Plan Review Details - Permit 16120745
Plan Review Stops For Permit 16120745
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2017-02-10 Cont ID  
Sent By cthroop Date 2017-02-10 Time 14:25 Rev Time 0.00
Received By cthroop Date 2017-02-08 Time 14:08 Sent To Z
Notes
2017-02-10 15:36:58SEPERATE PERMIT REQUIRED FOR GENERATOR ENCLOSURE.
 HOLD PERMIT # 16120745 UNTIL APPLICATION FOR ENCLOSURE
 IS MADE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-03 Cont ID  
Sent By vperez Date 2017-01-03 Time 10:43 Rev Time 0.00
Received By vperez Date 2017-01-03 Time 10:43 Sent To  
Notes
2017-01-03 10:55:05PROVISO
  
 TAP CONDUCTORS SHOWN FROM METAL WIREWAY TO BOTH ATS TO
 BE WITHIN NEC 240.21B REQUIREMENTS.
  
 PROVIDE SINAGE PER NEC 700.7
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-12 Cont ID  
Sent By wjolin Date 2017-01-12 Time 16:26 Rev Time 0.00
Received By wjolin Date 2017-01-12 Time 15:55 Sent To  
Notes
2017-01-12 16:01:201099 FLORIDA AVENUE
 PERMIT #16120745
 MASTER #15060144
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE COMMAND ROOM REQUIRES GENERATOR SUPERVISION
 DEVICES AND MANUAL START AND TRANSFER FEATURES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-09 Cont ID  
Sent By eschneid Date 2017-02-09 Time 15:27 Rev Time 0.00
Received By eschneid Date 2016-12-21 Time 13:18 Sent To  
Notes
2017-01-24 11:03:14RESUBMIT ROUTED TO ESCHNEIDER VIA ZONING INBOX
2016-12-21 13:18:18IN GENERATOR BOX

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-12-29 Cont ID  
Sent By tklarge Date 2016-12-29 Time 05:57 Rev Time 0.00
Received By tklarge Date 2016-12-29 Time 05:43 Sent To E
Notes
2016-12-29 05:58:40FUEL TANK IS ATTACHED TO BASE OF GENERATOR. PLUMBING
 PERMIT NOT REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-02-09 Cont ID  
Sent By cthroop Date 2017-02-10 Time 15:36 Rev Time 0.50
Received By eschneid Date 2017-02-09 Time 15:25 Sent To  
Notes
2017-02-09 15:27:26THE FENCED GENERATOR ENCLOSURE HAS BEEN SHIFTED TO THE
 WEST FROM THE PLANS APPROVED AS PART OF THE GARAGE
 MINOR AMENDMENT. PRIOR TO C.O. OF THE GARAGE, REVISED,
 AS-BUILT PLANS SHALL BE SUBMITTED TO THE CITY'S
 PLANNING DIVISION AS A MINOR PLANNED DEVELOPMENT
 AMENDMENT.
2017-02-01 11:12:12SENT TO MECHANICAL SO THEY CAN DO THEIR 1ST REVIEW.
2017-01-24 14:52:59ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 1 Status F Date 2017-01-12 Cont ID  
Sent By eschneid Date 2017-01-12 Time 09:54 Rev Time 0.75
Received By eschneid Date 2017-01-12 Time 09:54 Sent To FIRE
Notes
2017-01-12 11:09:24FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) THE SITE PLAN REFERENCES DETAIL SHEET AS003. PLEASE
 PROVIDE THIS SHEET.
  
 2) THE FENCED GENERATOR ENCLOSURE HAS BEEN SHIFTED TO
 THE WEST FROM THE PLANS APPROVED AS PART OF THE GARAGE
 MINOR AMENDMENT. PRIOR TO C.O. OF THE GARAGE, REVISED,
 AS-BUILT PLANS SHALL BE SUBMITTED TO THE CITY'S
 PLANNING DIVISION AS A MINOR PLANNED DEVELOPMENT
 AMENDMENT.
  
 3) THE SHIFTED GENERATOR ENCLOSURE IS NOT REFLECTED ON
 THE LANDSCAPE PLANS SUBMITTED AS PART OF THE LANDSCAPE
 PERMIT. ALL PLANS MUST SHOW THE SAME CONDITIONS.
  
 4) THE CITY'S LAND DEVELOPMENT REGULATIONS REQUIRE
 LANDSCAPE SCREENING AROUND THE GENERATOR ENCLOSURE. THE
 SHIFTED GENERATOR ENCLOSURE IS LOCATED WHERE THE
 EXISTING LANDSCAPE PLAN SHOWS THE LANDSCAPE SCREENING
 FOR THE WESTERN SIDE OF THE ENCLOSURE. THE CURB THAT
 HAS BEEN EXTENDED TO THE WEST OF THE GENERATOR DOES NOT
 INDICATE THAT IT CONTAINS LANDSCAPE. PROVIDE
 VERIFICATION THAT LANDSCAPE SCREENING WILL BE PROVIDED
 ON THE WEST SIDE OF THE ENCLOSURE.
  
 5) HOW TALL IS THE WEATHER PROOF ENCLOSURE TO THE
 HIGHEST POINT (APPEARS TO BE THE RAIN SHROUDS)? THE
 FULL HEIGHT OF THE WEATHERPOOF ENCLOSURE MUST BE
 SCREENED BY AN OPAQUE FENCE, WHICH REQUIRES A SEPARATE
 FENCE PERMIT, WITH PLANS.
  
 6) THE ELECTRICAL RISER DIAGRAM SHOWS A UTILITY PAD
 WITH MOUNTED TRANSFORMER, THE METER AND OTHER
 ELECTRICAL BOXES MOUNTED TO ABOVE GROUND EQUIPMENT
 RACKS. THESE ARE CURRENTLY NOT SHOWN ON THE SITE PLAN.
 ALL OF THESE MUST BE SHOWN ON THE SITE AND LANDSCAPE
 PLANS AND SCREENED FROM VIEW WITH LANDSCAPE AND THE
 LANDSCAPE PLAN MUST BE UPDATED ACCORDINGLY.
  
 7) WHAT MATERIAL IS PLANNED FOR THE OPAQUE FENCE
 ENCLOSURE?
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
2017-01-03 15:33:56ROUTED TO ERIC SCHNEIDER