Plan Review Details - Permit 16120779
Plan Review Stops For Permit 16120779
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-30 Cont ID  
Sent By jwitmer Date 2016-12-30 Time 15:34 Rev Time 0.00
Received By jwitmer Date 2016-12-30 Time 14:25 Sent To  
Notes
2016-12-30 15:32:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120779
 ADD: 5601 S. DIXIE HWY/ SUITE # 5613 (PCN:
 74-43-44-04-04-07-0010)
 CONT: TAB CONSTRUCTION/ CRC 038041
 TEL: 561-389-0518
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 30/2016
 ACTION: DENIED
  
 1) PLEASE CORRECT THE SITE ADDRESS AND UNIT ADDRESS SEE
 ADDRESS LISTED ABOVE. 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED.
  
 2) THE PERMIT APPLICATION UNDER THE HEADING OF
 LICENSURE LIST A CRC LICENSE, CERTIFIED RESIDENTIAL
 CONTRACTOR, PLEASE NOTE THIS IS OUT OF THE SCOPE OF
 WORK ALLOWED FOR A CRC LICENSE, SEE FLORIDA STATUTE
 489. 105 (3)(C) RESIDENTIAL CONTRACTOR MEANS A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO CONSTRUCTION,
 REMODELING, REPAIR, OR IMPROVEMENT OF ONE-FAMILY,
 TWO-FAMILY, OR THREE-FAMILY RESIDENCES NOT EXCEEDING
 TWO HABITABLE STORIES ABOVE NO MORE THAN ONE
 UNINHABITABLE STORY AND ACCESSORY USE STRUCTURES IN
 CONNECTION THEREWITH. PLEASE HAVE A QUALIFIED
 CONTRACTOR APPLY FOR THE BUILDING PERMIT.
  
 3) THE CONTRACTOR/ QUALIFIER WHO IS GOING TO PULL THE
 PERMIT AND SUPERVISE/ OVERSEE THE WORK IS THE ONE WHO
 CAN DRAW UP THE PLANS. THEY WILL NEED TO PRINT THEIR
 NAME, SIGN THEIR NAME AND PRINT THEIR LICENSE NUMBER ON
 THE PLANS THEY HAVE DRAWN. A CONTRACTOR CAN ONLY DRAW
 UP THE PLANS FOR WHICH THEY ARE LICENSED. 107.3.4
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
  
 4) THE PLANS INDICATE THIS IS NOT A CHANGE OF OCCUPANCY
 BUT A CHANGE OF USE WITHIN THE SAME OCCUPANCY
 CLASSIFICATION . GOOGLE INDICATES THE LAST KNOWN USE
 FOR THIS TENANT SPACE TO BE A PSYCHIC. THE NEW USE IS
 TO BE GUSTOS GRILL, BOTH ARE UNDER THE BUSINESS
 OCCUPANCY. PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING
 WHERE ALL KITCHEN EQUIPMENT WILL BE LOCATED, GRILLS,
 HOODS, STOVES, WORK TABLES, SINKS AND STORAGE FOR THE
 KITCHEN AREA. PLEASE PROVIDE WHERE THE TABLES AND
 CHAIRS WILL BE LOCATED IN THE PLAN AND PICK-UP AREA FOR
 TAKE OUT DINNERS. PLEASE SHOW THE EGRESS FOR THE PUBLIC
 AS WELL AS IN THE KITCHEN AREA. 107..3.5.1.1 MINIMUM
 REQUIREMENTS FOR COMMERCIAL PLAN REVIEW.
 4A) PLEASE PROVIDE HOW THE PUBLIC WILL GAIN ENTRY INTO
 THE RESTROOM WITHOUT GOING THROUGH THE KITCHEN WORK
 AREA.
  
 5) THE VALUE STATED FOR THE PROJECT IS EXTREMELY LOW
 FOR THE NEW CONSTRUCTION OF WALLS, PLUMBING,ELECTRICAL,
 MECHANICAL, EQUIPMENT, REFRIGARATION TABLES AND CHAIRS.
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 6) THE PLANS WILL ALSO NEED TO SHOW COMPLIANCE WITH
 2014 FBC-ACCESSIBLITY CODE SECTION:
 6A) 226.1. WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 6B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 6C) 227.1. WHERE PROVIDED, CHECK-OUT AISLES, SALES
 COUNTERS, SERVICE COUNTERS, FOOD SERVICE LINES, QUEUES,
 AND WAITING LINES SHALL COMPLY WITH 227 AND 904.
  
 6D) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6E) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 7A) MEANS OF EGRESS IS NOT ALLOWED THROUGH KITCHENS
 1014.2 NOR CAN THE RESTROOMS OPEN INTO ROOMS USED FOR
 THE PREPARATION OF FOOD FOR SERVICE TO THE PUBLIC.
 1210.4.
  
 7B) THE PROPOSED RESTROOM VESTIBULE IS NOT LARGE
 ENOUGH, DOES NOT COMPLY WITH ACCESSIBILITY CODE 404.2.6
 (A) DOORS IN SERIES.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-03 Cont ID  
Sent By rlecky Date 2017-01-03 Time 13:06 Rev Time 0.00
Received By rlecky Date 2017-01-03 Time 12:07 Sent To  
Notes
2017-01-03 13:08:0516120779
 5601 SOUTH DIXIE HWY
 COMMERCIAL REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN OCCUPANCY SENSOR FOR THE RESTROOM FBC
 405.2.2.2.
  
 PROVIDE A 20 AMPERE DEDICATED SIGN CIRCUIT. NEC 600.5
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-28 Cont ID  
Sent By pleduc Date 2016-12-28 Time   Rev Time 0.00
Received By pleduc Date 2016-12-27 Time 17:07 Sent To  
Notes
2016-12-28 10:29:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THIS APPEARS TO BE A CHANGE OF OCCUPANCY. THERE IS
 NO REFERENCE TO THE CURRENT EDITION OF THE FLORIDA FIRE
 PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PER THE FFPC THIS WOULD APPEAR TO BE CLASSIFIED AS A
 MERCANTILE OCCUPANCY. PLEASE PROVIDE THE APPLICABLE
 NOTE AND ENSURE COMPLIANCE WITH THE CODE.
  
 6.1.10.1* DEFINITION ? MERCANTILE OCCUPANCY. AN
 OCCUPANCY USED FOR THE DISPLAY AND SALE OF MERCHANDISE.
  
 A.6.1.10.1 MERCANTILE OCCUPANCY. MERCANTILE OCCUPANCIES
 INCLUDE THE FOLLOWING:
 (1) AUCTION ROOMS
 (2) DEPARTMENT STORES
 (3) DRUGSTORES
 (4) RESTAURANTS WITH FEWER THAN 50 PERSONS
 (5) SHOPPING CENTERS
 (6) SUPERMARKETS
  
  
  
  
 2) BASED ON THE NAME, THIS APPEARS TO BE RESTAURANT;
 HOWEVER, THERE IS INDICATIONS OF THE LOCATION OF
 EQUIPMENT OR TYPE OF COOKING. THE NAME INCLUDES THE
 WORD "GRIL".
  
 FOOD PRODUCTION CREATING GREASE LADEN VAPORS SHALL HAVE
 A HOOD SYSTEM INSTALLED PER NFPA 96.
  
 NFPA 101, CHAPTER 36, NEW MERCANTILE OCCUPANCIES.
 36.3.2.3 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENTIS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 PLEASE PROVIDE THE ABOVE INFORMATION AND THE TYPE AND
 METHOD OF FOOD PRODUCTION.
  
  
  
 3) THERE IS NO INDICATIONS OF SEATING.
  
 PLEASE PROVIDE THE SEATING PLAN IF APPLICABLE.
  
  
  
 4) THERE IS NO INDICATIONS OF THE TYPE OF EXIT HARDWARE
 ON THE EXIT DOORS.
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18
 THROUGH 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 PLEASE PROVIDE THE APPLICABLE INFORMATION
  
  
  
 5) THERE IS NO INDICATION OF FIRE EXTINGUISHERS
 PROTECTION. THE SPECIFIC TYPE AND SIZE WOULD BE
 DETERMINED FOR THE KITCHEN AREA (TYPE OF COOKING)
 AND/OR THE REMAINIG OCCUPANCY AREA.
  
 36.3.5.3 PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED
 IN ALL MERCANTILE OCCUPANCIES IN ACCORDANCE WITH
 9.7.4.1.
  
 PLEASSE PROVIDE THE TYPE AND LOCATION.
  
  
  
  
 6) THIS PROJECT APPEARS TO BE LOCATED IN A STRIP MALL
 TYPE OCCUPANCY. PLEASE PROVIDE THE WALL FIRE RATING
 SEPARATION OF THE ADJACENT BUSINESSES.
  
 PER TABLE 6.1.14.4.1, THE SEPARATION OF
 MERCANTILE/BUSINESS IS 2 HOURS; HOWEVER, *WHERE THE
 BUILDING IS TWO STORIES OR LESS IN HEIGHT AND THE TOTAL
 BUILDING SQUARE FOOTAGE IS LESS THAN 10,000 SQUARE
 FEET, NO SEPARATION IS REQUIRED.
  
 PLEASE PROVIDE THE APPLICABLE INFORAMTION.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 17:14 Rev Time 0.00
Received By gjohnson Date 2016-12-21 Time 13:10 Sent To  
Notes
2016-12-22 13:10:30B09

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 16:59 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 16:59 Sent To  
Notes
2017-01-12 17:09:051ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE FLOOR PLAN SHOWING ALL PLUMBING FIXTURES
 INCLUDING SINK THAT THE GREASE INTERCEPTOR IS BEING
 CONNECTED TO. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE WATER AND SANITARY RISER DIAGRAM . PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 3. PROVIDE MANUFACTURE SPEC FOR GREASE INTERCEPTOR. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SIZING CALCULATIONS AND PLAN MUST BE DESIGNED BY A
 DESIGN PROFESSIONAL OR PLUMBING CONTRACTOR THE SIZING
 CALCULATION COULD BE DONE BY MANUFACTURE. PER WPB AMEND
 TO FBC 107.3.4.3
  
 5. COMPLY WITH BUILDING AND FIRE COMMENTS. PER WPB
 AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  