Plan Review Details - Permit 16120785
Plan Review Stops For Permit 16120785
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-23 Cont ID  
Sent By   Date 2017-02-23 Time   Rev Time 0.00
Received By   Date 2017-02-22 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-09 Cont ID  
Sent By jwitmer Date 2017-02-09 Time 14:19 Rev Time 0.00
Received By jwitmer Date 2017-02-09 Time 12:15 Sent To  
Notes
2017-02-09 14:22:27BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120785 (2) COVERED PAVILIONS
 ADD: 5100 N. HAVERHILL RD.
 CONT: STRATICON LLC
 TEL: 772-210-0700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. FEB. 09/2017
 ACTION: DENIED
  
 NOTE!!!!!!!! A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 1) COMPLIED.
  
 2) 2ND REQUEST. 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 8. STRUCTURAL REQUIREMENTS COLUMNS, BEAMS AN ROOF
 FRAMING MEMBERS, COMPONENTS AND CLADDING.
  
 3) 2ND REQUEST. MISSING: 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING ASSEMBLIES.
  
 4) 2ND REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) 2ND REQUEST. SHEET S-1.01 GAZEBO FOUNDATION NOTES.
 GAZEBO FOUNDATIONS ARE ESTIMATED SIZE AND MUST BE
 VERIFIED USING SPECIALTY ENGINEER COLUMN BASE LOADS.
 THIS REVIEW CYCLE THERE WERE NO PLANS NOR CALCULATIONS
 FOR THE GAZEBO. WITHOUT ANY PLANS IT IS UNKNOWN IF THE
 METAL DECK ROOFING IS STRUCTURAL, PURLIN SPACING IS
 UNKNOWN NOR THE SIZE OF ANY HIPS AND OR IF THERE ARE
 ANY HORIZONTAL STEEL BEAMS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-18 Cont ID  
Sent By jwitmer Date 2017-01-18 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2017-01-18 Time 14:11 Sent To  
Notes
2017-01-18 15:54:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120785 (2) COVERED PAVILIONS
 ADD: 5100 N. HAVERHILL RD.
 CONT: STRATICON LLC
 TEL: 772-210-0700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. JAN. 18/2016
 ACTION: DENIED
  
 1) THERE ARE 2 PAVILIONS AND ONE BUILDING WITH
 RESTROOMS UNDER THE SAME ADDRESS. EACH BUILDING NEEDS
 IT OWN ADDRESS FOR IDENTIFICATION DURING CONSTRUCTION
 AS WELL AS FOR POLICE AND FIRE RESPONSE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION OF THE PROJECT.
  
 2) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 8. STRUCTURAL REQUIREMENTS COLUMNS, BEAMS AN ROOF
 FRAMING MEMBERS, COMPONENTS AND CLADDING.
  
 3) MISSING: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING ASSEMBLIES.
  
 4) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) SHEET S-1.01 GAZEBO FOUNDATION NOTES. GAZEBO
 FOUNDATIONS ARE ESTIMATED SIZE AND MUST BE VERIFIED
 USING SPECIALTY ENGINEER COLUMN BASE LOADS. THIS REVIEW
 CYCLE THERE WERE NO PLANS NOR CALCULATIONS FOR THE
 GAZEBO. WITHOUT ANY PLANS IT IS UNKNOWN IF THE METAL
 DECK ROOFING IS STRUCTURAL, PURLIN SPACING IS UNKNOWN
 NOR THE SIZE OF ANY HIPS AND OR IF THERE ARE ANY
 HORIZONTAL STEEL BEAMS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2017-02-23 Cont ID  
Sent By rlecky Date 2017-02-23 Time 15:51 Rev Time 0.00
Received By rlecky Date 2017-02-23 Time 15:50 Sent To  
Notes
2017-02-23 15:51:36NO ELECTRICAL INCLUDED WITH THIS SUBMITTAL FOR REVIEW.
 RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-27 Cont ID  
Sent By vperez Date 2017-01-27 Time 12:01 Rev Time 0.00
Received By vperez Date 2017-01-27 Time 12:01 Sent To  
Notes
2017-01-27 12:01:49INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM,
 ACCESS CONTROLS (GATES), CCTV, PHONE AND DATA, WIRELESS
 SYSTEMS, ETC. LIFT STATION A NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC
 107.
 4. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 5. PROVIDE GENERAL NOTES FOR HIGH LEG MARKING TO COMPLY
 WITH NEC 110.15 AND NEC 408.3F1
 6. GFCI PROTECTION FOR EWC TO BE ACCESSIBLE, SHOW AT
 PANEL ON A GFCI BREAKER. NEC 210.8
 7. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE
 REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR ALL
 UNDERGROUND WORK.
 8. ADDRESS FIRE, MECHANICAL AND BUILDING COMMENTS
 RELATED TO ELECTRICAL.
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-03-01 Cont ID  
Sent By wjolin Date 2017-03-01 Time 12:27 Rev Time 0.00
Received By wjolin Date 2017-03-01 Time 12:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-02-07 Cont ID  
Sent By wjolin Date 2017-02-07 Time 15:55 Rev Time 0.00
Received By wjolin Date 2017-02-07 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-01-24 Cont ID  
Sent By wjolin Date 2017-01-24 Time 15:09 Rev Time 0.00
Received By wjolin Date 2017-01-24 Time 14:43 Sent To  
Notes
2017-01-24 15:09:275100 NORTH HAVERHILL ROAD - TWO PAVILLIONS
 PERMIT #16120785
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 1 SECTION 8.2.3.1.1 APPROVED FIRE DEPARTMENT
 ACCESS ROADS AND FIRE HYDRANTS SHALL BE PROVIDED FOR
 EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING
 HEREAFTER CONSTRUCTED OR RELOCATED. A FIRE DEPARTMENT
 ACCESS ROAD SHALL EXTEND TO WITHIN 50 FEET OF AT LEAST
 ONE EXTERIOR DOOR THAT CAN BE OPENED FROM THE OUTSIDE
 AND THAT PROVIDES ACCESS TO THE INTERIOR OF THE
 BUILDING. WHEN BUILDINGS ARE PROTECTED THROUGHOUT WITH
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM THAT IS
 INSTALLED IN ACCORDANCE WITH NFPA 13, THE DISTANCE
 SHALL BE PERMITTED TO BE INCREASED TO 450 FEET.
  
 PROVIDE SEPARATE ADDRESSES OR BUILDING IDENTIFICATIONS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-01 Cont ID  
Sent By lmarchan Date 2017-03-01 Time 12:35 Rev Time 0.00
Received By lmarchan Date 2017-02-21 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-14 Cont ID  
Sent By lmarchan Date 2017-02-14 Time 08:31 Rev Time 0.00
Received By lmarchan Date 2017-02-07 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-27 Cont ID  
Sent By vperez Date 2017-01-27 Time 12:02 Rev Time 0.00
Received By vperez Date 2017-01-27 Time 12:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-18 Cont ID  
Sent By jwitmer Date 2017-01-18 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2017-01-18 Time 14:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-03-01 Cont ID  
Sent By lmarchan Date 2017-03-01 Time 12:35 Rev Time 0.00
Received By lmarchan Date 2017-03-01 Time 12:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-01-24 Cont ID  
Sent By ajones Date 2017-01-24 Time 11:10 Rev Time 0.00
Received By ajones Date 2017-01-24 Time 11:10 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved