| 2016-12-28 16:11:22 | BUILDING PLAN REVIEW |
| | W. P. B. SUBMITTAL: 16120744 |
| | W. P. B. PERMIT: 16020418 / STADIUM, NATIONALS |
| | CLUBHOUSE & PRACTICE FIELDS |
| | W. P. B. PERMIT: 16020419/ ASTROS CLUBHOUSE |
| | W. P. B. PERMIT: 16020417/ TEAM STORE & BAR |
| | |
| | ADD: 5444 N. HAVERHILL RD. |
| | CONT: HUNT CONSTRUCTION |
| | TEL: 561-568-8045 / MICHAEL SANCHEZ |
| | E-MAIL: [email protected] |
| | |
| | HCS ARCHITECT/ INTERIOR DESIGNER |
| | ASSOCIATE ARCHITECT/ INTERIOR DESIGNER |
| | GLIDDEN SPINA INTERIORS |
| | |
| | STRUCTURAL ENGINEER |
| | BLISS & NYITRAY, INC |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: TUES-WED. DEC. 27-28/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) I'VE STARTED MY REVIEW WITH THE PRODUCT APPROVALS |
| | FOR THE BALLPARK OF THE PALM BEACHES. THE ONE THING |
| | THAT SEEMS TO BE MISSING IS EITHER THE ARCHITECTURAL OR |
| | STRUCTURAL SHEETS THAT WILL PROVIDE THE PRESSURES FOR |
| | THE 3 ROOF ZONES AND 2 WALL ZONES. EXCEPT FOR THE ROOF |
| | NONE OF THE PRODUCT APPROVALS SUBMITTED SHOWS WHERE |
| | THEY ARE LOCATED IN RELATION TO THE BUILDINGS. FOR |
| | EXAMPLE IS THE ROOF TOP BILCO HATCH LOCATED IN ROOF |
| | ZONE 1, 2 OR 3, THIS INFORMATION WOULD BE HELPFUL IN |
| | CHECKING THE VARIOUS PRODUCTS FOR CODE COMPLIANCE. MIKE |
| | IF YOU COULD HELP ME WITH THESE ITEMS LISTED BELOW I'LL |
| | KEEP GOING THROUGH THE DOCUMENTS TO SEE WHERE THE |
| | TROUBLE AREAS WILL BE TO BE ABLE TO COMPLETE THE REVIEW |
| | IN A TIMELY MANNER. |
| | |
| | 2) THE ROOFING ENGINEERING BY JAMES BUCKNER P. E. |
| | INDICATES THAT THERE IS A DIGITAL SIGNATURE. THE |
| | DIGITAL SIGNATURE WILL NOT OPEN FOR VERIFICATION. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 3) WITH THE ROOFING ENHANCED FASTENING DOCUMENTS FOR |
| | ALL LOCATIONS AND VARIOUS HEIGHTS SUBMITTED, THERE IS 5 |
| | PAGES WITHIN EACH SET OR GROUP OF SIGNED AND SEALED |
| | DOCUMENTS AND ONLY THE COVERSHEET IS SIGNED AND SEALED, |
| | THEY NEED TO COMPLY WITH 61G15-23.002(2) FL. ADMIN. |
| | CODE. A COVER SHEET OR INDEX SHEET FOR ENGINEERING |
| | SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| | SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| | PREPARATION OF EACH SECTION OF THE ENGINEERING |
| | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| | SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| | THE COVER SHEET OR INDEX SHEET. |
| | |
| | 4) SHEET 074114-01 METAL ROOF PANELS PRODUCT DATA |
| | SHEETS BERRIDGE S-DECK FOR CURVED WALK WAYS INDICATES |
| | THERE IS A FLORIDA PRODUCT APPROVAL 6 SHEETS WERE |
| | SUBMITTED BUT NOT WITH A FLORIDA APPROVAL. PLEASE |
| | SUBMIT THE PRODUCT APPROVAL AND IDENTIFY WHICH |
| | SUB-SYSTEM IS BEING INSTALLED. PLEASE ALSO IDENTIFY |
| | IN THE PLANS THE LOCATION THIS PRODUCT WILL BE |
| | INSTALLED, AND IF THERE IS ANY DECKING REQUIREMENTS |
| | UNDERNEATH THIS PRODUCT OR IS IT SECURED TO HORIZONTAL |
| | PURLINS? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: D) ROOFING PRODUCTS AND |
| | ASSEMBLIES. |
| | |
| | |
| | 5) SUBMITTED WITH THE BILCO HATCH DOCUMENTS, SHEET |
| | 077200-02 ROOF HATCH STAIR CUT SHEET WAS SUBMITTED, 4 |
| | PAGES. PLEASE NOTE IN THE FINE PRINT IT STATES THE |
| | STAIRS SOLD BY OTHERS, PLEASE PROVIDE COMPLIANCE WITH |
| | 2014 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS |
| | OR ELEVATED STRUCTURES. PERMANENT LADDERS INSTALLED TO |
| | PROVIDE THE REQUIRED ACCESS. |
| | |
| | |
| | 6) SHEET 077200-01 SAFETY POST AND SAFETY RAILS THE |
| | SAFETY RAILS DOES NOT INDICATE ELEVATION ABOVE THE |
| | FINISH ROOF LEVEL TO THE TOP OF THE GUARDRAIL AND |
| | COMPLIANCE WITH 2014 FBC-B 1013.3 GUARD HEIGHT. |
| | REQUIRED GUARDS SHALL NOT BE LESS THAN 42 INCHES (1067 |
| | MM) HIGH, MEASURED VERTICALLY. |
| | |
| | 7A) SHEET 074213-01 MECHANICAL SCREEN, THE COVERSHEET 1 |
| | OF 13 HAS NOTES FROM THE ARCHITECT TO PROVIDE % OPENING |
| | PERCENTAGE SEE NOTE 7.2 PROFILE IS CLOSER TO THE BASIS |
| | OF DESIGN PREFERRED IF MEETS ALL SPEC REQUIREMENTS. |
| | SHEET 2 AGAIN INDICATES THIS SUBMITTAL DOES NOT MEET |
| | THE 40 % OPENING PERCENTAGE OF THE SPECIFICATIONS. THE |
| | DESIGNER OF RECORD WAS SHOWING THAT THE PANEL 7.2 RIB |
| | MET THE 40 % OF OPENINGS WHEREAS THE CONTRACTOR HAS |
| | CONTINUED TO SUBMIT THE M-36 PANELS WHEN EVEN |
| | HIGHLIGHTED BY THE DESIGN PROFESSIONAL. PLEASE PROVIDE |
| | PRODUCT APPROVALS FOR THIS SYSTEM AND TESTING RESULTS |
| | FOR WIND RESISTANCE. |
| | FL 15598-R3 SUBMITTED. 2014 FBC-B 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: (31)(C) PANEL WALLS: SIDING, SOFFITS |
| | AND PRODUCTS INTRODUCED AS A RESULT OF NEW TECHNOLOGY. |
| | |
| | 7B) PROVIDE PLANS WHERE THIS PRODUCT IS TO BE INSTALLED |
| | AND THE ASSOCIATED PRESSURES FOR THIS WALL ZONE, IT |
| | APPEARS THE ATTACHMENT ANALYSIS IS FOR THE 7.2 STEEL |
| | PRODUCT WITH THE 40 % OPENINGS BUT THE ACTUAL DOCUMENT |
| | THE CONTRACTOR SUBMITTED M-36 FOR PRESSURES WITH ONLY |
| | 23 % OPENINGS. IT APPEARS THERE MAYBE MORE OF A |
| | NARRATIVE FOR THIS PRODUCT , WHY THE DESIGNER IS |
| | REQUESTING THE 7.2 PANEL WITH THE 40% OPENINGS, THE |
| | PRODUCT TESTING SHEETS ARE FOR THE M-36 NEITHER THE |
| | STEEL NOR ALUMINUM IDENTIFIED AND SAFETY FACTOR NOT |
| | GIVEN EITHER. |
| | SHEETS 7 & 8 OF 13 ARE NOT HIGHLIGHTED AS TO THE PURLIN |
| | SPANS FOR EITHER ALUMINUM OR STEEL PANELS. NOR THE |
| | DESIGN SAFETY FACTOR TO BE USED. 1403.3 STRUCTURAL. |
| | EXTERIOR WALLS, AND THE ASSOCIATED OPENINGS, SHALL BE |
| | DESIGNED AND CONSTRUCTED TO RESIST SAFELY THE |
| | SUPERIMPOSED LOADS REQUIRED BY CHAPTER 16. |
| | |
| | 7C) SHEET 074213-05 ROOF SCREENING ENGINEERING |
| | CALCULATIONS BY JAMES BUCKNER STATE THEY ARE DIGITALLY |
| | SIGNED BUT DO NOT OPEN FOR SIGNATURE REVIEW. |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 8) SHEET 08-9100-003 INDICATES GREENHECK EHH-601DE WALL |
| | LOUVER WITH BOTH A FLORIDA APPROVAL19665 AND MIAMI-DADE |
| | NOA 15-1013.12 BUT NO PRODUCT APPROVALS WERE SUBMITTED. |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(C) PANEL WALLS: WALL LOUVERS, |
| | |
| | 9) SHEET 08-3323-05 IS FOR CORNELL SERVICE DOORS PAGES |
| | 1-38 INSTALLATION INSTRUCTIONS, PLEASE PROVIDE |
| | COMPLIANCE WITH : 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(A) |
| | EXTERIOR DOORS . |
| | |
| | 10A) SHEET 084333-01 INSTALLATION INSTRUCTIONS FOR |
| | EURO-C3 BIFOLD ALUMINUM DOOR SYSTEM WAS SUBMITTED BUT |
| | NO PRODUCT APPROVALS. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF |
| | HATCHES. |
| | |
| | 10B) THE INSTALLATION INSTRUCTIONS ALSO INDICATE WATER |
| | PENETRATION NOT TESTED, THE OVERHANG HAS TO BE IN |
| | ACCORDANCE WITH 1710.5.2 EXTERIOR WINDOWS AND DOOR |
| | ASSEMBLIES NOT PROVIDED FOR IN SECTION 1710.5.1.SEE |
| | EXCEPTION #2 . DOOR ASSEMBLIES INSTALLED WHERE THE |
| | OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT |
| | BE TESTED FOR WATER INFILTRATION. |
| | |
| | 11) PRODUCT EVALUATION REPORT FOR EURO-C3 BIFOLD |
| | ALUMINUM DOOR SYSTEM PLEASE SUPPLY EITHER THE FLORIDA |
| | APPROVAL COVERSHEETS OR MIAMI-DADE COVERSHEETS THAT |
| | SHOULD ACCOMPANY THIS REPORT. WITHIN THE REPORT |
| | SUBMITTED TO THE CITY FOR REVIEW COMPLIANCE METHOD |
| | INDICATED IS COMPLIANCE METHOD 61G20-3.005(1)(D) |
| | PRODUCT EVALUATION REPORT BY A LICENSED PROFESSIONAL |
| | ENGINEER. THIS SECTION IS UNDER 61G20-3.005 PRODUCT |
| | EVALUATION AND QUALITY ASSURANCE FOR STATE APPROVAL. IF |
| | THIS PRODUCT HAS NOT ACHIEVED EITHER STATE APPROVAL, |
| | THEN THE MANUFACTURER WOULD BE REQUIRED TO SUBMIT ON |
| | THE WEST PALM BEACH LOCAL/ SITE SPECIFIC PRODUCT |
| | APPROVAL FORMS. PLEASE RESPOND WITH AN E-MAIL ADDRESS |
| | IF THE LOCAL PRODUCT APPROVAL FORMS AND REQUIREMENTS |
| | CAN BE E-MAILED TO YOU AND RETURNED TO THE BUILDING |
| | DEPARTMENT FOR REVIEW AND APPROVAL. |
| | |
| | 12A) 084400-R2 GLASS & ALUMINUM SHOP DRAWING SUBMITTALS |
| | REVIEWED BY HSMC BALLPARK PARTNERS BUT NOT BY EITHER |
| | THE ARCHITECT OF RECORD NOR THE STRUCTURAL ENGINEER. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 12B) WITHIN THE GLASS & ALUMINUM SHOP DRAWING |
| | SUBMITTALS THERE IS REFERENCE TO TWO PRODUCTS; |
| | YKK AP YHS-50 FI OGCS |
| | YKK AP 35H MEDIUM STYLE DOOR |
| | PLEASE PROVIDE PRODUCT APPROVALS FOR BOTH A QUICK |
| | SEARCH ON THE FLORIDA WEBSITE IT DIDN?T APPEAR THEY |
| | WERE LISTED. PLEASE PROVIDE APPROVALS. IF NOT THEN |
| | LOCAL APPROVALS WILL BE REQUIRED. IF THIS PRODUCT HAS |
| | NOT ACHIEVED EITHER STATE APPROVAL, THEN THE |
| | MANUFACTURER WOULD BE REQUIRED TO SUBMIT ON THE WEST |
| | PALM BEACH LOCAL/ SITE SPECIFIC PRODUCT APPROVAL FORMS. |
| | PLEASE RESPOND WITH AN E-MAIL ADDRESS IF THE LOCAL |
| | PRODUCT APPROVAL FORMS AND REQUIREMENTS CAN BE E-MAILED |
| | TO YOU AND RETURNED TO THE BUILDING DEPARTMENT FOR |
| | REVIEW AND APPROVAL. |
| | 2014 FBC-B 1710.5.1 EXTERIOR WINDOWS AND DOORS. |
| | EXTERIOR WINDOWS AND DOORS SHALL BE TESTED BY AN |
| | APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE |
| | LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF |
| | ONE OF THE FOLLOWING SPECIFICATIONS: ANSI/AAMA/NWWDA |
| | 101/I.S. 2 OR ANSI/ AAMA/WDMA/101/I.S.2/NAFS OR |
| | AAMA/WDMA/ CSA101/I.S.2/A440 OR TAS 202 (HVHZ SHALL |
| | COMPLY WITH TAS 202 UTILIZING ASTM E 1300 OR SECTION |
| | 2404). |
| | |
| | 13) 084400-02 YKK20D NARROW STYLE OUTSWING ENTRANCE |
| | DOOR HASN?T PROVIDED IF THIS PRODUCT IS COVERED UNDER |
| | EITHER A FLORIDA STATE APPROVAL OR A MIAMI-DADE NOA. |
| | PLEASE PROVIDE OR SUBMIT FOR A LOCAL PRODUCT APPROVAL. |
| | 2014 FBC-B 1710.5.1 EXTERIOR WINDOWS AND DOORS. |
| | EXTERIOR WINDOWS AND DOORS SHALL BE TESTED BY AN |
| | APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE |
| | LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF |
| | ONE OF THE FOLLOWING SPECIFICATIONS: ANSI/AAMA/NWWDA |
| | 101/I.S. 2 OR ANSI/ AAMA/WDMA/101/I.S.2/NAFS OR |
| | AAMA/WDMA/ CSA101/I.S.2/A440 OR TAS 202. |
| | 14) 084400-04 YKK 45 FS NOA_HKS MONOLITHIC ? NON-IMPACT |
| | GLASS/ ? INCH TEMP. GLAZING. THE INSTALLATION OF THIS |
| | PRODUCT IS UNKNOWN, INTERIOR OR EXTERIOR LOCATION? NO |
| | PLANS SUBMITTED. IF EXTERIOR THEN SHOW COMPLIANCE WITH: |
| | 2014 FBC-B 1710.5.1 EXTERIOR WINDOWS AND DOORS. |
| | EXTERIOR WINDOWS AND DOORS SHALL BE TESTED BY AN |
| | APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE |
| | LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF |
| | ONE OF THE FOLLOWING SPECIFICATIONS: ANSI/AAMA/NWWDA |
| | 101/I.S. 2 OR ANSI/ AAMA/WDMA/101/I.S.2/NAFS OR |
| | AAMA/WDMA/ CSA101/I.S.2/A440 OR TAS 202. |
| | 15) 084400-07 YKK YES 45 TU NON-RATED GLAZING / |
| | TEMPERED IS THIS INTERIOR OR EXTERIOR GLAZING SYSTEM. |
| | 2014 FBC-B 1710.5.1 EXTERIOR WINDOWS AND DOORS. |
| | EXTERIOR WINDOWS AND DOORS SHALL BE TESTED BY AN |
| | APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE |
| | LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF |
| | ONE OF THE FOLLOWING SPECIFICATIONS: ANSI/AAMA/NWWDA |
| | 101/I.S. 2 OR ANSI/ AAMA/WDMA/101/I.S.2/NAFS OR |
| | AAMA/WDMA/ CSA101/I.S.2/A440 OR TAS 202. ( |
| | |
| | 16) 085656-01 BULLET PROOF GLASS SHOP DRAWINGS QUIKSERV |
| | PLEASE PROVIDE COMPLIANCE WITH : 2014 FBC-B 1710.5.1 |
| | EXTERIOR WINDOWS AND DOORS. EXTERIOR WINDOWS AND DOORS |
| | SHALL BE TESTED BY AN APPROVED INDEPENDENT TESTING |
| | LABORATORY, AND SHALL BE LABELED TO INDICATE COMPLIANCE |
| | WITH THE REQUIREMENTS OF ONE OF THE FOLLOWING |
| | SPECIFICATIONS: ANSI/AAMA/NWWDA 101/I.S. 2 OR ANSI/ |
| | AAMA/WDMA/101/I.S.2/NAFS OR AAMA/WDMA/ |
| | CSA101/I.S.2/A440 OR TAS 202. |
| | |
| | 17A) 085656-04 TICKET WINDOW INTERCOM SYSTEM. ON THE |
| | CUT SHEET 3 OF 6 THE SHEET INDICATES THE USE OF A CALL |
| | BUTTON, MICROPHONE, AND SPEAKER PLEASE PROVIDE DETAILS |
| | SHOWING COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE |
| | 308 REACH RANGES FOR FRONT AND SIDE APPROACH AS WELL AS |
| | SECTION 309.1-4 OPERABLE PARTS. |
| | |
| | 17B) 085656-04 TICKET WINDOW INTERCOM SYSTEM. 2014 |
| | FBC-ACCESSIBILITY ASSISTIVE LISTING SYSTEMS, EXCEPTION. |
| | WHERE TICKET OFFICES OR WINDOWS ARE PROVIDED, SIGNS |
| | SHALL NOT BE REQUIRED AT EACH ASSEMBLY AREA PROVIDED |
| | THAT SIGNS ARE DISPLAYED AT EACH TICKET OFFICE OR |
| | WINDOW INFORMING PATRONS OF THE AVAILABILITY OF |
| | ASSISTIVE LISTENING SYSTEMS. |
| | |
| | 18) 089100-001 & 089100-002 MECHANICAL LOUVERS |
| | ESD-635DE NO PRODUCT APPROVALS WERE SUBMITTED, NEITHER |
| | HAS THE DESIGNER OR CONTRACTOR INDICATED IF THE LOUVER |
| | IS A CHANNEL FRAME OR FLANGED SLEEVE. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(C) PANEL WALLS: WALL LOUVERS, |
| | |
| | 19) 092400-10 THIS SUBMITTAL INDICATES THE USE OF STO |
| | ESSENCE IFIS SYSTEMS ARE TO BE INSTALLED. PLEASE |
| | PROVIDE COMPLIANCE WITH: 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(C) PANEL WALLS: EFIS SYSTEMS |
| | |
| | 20A)233400-006 THIS SUBMITTAL INDICATES THE USE OF ROOF |
| | TOP EXHAUST FANS CCD. PLEASE PROVIDE COMPLIANCE WITH: |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOF TOP VENTILATORS & CURBS |
| | |
| | 20B) NO ROOF PLANS WERE SUBMITTED SHOWING THE LOCATION |
| | OF THE ROOF TOP FANS, ROOF ZONES AND ASSOCIATED |
| | PRESSURES. 107.3.5.1.1 MINIMUM CRITERIA FOR COMMERCIAL |
| | PLAN REVIEW (8) ROOF PLAN & SYSTEMS. |
| | |
| | 21A) EXHAUST FAN FOR MASCOT ROOM SUB# 233400-006 |
| | EXHAUST FAN MODEL G-065-YG. PLEASE PROVIDE COMPLIANCE |
| | WITH: 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOF TOP VENTILATORS & CURBS |
| | |
| | 21B) NO ROOF PLANS WERE SUBMITTED SHOWING THE LOCATION |
| | OF THE ROOF TOP FANS, ROOF ZONES AND ASSOCIATED |
| | PRESSURES. 107.3.5.1.1 MINIMUM CRITERIA FOR COMMERCIAL |
| | PLAN REVIEW (8) ROOF PLAN & SYSTEMS. |
| | |
| | 22) GOOSENECK CURB CAP/ SEE SHEET 8OF 11 VERSES SHEET 9 |
| | OF 11. SHEET 9 INDICATES THE GREENHECK ROOF TOP CAP |
| | DOES HAVE BOTH A MIAMI-DADE NOA AND FL STATE APPROVAL W |
| | PRESSURES OF +/- 70 PSF . PLEASE PROVIDE COMPLIANCE |
| | WITH: 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | |
| | 23) REPORT ROOFTOP UNIT CURBS/ CURB TECHNOLOGIES BY |
| | MOHAMAD MAAMOURI P. E. SIGNATURE IS NOT A DIGITAL |
| | SIGNATURE. 61G15-23.005 PROCEDURES FOR SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 24) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |