| 2016-12-30 16:46:28 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | 1) FINAL APPROVAL IS PENDING SITE FIRE INSPECTIONS AND |
| | VERIFICATION AS NECASSARY PRIOR TO EVENT START. |
| 2016-12-27 08:19:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE LOCATION OF THE GENERATORS DO NOT INDICATE ANY |
| | SEPARATION DIMENSIONS OR EXHAUST LOCATIONS. PLEASE |
| | PROVIDE THEM SHOWING COMPLOIANCE WITH THE BELOW NOTED |
| | CODE. |
| | |
| | 11.7 STATIONARY GENERATORS AND STANDBY POWER SYSTEMS. |
| | 11.7.1 STATIONARY COMBUSTION ENGINES AND GAS TURBINES |
| | INSTALLATION. STATIONARY GENERATOR SETS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH NFPA 37, STANDARD FOR THE |
| | INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES |
| | AND GAS TURBINES, AND NFPA 70. |
| | |
| | 11.7.2.2 PORTABLE GENERATORS SHALL BE POSITIONED SO |
| | THAT THE EXHAUST IS DIRECTED AS FOLLOWS: |
| | (1) AT LEAST 5 FT (1.5 M) IN ANY DIRECTION AWAY FROM |
| | ANY OPENINGS OR AIR INTAKES |
| | (2) AWAY FROM THE BUILDING |
| | |
| | |
| | |
| | 2) A 1,000 KW GENERATOR IS LOCATED NEXT TO THE TENT. |
| | PLEASE SEPARATE AND PROVIDE THE REQUIRED MINIMUM |
| | DIMENSION NOTED BELOW AND FUEL CAPACITY AND TIME ON THE |
| | PLAN. |
| | |
| | 25.1.12 GENERATORS. |
| | 25.1.12.1 GENERATORS AND OTHER INTERNAL COMBUSTION |
| | POWER SOURCES SHALL BE SEPARATED FROM TEMPORARY |
| | MEMBRANE STRUCTURES AND TENTS BY A MINIMUM OF 5 FT (1.5 |
| | M) AND SHALL BE PROTECTED FROM CONTACT BY FENCING, |
| | ENCLOSURE, OR OTHER APPROVED MEANS. |
| | 25.1.12.2 FUELING. FUEL TANKS SHALL BE OF ADEQUATE |
| | CAPACITY TO PERMIT UNINTERRUPTED OPERATION DURING |
| | NORMAL OPERATING HOURS. REFUELING SHALL BE CONDUCTED |
| | ONLY WHEN NOT IN USE. |
| | 25.1.12.3 FIRE EXTINGUISHERS. A MINIMUM OF ONE PORTABLE |
| | FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN |
| | 2-A:10-B:C SHALL BE PROVIDED. |
| | |
| | |
| | |
| | |
| | 3) PLEASE INDICATE WITH A NOTE COMPLIANCE WITH THE |
| | BELOW NOTED CODE. |
| | |
| | 14.14 MARKING OF MEANS OF EGRESS. |
| | 14.14.1 GENERAL. |
| | 14.14.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| | MARKED IN ACCORDANCE WITH SECTION 14.14 WHERE REQUIRED |
| | IN CHAPTERS 11 THROUGH 43 OF NFPA 101. [101:7.10.1.1] |
| | 14.14.1.2 EXITS. |
| | 14.14.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS, |
| | SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY |
| | VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. |
| | [101:7.10.1.2.1] |
| | |
| | |
| | |
| | 4) PLEASE INDICATE WITH A NOTE COMPLIANCE WITH THE |
| | BELOW NOTED CODE. |
| | |
| | |
| | 14.13 EMERGENCY LIGHTING. |
| | 14.13.1 GENERAL. |
| | 14.13.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| | EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 14.13 FOR THE FOLLOWING: |
| | (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| | 11 THROUGH 43 OF NFPA 101 |
| | |
| | |
| | |
| | 5) PLEASE INDICATE WHAT NFPA OCCUPANCY CODE YOU ARE |
| | PROPOSING TO COMPLY FOR THIS EVENT. |
| | |
| | |
| | |
| | 6) PLEASE PROVIDE THE TENT DIMENSIONS AND YOUR |
| | OCCUPANCY LOAD CALCULATIONS TO CONFIRM COMPLIANCE WITH |
| | NFPA 101 |
| | |
| | |
| | |
| | 7) PLEASE PROVIDE THE DIMENSIONS OF THE EXIT DOORS |
| | CLEARLY AS THERE ARE TOO SMALL TO READ AND TO CONFIRM |
| | EXIT CAPACITY. |
| | |
| | |
| | |
| | 8) THERE IS AN EXIT DOOR INDICATED AT THE RESTROOMS |
| | THAT APPEAR TO OPEN UP TO SOME SORT OF STRUCTURE OR |
| | FENCED AREA. PLEASE IDENTIFY THIS AREA AS IT APPEARS TO |
| | LIMIT THE EXITING OF PEOPLE. |
| | |
| | |
| | |
| | 9) THERE IS A TENT INDICATED AS KITCHEN PREP. PLEASE |
| | CONFIRM OR EXPLAIN THAT NO COOKING WILL TAKE PLACE |
| | UNDER THIS TENT OR ANY OTHER TENT. |
| | |
| | |
| | |
| | 10) PLEASE CONFIRM AND INDICATE THE LOCATION OF ALL NO |
| | SMOKING SIGNS. |
| | |
| | |
| | |
| | 11) PLEASE PROVIDE THE TYPE OF EXIT HARDWARE FOR EACH |
| | OF THE DOORS. |
| | |
| | |
| | |
| | 12) PLEASE PROVIDE EACH OF THE ISLE WIDTHS AS THEY ARE |
| | TOO SMALL AND UNCLEAR AND NEED TO BE CONFIRMED. |
| | |
| | |
| | |
| | 13) PLEASE PROVIDE THE NATURE OF THE EVENT AND THE |
| | PROPOSED PRODUCTS OR USE OF THE BOOTHS. |
| | |
| | |
| | |
| | 14) PLEASE PROVIDE THE LOCATION OF POWER CORDS/CABLES |
| | AND HOW THEY WILL BE PROTECTED FROM DAMAGE AND/OR |
| | PEDESTRIAN TRAFFIC. |
| | |
| | |
| | |
| | 15) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 16) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |