIES.
  
 E) ROOF TILE ADHESIVE AS SPECIFIED BY THE ARCHITECT OF
 RECORD ON COVER PAGE OF NOA SUBMITTED. SEE NOA FOR
 LISTED ADHESIVES.
  
 F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES.
  
 9- ARCHITECT OF RECORD TO REVIEW ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- ARCHITECT TO CLARIFY WHAT ARE THE THREE ADDITIONAL
 LINES SHOWN IN THE WALL BY THE NEW MASTER BEDROOM
 CLOSET. PROVIDE WALL LEGEND. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By jgomez Date 2017-01-25 Time 15:01 Rev Time 0.00
Received By jgomez Date 2017-01-25 Time 07:54 Sent To  
Notes
2017-01-25 08:04:08RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM.
 AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH COUNTY
 (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- SPECIFY TYPE AND SIZE OF WINDOW FOR BEDROOM #3 TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE THE FOLLOWING INFORMATION FOR THE CONVERSION
 OF GARAGE TO BEDROOM:
 A) CONVERSION OF GARAGE TO LIVABLE AREA CHANGES THE
 RISK CATEGORY FROM RISK CATEGORY I TO RISK CATEGORY II.
 PLANS SUBMITTED STILL SHOW THE GARAGE DOOR. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 GARAGE DOOR WILL COMPLY WITH THE WIND LOADS REQUIRED BY
 R301.1 FBC-RESIDENTIAL.
  
 B) CONVERSION OF GARAGE TO LIVABLE AREA: PLANS
 SUBMITTED STILL SHOW THE GARAGE DOOR. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS SHOWING HOW THE GARAGE DOOR
 WILL COMPLY WITH ALL THE REQUIREMENTS OF THE ENERGY
 CODE FOR THE BUILDING THERMAL ENVELOPE SEC. R103.2
 FBC-ENERGY CONSERVATION. NOTE: COORDINATE WITH THE
 ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 EXISTING GARAGE EXTERIOR WALLS AND CEILING SHOWING
 COMPLIANCE WITH THE INSULATION REQUIREMENTS SHOWN ON
 THE ENERGY CALCULATIONS. SEC. R103.2 FBC-ENERGY
 CONSERVATION.
  
 4- ENERGY CALCULATIONS SUBMITTED;
 A) OWNER OR LEGALLY DESIGNATED AGENT NEEDS TO CERTIFY
 AT BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS TO
 PROVIDE HIS NAME, LICENSE NUMBER, ETC AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS.
  
 C) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER NAME AND BUILDER NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) FLOOR PLANS SHOW THE EXISTING GARAGE DOOR TO REMAIN.
 NEED TO INCLUDE THE INFORMATION OF THE GARAGE DOOR IN
 THE BUILDING THERMAL ENVELOPE. PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE THERMAL
 ENVELOPE. COORDINATE WITH ARCHITECT OF RECORD AND ITEM
 # 3 ABOVE TO AVOID CONFLICTS/DELAYS. SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) ATTIC INFORMATION ON PAGE 3 OF 5 IS CONSIDERING A
 VENT RATIO OF 1/300. TYPICALLY THE VENT RATIO REQUIRED
 BY SEC. R806.2 FBC-RESIDENTIAL IS 1/150. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 EXISTING HOUSE COMPLIES WITH THE CONDITIONS REQUIRED BY
 THE EXCEPTION ON SEC. R806.2 FBC-RESIDENTIAL TO
 CONSIDER THE 1/300 VENTILATION RATIO.
  
 F) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-10 Cont ID  
Sent By rlecky Date 2017-01-10 Time 14:16 Rev Time 0.00
Received By rlecky Date 2017-01-10 Time 13:45 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2017-06-21 Cont ID  
Sent By fmittner Date 2017-06-21 Time 10:01 Rev Time 0.00
Received By fmittner Date 2017-06-21 Time 10:01 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-06-06 Cont ID  
Sent By jgomez Date 2017-06-09 Time 15:25 Rev Time 0.00
Received By fmittner Date 2017-06-06 Time 14:19 Sent To  
Notes
2017-06-06 14:20:15SENT TO JULIO
2017-06-02 11:04:17ROUTED TO FREDERIKE MITTNER

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-04-05 Cont ID  
Sent By fmittner Date 2017-04-05 Time 10:01 Rev Time 0.00
Received By fmittner Date 2017-04-05 Time 10:01 Sent To  
Notes
2017-03-27 18:07:51PLANS WERE REVISED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2017-01-30 Cont ID  
Sent By fmittner Date 2017-01-30 Time 14:46 Rev Time 0.00
Received By fmittner Date 2017-01-30 Time 14:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-06-30 Cont ID  
Sent By jgomez Date 2017-06-30 Time 18:19 Rev Time 0.00
Received By jgomez Date 2017-06-29 Time 11:44 Sent To  
Notes
2017-06-30 11:44:29IMPACT FEES ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-06-23 Cont ID  
Sent By jgomez Date 2017-06-23 Time 15:09 Rev Time 0.00
Received By jgomez Date 2017-06-16 Time 11:32 Sent To  
Notes
2017-06-20 11:32:59RESUB ROUTED TO FMITTNER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-06-09 Cont ID  
Sent By jgomez Date 2017-06-09 Time 15:25 Rev Time 0.00
Received By jgomez Date 2017-06-01 Time 16:08 Sent To HIST
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-05-18 Cont ID  
Sent By jgomez Date 2017-05-18 Time 15:18 Rev Time 0.00
Received By jgomez Date 2017-05-05 Time 16:39 Sent To  
Notes
2017-05-08 16:39:40JGOMEZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-01 Cont ID  
Sent By jgomez Date 2017-05-01 Time 18:10 Rev Time 0.00
Received By jgomez Date 2017-04-14 Time 11:07 Sent To  
Notes
2017-04-17 11:07:44RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-12 Cont ID  
Sent By jgomez Date 2017-04-05 Time 10:58 Rev Time 0.00
Received By jgomez Date 2017-03-14 Time 11:32 Sent To  
Notes
2017-04-12 10:59:05HISTORIC AND ZONING REVIEWS DONE ON 04/05/17. JG.
2017-03-20 11:34:51R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-02 Cont ID  
Sent By jgomez Date 2017-02-02 Time 15:31 Rev Time 0.00
Received By jgomez Date 2016-12-29 Time 10:17 Sent To  
Notes
2016-12-30 10:18:14R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 7 Status P Date 2017-06-30 Cont ID  
Sent By jgomez Date 2017-06-30 Time 18:17 Rev Time 0.00
Received By jgomez Date 2017-06-30 Time 18:17 Sent To  
Notes
2017-06-30 18:18:22NO FEES DUE. MU-2017-018299.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status F Date 2017-06-23 Cont ID  
Sent By jgomez Date 2017-06-23 Time 15:09 Rev Time 0.00
Received By jgomez Date 2017-06-23 Time 15:09 Sent To  
Notes
2017-06-23 15:09:261- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM.
 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2017-06-09 Cont ID  
Sent By jgomez Date 2017-06-09 Time 15:25 Rev Time 0.00
Received By jgomez Date 2017-06-09 Time 15:24 Sent To  
Notes
2017-06-09 15:25:441- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM.
 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2017-05-18 Cont ID  
Sent By jgomez Date 2017-05-18 Time 15:16 Rev Time 0.00
Received By jgomez Date 2017-05-18 Time 15:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-05-01 Cont ID  
Sent By jgomez Date 2017-05-01 Time 10:29 Rev Time 0.00
Received By jgomez Date 2017-05-01 Time 10:29 Sent To  
Notes
2017-05-01 10:30:101- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM.
 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-03-27 Cont ID  
Sent By jgomez Date 2017-03-27 Time 19:09 Rev Time 0.00
Received By jgomez Date 2017-03-27 Time 19:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By jgomez Date 2017-01-25 Time 18:05 Rev Time 0.00
Received By jgomez Date 2017-01-25 Time 18:05 Sent To  
Notes
2017-01-25 18:05:471- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM.
 AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH COUNTY
 (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-01 Cont ID  
Sent By jgomez Date 2017-05-01 Time 15:11 Rev Time 0.00
Received By jgomez Date 2017-05-01 Time 15:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-27 Cont ID  
Sent By jgomez Date 2017-03-27 Time 19:10 Rev Time 0.00
Received By jgomez Date 2017-03-27 Time 19:10 Sent To HIST
Notes
2017-03-27 19:15:09RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS.
 A) ONLY THE EQUIPMENT SIZING SUMMARY WAS SUBMITTED.
 NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING
 CALCULATIONS. SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE
 HIS NAME, LICENSE NUMBER, ETC AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 C) MASTER BEDROOM NEEDS TO COMPLY WITH THE BALANCED
 RETURN AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION
 (2014). NOTE: ALL THE SUPPLY AIR INTO THE MASTER
 BEDROOM SHALL BE INCLUDED. THIS INCLUDES MASTER BATH
 AND CLOSET. SEE EXCEPTION #3 OF SEC. M1602.4 AND REVISE
 THE SIZE OF THE TRANSFER DUCT SPECIFIED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By jgomez Date 2017-02-02 Time 15:08 Rev Time 0.00
Received By jgomez Date 2017-02-02 Time 15:06 Sent To  
Notes
2017-02-02 15:31:35RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS.
 A) ONLY THE EQUIPMENT SIZING SUMMARY WAS SUBMITTED.
 NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MANUFACTURER AND MODEL
 NUMBER AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH EQUIPMENT LISTED ON DRAWING M.1
 TO AVOID CONFLICTS/DELAYS.
  
 B) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE
 HIS NAME, LICENSE NUMBER, ETC AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
  
 C) MASTER BEDROOM NEEDS TO COMPLY WITH THE BALANCED
 RETURN AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION
 (2014). NOTE: ALL THE SUPPLY AIR INTO THE MASTER
 BEDROOM SHALL BE INCLUDED. THIS INCLUDES MASTER BATH
 AND CLOSET. SEE EXCEPTION #3 OF SEC. M1602.4 AND REVISE
 THE SIZE OF THE TRANSFER DUCT SPECIFIED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-20 Time 14:07 Rev Time 0.00
Received By gjohnson Date 2017-01-20 Time 14:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-06-09 Cont ID  
Sent By jgomez Date 2017-06-09 Time 15:26 Rev Time 0.00
Received By jgomez Date 2017-06-09 Time 15:26 Sent To  
Notes
2017-06-09 15:27:041- ROOF TILE NOA 16-0711.05.
  
 2- ROOF TILE ADHESIVE NOA 17-0322.03

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By jgomez Date 2017-05-18 Time 15:18 Rev Time 0.00
Received By jgomez Date 2017-05-18 Time 15:16 Sent To  
Notes
2017-05-18 15:18:591- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) NEW COMMENT BASED ON ENERGY CALCULATIONS AND
 ARCHITECT'S REVISIONS FOR ROOF VENTILATION. NEED
 PRODUCT APPROVAL FOR NEW ROOF VENTS AS SPECIFIED ON
 PLANS. NOTE: MAKE SURE VENTS ARE DESIGNED FOR CONCRETE
 ROOF TILE.
  
 B) ORIGINAL COMMENT: CONCRETE ROOF TILE. ONLY ONE COPY
 WAS SUBMITTED. NEED TO PROVIDE 2 COPIES.
 RESPONSE: THE COVER PAGE AND THE REST OF THE PAGES OF
 THE SECOND COPY SUBMITTED DON'T MATCH. OVER PAGE
 SUBMITTED IS FOR NOA 16-0711.05 BUT THE FOLLOWING PAGE
 ARE FOR NOA 12-0222.03. PROVIDE COMPLETE AND CORRECT
 NOA'S (2 COPIES).
  
 C) ORIGINAL COMMENT: ROOF TILE ADHESIVE AS SPECIFIED BY
 THE ARCHITECT OF RECORD ON COVER PAGE OF NOA SUBMITTED.
 SEE NOA FOR LISTED ADHESIVES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 2- ARCHITECT OF RECORD TO REVIEW ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-04-05 Cont ID  
Sent By fmittner Date 2017-04-05 Time 10:01 Rev Time 0.00
Received By fmittner Date 2017-04-05 Time 10:01 Sent To  
Notes
2017-03-27 18:07:41PLANS WERE REVISED. JG.

Review Stop Z ZONING
Rev No 1 Status N Date 2017-01-30 Cont ID  
Sent By fmittner Date 2017-01-30 Time 14:46 Rev Time 0.00
Received By fmittner Date 2017-01-30 Time 14:46 Sent To  
Notes
***NONE***