Plan Review Details - Permit 16120874
Plan Review Stops For Permit 16120874
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-28 Cont ID  
Sent By hmoser Date 2017-01-05 Time 10:23 Rev Time 0.00
Received By pleduc Date 2016-12-28 Time 14:32 Sent To M
Notes
2016-12-28 14:40:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) IF THERE IS AN EXISTING FIRE ALARM IN THE BUILDING
 OR OCCUPANCY, IT SHALL ACTIVATE WITH THE FIRE
 SUPPRESSION ACTIVATION PER NFPA 96.
  
 10.6 SYSTEM ANNUNCIATION.
 10.6.1 UPON ACTIVATION OF AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM, AN AUDIBLE ALARM OR VISUAL
 INDICATOR SHALL BE PROVIDED TO SHOW THAT THE SYSTEM HAS
 ACTIVATED.
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCY WHERE THE EXTINGUISHING SYSTEM IS
 LOCATED, THE ACTIVATION OF THE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM SHALL ACTIVATE THE FIRE ALARM
 SIGNALING SYSTEM.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-05 Cont ID  
Sent By hmoser Date 2017-01-05 Time 10:23 Rev Time 0.00
Received By hmoser Date 2016-12-27 Time 13:49 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-01-05 Cont ID  
Sent By hmoser Date 2017-01-05 Time 10:22 Rev Time 0.00
Received By hmoser Date 2017-01-05 Time 10:00 Sent To  
Notes
***NONE***