Plan Review Details - Permit 16120833
Plan Review Stops For Permit 16120833
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-20 Cont ID  
Sent By pleduc Date 2017-01-20 Time   Rev Time 0.00
Received By pleduc Date 2017-01-20 Time 13:09 Sent To M
Notes
2017-01-20 13:23:22THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) A "NO PRESSURE TEST" NOTE IS INDICATED ON THE
 SUBMITTAL.
  
 PER NFPA 13, A "NO PRESSURE TEST" IS NOT INDICATED IN
 ANY CODE REFERENCE.
  
 PER NFPA 13, WHERE A SYSTEM CAN NOT BE ISOLATED A
 "SYSTEM WORKING PRESSURE TEST" SHALL BE DONE.
  
  
 SPRINKLER TESTING
 24.2 ACCEPTANCE REQUIREMENTS.
 24.2.1* HYDROSTATIC TESTS.
 24.2.1.1 UNLESS PERMITTED BY 24.2.1.2 THROUGH 24.2.1.8,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
  
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
 24.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE
 PRESSURE OR VISUAL LEAKAGE.
  
  
 PLEASE ENSURE A PRESSURE GAUGE IS PROVIDED AND THE
 SYSTEM WORKING PRESSURE IS IDENTIFIED. A TEST WILL
 CONDUCTED FOR 2 HOURS DOCUMENTING ANY PRESSURE LOSS OR
 VISUAL LEAKAGE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-28 Cont ID  
Sent By pleduc Date 2016-12-28 Time   Rev Time 0.00
Received By pleduc Date 2016-12-28 Time 16:12 Sent To M
Notes
2016-12-28 16:45:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS A CALL-OUT NOTE - 01 - INDICATING
 PRELIMIARY FIRE PROTECTION PLAN AND IN PARENTHESES "FOR
 REFERENCE ONLY - COMPLETE ENGINEERED FIRE PROTECTION
 SHOP DRAWING PLANS TO BE PROVIDED FOR REVIEW AND
 APPROVAL"
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
 2) PLEASE PROVIDE MANUFACTURES SPEC SHEETS FOR ALL
 INSTALLED EQUIPMENT FOR FEILD VERIFICATION PURPOSES.
  
  
  
 3) PER NFPA 13 THERE ARE MORE THAN 20 HEADS AND THE
 MODIFICATIONS SUCH AS RELOCATED DROPS THAT CAN NOT BE
 ISOLATED SHALL NOT REQUIRE TESTING IN EXCESS OF WORKING
 PRESSURE.
  
 AN ISOLATION VALVE CAN NOT BE INSTALLED ON AN ARM OVER,
 BUT IT CAN BE INSTALLED FOR THE ENTIRE SYSTEM IF
 POSSIBLE AND APPLICABLE.
  
 THE INSTALLTION IS LIMITED TO AN OCCUPANCY THAT MAY
 HAVE AN ISOLATION VALVE OR ONE THAT CAN BE INSTALLED
 FOR TESTING OF 200PSI FOR 2 HOURS.
  
 PLEASE REVIEW THIS INSTALLATION AND PROVIDE AN
 ISOLATION VALVE IF POSSIBLE AND APPLICABLE.
  
 PROVIDE A NOTE INDICATING IF ONE WILL BE INSTALLED OR
 WHY IT CAN NOT BE INSTALLED.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-27 Cont ID  
Sent By hmoser Date 2017-01-27 Time 15:26 Rev Time 0.00
Received By hmoser Date 2017-01-18 Time 09:19 Sent To  
Notes
2017-01-19 09:20:02RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-05 Cont ID  
Sent By hmoser Date 2017-01-05 Time 09:50 Rev Time 0.00
Received By hmoser Date 2016-12-22 Time 15:25 Sent To  
Notes
2016-12-22 15:25:58ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-01-27 Cont ID  
Sent By hmoser Date 2017-01-27 Time 15:26 Rev Time 0.00
Received By hmoser Date 2017-01-27 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-05 Cont ID  
Sent By hmoser Date 2017-01-05 Time 09:50 Rev Time 0.00
Received By hmoser Date 2017-01-05 Time 09:46 Sent To  
Notes
2017-01-05 09:50:06PLAN DENIED
 PROVIDE THE SIZE OF ARMOUERS ON THE PLAN.
 PER SECTION 107 FBC 2014
 REFER TO FIRE COMMENTS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676