Plan Review Details - Permit 16120771
Plan Review Stops For Permit 16120771
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2017-01-04 Cont ID  
Sent By pleduc Date 2017-01-04 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2017-01-03 Time 08:36 Sent To  
Notes
2017-01-04 07:28:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120771
 ADD: 825 S. DIXIE HWY.
 CONT: TENTLOGIX, INC.
 TEL: 561-723-3003
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. JAN. 04/ 2017
 ACTION: PROVISOS
  
 1) PROVIDE THE NAME AND QUALIFICATIONS OF THE SPECIAL
 INSPECTOR THAT YOU HAVE ELECTED TO USE FOR THRESHOLD
 INSPECTIONS WHICH ARE A STATUTORY REQUIREMENT DUE TO
 THE NUMBER OF OCCUPANTS. THRESHOLD BUILDING / FL S. S.
 553.71(7).
  
 2) 2014 FBC-B SECTION 3103 TEMPORARY STRUCTURES.
 3103.1. TENTS AND OTHER MEMBRANE STRUCTURES ERECTED FOR
 A PERIOD OF LESS THAN 180 DAYS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 3) LOSBERGER MAXIFLEX FRAME STRUCTURES STRUCTURAL
 EVALUATION REPORT, A TRUE ELECTRONIC VERSION IS ON FILE
 UNDER THIS PERMIT UNDER ATTACHMENTS, BUILDING OFFICIAL
 ROBERT BROWN HAS REVIEWED THE WIND DESIGN CRITERIA AND
 CLASSIFIED THIS STRUCTURE TO MEET THE WIND REQUIREMENTS
 OF 3105.4.2.1 SINCE THIS IS NON-HURRICANE SEASON AND
 THE EVENT IS FOR 3 DAYS ONLY.
  
 4) REVIEWED FOR ACCESSIBLE PARKING ON SITE. DEAR MR.
 BROWN:
 THERE IS ESSENTIALLY NO ON-SITE PARKING FOR AT THE
 EVENT SITE. SELF-PARKERS WILL PARK AT ESPERANTE
 CORPORATE CENTER, CITY PLACE AND THE DREYFOOS SCHOOL.
 THERE IS VALET PARKING AVAILABLE ON THE LOT IMMEDIATELY
 NORTH OF THE EVENT SITE FOR APPROXIMATELY 300 CARS. THE
 LOT IS GRASS AND MUST BE PARKED ON BY ATTENDANTS. THERE
 ARE, HOWEVER THIRTEEN LINED, PAVED SPOTS ON THIS LOT (3
 OF WHICH ARE ALREADY MARKED AS ACCESSIBLE. WE COULD PUT
 TEMPORARY SIGNS ON ALL THE OTHER SPOTS AND RESERVE THIS
 AS ACCESSIBLE PARKING.
 THANK YOU,
 DAVID TESSEO
 DIRECTOR OF OPERATIONS
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-11 Cont ID  
Sent By vperez Date 2017-01-11 Time 17:10 Rev Time 0.00
Received By vperez Date 2017-01-11 Time 17:10 Sent To  
Notes
2017-01-11 17:11:53PROVISO:
  
 CONTRACTOR AGREED TO PROVIDE AS-BUILT FOR RISER DIAGRAM
 AND BONDING AND GROUNDING ARRANGEMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-03 Cont ID  
Sent By vperez Date 2017-01-03 Time 12:16 Rev Time 0.00
Received By vperez Date 2017-01-03 Time 12:16 Sent To  
Notes
2017-01-03 12:15:56INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE PROVIDE A ONE-LINE DIAGRAM REFLECTING ALL
 PANELBOARDS, CONDUIT AND CONDUCTOR SIZE ARRANGEMENT.
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA.
 2. PROVIDE A PANEL SCHEDULE REFLECTING ALL ELECTRICAL
 LOADS; EXAMPLE LIGHTING, RECEPTACLES AND MECHANICAL
 EQUIPMENT. LOAD CALCULATIONS REQUIRED TO BE WITHIN
 GENERATOR CAPACITY. FBC 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA.
 3. SHOW BONDING AND GROUNDING SCHEME FOR THE GENERATOR
 AND ANY CONDUCTIVE METAL PARTS OF THE TENT. FOLLOW NEC
 250 REQUIREMENTS.
 4. PROVIDE A FIXTURE SCHEDULE AND PRODUCT DATA SHEETS
 REFLECTING ALL LIGHTING FIXTURES BEING USED. LISTINGS
 WILL BE VERIFIED. FBC 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA.
 5. PROVIDE GENERAL NOTES TO COMPLY WITH ALL APPLICABLE
 TEMPORARY REQUIREMENTS PER NEC 590, REGARDING GFCI
 PROTECTION, PROTECTION AGAINST ACCIDENTAL DAMAGE
 (CORDS), LAMP PROTECTION, SUPPORTS ETC.
 6. EXITS SIGNS AND EM LIGHTING ADDRESSED UNDER FIRE
 REVIEW COMMENTS.
 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-30 Cont ID  
Sent By pleduc Date 2016-12-30 Time   Rev Time 0.00
Received By pleduc Date 2016-12-27 Time 08:07 Sent To  
Notes
2016-12-30 16:46:28THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) FINAL APPROVAL IS PENDING SITE FIRE INSPECTIONS AND
 VERIFICATION AS NECASSARY PRIOR TO EVENT START.
2016-12-27 08:19:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE LOCATION OF THE GENERATORS DO NOT INDICATE ANY
 SEPARATION DIMENSIONS OR EXHAUST LOCATIONS. PLEASE
 PROVIDE THEM SHOWING COMPLOIANCE WITH THE BELOW NOTED
 CODE.
  
 11.7 STATIONARY GENERATORS AND STANDBY POWER SYSTEMS.
 11.7.1 STATIONARY COMBUSTION ENGINES AND GAS TURBINES
 INSTALLATION. STATIONARY GENERATOR SETS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 37, STANDARD FOR THE
 INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES
 AND GAS TURBINES, AND NFPA 70.
  
 11.7.2.2 PORTABLE GENERATORS SHALL BE POSITIONED SO
 THAT THE EXHAUST IS DIRECTED AS FOLLOWS:
 (1) AT LEAST 5 FT (1.5 M) IN ANY DIRECTION AWAY FROM
 ANY OPENINGS OR AIR INTAKES
 (2) AWAY FROM THE BUILDING
  
  
  
 2) A 1,000 KW GENERATOR IS LOCATED NEXT TO THE TENT.
 PLEASE SEPARATE AND PROVIDE THE REQUIRED MINIMUM
 DIMENSION NOTED BELOW AND FUEL CAPACITY AND TIME ON THE
 PLAN.
  
 25.1.12 GENERATORS.
 25.1.12.1 GENERATORS AND OTHER INTERNAL COMBUSTION
 POWER SOURCES SHALL BE SEPARATED FROM TEMPORARY
 MEMBRANE STRUCTURES AND TENTS BY A MINIMUM OF 5 FT (1.5
 M) AND SHALL BE PROTECTED FROM CONTACT BY FENCING,
 ENCLOSURE, OR OTHER APPROVED MEANS.
 25.1.12.2 FUELING. FUEL TANKS SHALL BE OF ADEQUATE
 CAPACITY TO PERMIT UNINTERRUPTED OPERATION DURING
 NORMAL OPERATING HOURS. REFUELING SHALL BE CONDUCTED
 ONLY WHEN NOT IN USE.
 25.1.12.3 FIRE EXTINGUISHERS. A MINIMUM OF ONE PORTABLE
 FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN
 2-A:10-B:C SHALL BE PROVIDED.
  
  
  
  
 3) PLEASE INDICATE WITH A NOTE COMPLIANCE WITH THE
 BELOW NOTED CODE.
  
 14.14 MARKING OF MEANS OF EGRESS.
 14.14.1 GENERAL.
 14.14.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN ACCORDANCE WITH SECTION 14.14 WHERE REQUIRED
 IN CHAPTERS 11 THROUGH 43 OF NFPA 101. [101:7.10.1.1]
 14.14.1.2 EXITS.
 14.14.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
 [101:7.10.1.2.1]
  
  
  
 4) PLEASE INDICATE WITH A NOTE COMPLIANCE WITH THE
 BELOW NOTED CODE.
  
  
 14.13 EMERGENCY LIGHTING.
 14.13.1 GENERAL.
 14.13.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 14.13 FOR THE FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43 OF NFPA 101
  
  
  
 5) PLEASE INDICATE WHAT NFPA OCCUPANCY CODE YOU ARE
 PROPOSING TO COMPLY FOR THIS EVENT.
  
  
  
 6) PLEASE PROVIDE THE TENT DIMENSIONS AND YOUR
 OCCUPANCY LOAD CALCULATIONS TO CONFIRM COMPLIANCE WITH
 NFPA 101
  
  
  
 7) PLEASE PROVIDE THE DIMENSIONS OF THE EXIT DOORS
 CLEARLY AS THERE ARE TOO SMALL TO READ AND TO CONFIRM
 EXIT CAPACITY.
  
  
  
 8) THERE IS AN EXIT DOOR INDICATED AT THE RESTROOMS
 THAT APPEAR TO OPEN UP TO SOME SORT OF STRUCTURE OR
 FENCED AREA. PLEASE IDENTIFY THIS AREA AS IT APPEARS TO
 LIMIT THE EXITING OF PEOPLE.
  
  
  
 9) THERE IS A TENT INDICATED AS KITCHEN PREP. PLEASE
 CONFIRM OR EXPLAIN THAT NO COOKING WILL TAKE PLACE
 UNDER THIS TENT OR ANY OTHER TENT.
  
  
  
 10) PLEASE CONFIRM AND INDICATE THE LOCATION OF ALL NO
 SMOKING SIGNS.
  
  
  
 11) PLEASE PROVIDE THE TYPE OF EXIT HARDWARE FOR EACH
 OF THE DOORS.
  
  
  
 12) PLEASE PROVIDE EACH OF THE ISLE WIDTHS AS THEY ARE
 TOO SMALL AND UNCLEAR AND NEED TO BE CONFIRMED.
  
  
  
 13) PLEASE PROVIDE THE NATURE OF THE EVENT AND THE
 PROPOSED PRODUCTS OR USE OF THE BOOTHS.
  
  
  
 14) PLEASE PROVIDE THE LOCATION OF POWER CORDS/CABLES
 AND HOW THEY WILL BE PROTECTED FROM DAMAGE AND/OR
 PEDESTRIAN TRAFFIC.
  
  
  
 15) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 16) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-11 Cont ID  
Sent By vperez Date 2017-01-11 Time 17:12 Rev Time 0.00
Received By vperez Date 2017-01-11 Time 17:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-04 Cont ID  
Sent By jwitmer Date 2017-01-04 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2016-12-21 Time 13:02 Sent To  
Notes
2016-12-22 13:02:1512/30 - B16
 ROUTED TO TEMP TENT INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-01-03 Cont ID  
Sent By skennedy Date 2017-01-03 Time 12:33 Rev Time 0.00
Received By skennedy Date 2017-01-03 Time 12:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-12-31 Cont ID  
Sent By tklarge Date 2016-12-31 Time 03:44 Rev Time 0.00
Received By tklarge Date 2016-12-31 Time 03:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-01-03 Cont ID  
Sent By ajones Date 2017-01-03 Time 16:28 Rev Time 0.00
Received By ajones Date 2017-01-03 Time 16:28 Sent To  
Notes
***NONE***