Plan Review Details - Permit 16120744
Plan Review Stops For Permit 16120744
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-22 Cont ID  
Sent By jwitmer Date 2018-01-22 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2018-01-22 Time 07:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-28 Cont ID  
Sent By jwitmer Date 2016-12-28 Time 16:11 Rev Time 0.00
Received By jwitmer Date 2016-12-27 Time 08:49 Sent To  
Notes
2016-12-28 16:11:22BUILDING PLAN REVIEW
 W. P. B. SUBMITTAL: 16120744
 W. P. B. PERMIT: 16020418 / STADIUM, NATIONALS
 CLUBHOUSE & PRACTICE FIELDS
 W. P. B. PERMIT: 16020419/ ASTROS CLUBHOUSE
 W. P. B. PERMIT: 16020417/ TEAM STORE & BAR
  
 ADD: 5444 N. HAVERHILL RD.
 CONT: HUNT CONSTRUCTION
 TEL: 561-568-8045 / MICHAEL SANCHEZ
 E-MAIL: [email protected]
  
 HCS ARCHITECT/ INTERIOR DESIGNER
 ASSOCIATE ARCHITECT/ INTERIOR DESIGNER
 GLIDDEN SPINA INTERIORS
  
 STRUCTURAL ENGINEER
 BLISS & NYITRAY, INC
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES-WED. DEC. 27-28/ 2016
 ACTION: DENIED
  
 1) I'VE STARTED MY REVIEW WITH THE PRODUCT APPROVALS
 FOR THE BALLPARK OF THE PALM BEACHES. THE ONE THING
 THAT SEEMS TO BE MISSING IS EITHER THE ARCHITECTURAL OR
 STRUCTURAL SHEETS THAT WILL PROVIDE THE PRESSURES FOR
 THE 3 ROOF ZONES AND 2 WALL ZONES. EXCEPT FOR THE ROOF
 NONE OF THE PRODUCT APPROVALS SUBMITTED SHOWS WHERE
 THEY ARE LOCATED IN RELATION TO THE BUILDINGS. FOR
 EXAMPLE IS THE ROOF TOP BILCO HATCH LOCATED IN ROOF
 ZONE 1, 2 OR 3, THIS INFORMATION WOULD BE HELPFUL IN
 CHECKING THE VARIOUS PRODUCTS FOR CODE COMPLIANCE. MIKE
 IF YOU COULD HELP ME WITH THESE ITEMS LISTED BELOW I'LL
 KEEP GOING THROUGH THE DOCUMENTS TO SEE WHERE THE
 TROUBLE AREAS WILL BE TO BE ABLE TO COMPLETE THE REVIEW
 IN A TIMELY MANNER.
  
 2) THE ROOFING ENGINEERING BY JAMES BUCKNER P. E.
 INDICATES THAT THERE IS A DIGITAL SIGNATURE. THE
 DIGITAL SIGNATURE WILL NOT OPEN FOR VERIFICATION.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) WITH THE ROOFING ENHANCED FASTENING DOCUMENTS FOR
 ALL LOCATIONS AND VARIOUS HEIGHTS SUBMITTED, THERE IS 5
 PAGES WITHIN EACH SET OR GROUP OF SIGNED AND SEALED
 DOCUMENTS AND ONLY THE COVERSHEET IS SIGNED AND SEALED,
 THEY NEED TO COMPLY WITH 61G15-23.002(2) FL. ADMIN.
 CODE. A COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET.
  
 4) SHEET 074114-01 METAL ROOF PANELS PRODUCT DATA
 SHEETS BERRIDGE S-DECK FOR CURVED WALK WAYS INDICATES
 THERE IS A FLORIDA PRODUCT APPROVAL 6 SHEETS WERE
 SUBMITTED BUT NOT WITH A FLORIDA APPROVAL. PLEASE
 SUBMIT THE PRODUCT APPROVAL AND IDENTIFY WHICH
 SUB-SYSTEM IS BEING INSTALLED. PLEASE ALSO IDENTIFY
 IN THE PLANS THE LOCATION THIS PRODUCT WILL BE
 INSTALLED, AND IF THERE IS ANY DECKING REQUIREMENTS
 UNDERNEATH THIS PRODUCT OR IS IT SECURED TO HORIZONTAL
 PURLINS? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: D) ROOFING PRODUCTS AND
 ASSEMBLIES.
  
  
 5) SUBMITTED WITH THE BILCO HATCH DOCUMENTS, SHEET
 077200-02 ROOF HATCH STAIR CUT SHEET WAS SUBMITTED, 4
 PAGES. PLEASE NOTE IN THE FINE PRINT IT STATES THE
 STAIRS SOLD BY OTHERS, PLEASE PROVIDE COMPLIANCE WITH
 2014 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. PERMANENT LADDERS INSTALLED TO
 PROVIDE THE REQUIRED ACCESS.
  
  
 6) SHEET 077200-01 SAFETY POST AND SAFETY RAILS THE
 SAFETY RAILS DOES NOT INDICATE ELEVATION ABOVE THE
 FINISH ROOF LEVEL TO THE TOP OF THE GUARDRAIL AND
 COMPLIANCE WITH 2014 FBC-B 1013.3 GUARD HEIGHT.
 REQUIRED GUARDS SHALL NOT BE LESS THAN 42 INCHES (1067
 MM) HIGH, MEASURED VERTICALLY.
  
 7A) SHEET 074213-01 MECHANICAL SCREEN, THE COVERSHEET 1
 OF 13 HAS NOTES FROM THE ARCHITECT TO PROVIDE % OPENING
 PERCENTAGE SEE NOTE 7.2 PROFILE IS CLOSER TO THE BASIS
 OF DESIGN PREFERRED IF MEETS ALL SPEC REQUIREMENTS.
 SHEET 2 AGAIN INDICATES THIS SUBMITTAL DOES NOT MEET
 THE 40 % OPENING PERCENTAGE OF THE SPECIFICATIONS. THE
 DESIGNER OF RECORD WAS SHOWING THAT THE PANEL 7.2 RIB
 MET THE 40 % OF OPENINGS WHEREAS THE CONTRACTOR HAS
 CONTINUED TO SUBMIT THE M-36 PANELS WHEN EVEN
 HIGHLIGHTED BY THE DESIGN PROFESSIONAL. PLEASE PROVIDE
 PRODUCT APPROVALS FOR THIS SYSTEM AND TESTING RESULTS
 FOR WIND RESISTANCE.
 FL 15598-R3 SUBMITTED. 2014 FBC-B 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(C) PANEL WALLS: SIDING, SOFFITS
 AND PRODUCTS INTRODUCED AS A RESULT OF NEW TECHNOLOGY.
  
 7B) PROVIDE PLANS WHERE THIS PRODUCT IS TO BE INSTALLED
 AND THE ASSOCIATED PRESSURES FOR THIS WALL ZONE, IT
 APPEARS THE ATTACHMENT ANALYSIS IS FOR THE 7.2 STEEL
 PRODUCT WITH THE 40 % OPENINGS BUT THE ACTUAL DOCUMENT
 THE CONTRACTOR SUBMITTED M-36 FOR PRESSURES WITH ONLY
 23 % OPENINGS. IT APPEARS THERE MAYBE MORE OF A
 NARRATIVE FOR THIS PRODUCT , WHY THE DESIGNER IS
 REQUESTING THE 7.2 PANEL WITH THE 40% OPENINGS, THE
 PRODUCT TESTING SHEETS ARE FOR THE M-36 NEITHER THE
 STEEL NOR ALUMINUM IDENTIFIED AND SAFETY FACTOR NOT
 GIVEN EITHER.
 SHEETS 7 & 8 OF 13 ARE NOT HIGHLIGHTED AS TO THE PURLIN
 SPANS FOR EITHER ALUMINUM OR STEEL PANELS. NOR THE
 DESIGN SAFETY FACTOR TO BE USED. 1403.3 STRUCTURAL.
 EXTERIOR WALLS, AND THE ASSOCIATED OPENINGS, SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST SAFELY THE
 SUPERIMPOSED LOADS REQUIRED BY CHAPTER 16.
  
 7C) SHEET 074213-05 ROOF SCREENING ENGINEERING
 CALCULATIONS BY JAMES BUCKNER STATE THEY ARE DIGITALLY
 SIGNED BUT DO NOT OPEN FOR SIGNATURE REVIEW.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 8) SHEET 08-9100-003 INDICATES GREENHECK EHH-601DE WALL
 LOUVER WITH BOTH A FLORIDA APPROVAL19665 AND MIAMI-DADE
 NOA 15-1013.12 BUT NO PRODUCT APPROVALS WERE SUBMITTED.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) PANEL WALLS: WALL LOUVERS,
  
 9) SHEET 08-3323-05 IS FOR CORNELL SERVICE DOORS PAGES
 1-38 INSTALLATION INSTRUCTIONS, PLEASE PROVIDE
 COMPLIANCE WITH : 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(A)
 EXTERIOR DOORS .
  
 10A) SHEET 084333-01 INSTALLATION INSTRUCTIONS FOR
 EURO-C3 BIFOLD ALUMINUM DOOR SYSTEM WAS SUBMITTED BUT
 NO PRODUCT APPROVALS. 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF
 HATCHES.
  
 10B) THE INSTALLATION INSTRUCTIONS ALSO INDICATE WATER
 PENETRATION NOT TESTED, THE OVERHANG HAS TO BE IN
 ACCORDANCE WITH 1710.5.2 EXTERIOR WINDOWS AND DOOR
 ASSEMBLIES NOT PROVIDED FOR IN SECTION 1710.5.1.SEE
 EXCEPTION #2 . DOOR ASSEMBLIES INSTALLED WHERE THE
 OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT
 BE TESTED FOR WATER INFILTRATION.
  
 11) PRODUCT EVALUATION REPORT FOR EURO-C3 BIFOLD
 ALUMINUM DOOR SYSTEM PLEASE SUPPLY EITHER THE FLORIDA
 APPROVAL COVERSHEETS OR MIAMI-DADE COVERSHEETS THAT
 SHOULD ACCOMPANY THIS REPORT. WITHIN THE REPORT
 SUBMITTED TO THE CITY FOR REVIEW COMPLIANCE METHOD
 INDICATED IS COMPLIANCE METHOD 61G20-3.005(1)(D)
 PRODUCT EVALUATION REPORT BY A LICENSED PROFESSIONAL
 ENGINEER. THIS SECTION IS UNDER 61G20-3.005 PRODUCT
 EVALUATION AND QUALITY ASSURANCE FOR STATE APPROVAL. IF
 THIS PRODUCT HAS NOT ACHIEVED EITHER STATE APPROVAL,
 THEN THE MANUFACTURER WOULD BE REQUIRED TO SUBMIT ON
 THE WEST PALM BEACH LOCAL/ SITE SPECIFIC PRODUCT
 APPROVAL FORMS. PLEASE RESPOND WITH AN E-MAIL ADDRESS
 IF THE LOCAL PRODUCT APPROVAL FORMS AND REQUIREMENTS
 CAN BE E-MAILED TO YOU AND RETURNED TO THE BUILDING
 DEPARTMENT FOR REVIEW AND APPROVAL.
  
 12A) 084400-R2 GLASS & ALUMINUM SHOP DRAWING SUBMITTALS
 REVIEWED BY HSMC BALLPARK PARTNERS BUT NOT BY EITHER
 THE ARCHITECT OF RECORD NOR THE STRUCTURAL ENGINEER. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 12B) WITHIN THE GLASS & ALUMINUM SHOP DRAWING
 SUBMITTALS THERE IS REFERENCE TO TWO PRODUCTS;
 YKK AP YHS-50 FI OGCS
 YKK AP 35H MEDIUM STYLE DOOR
 PLEASE PROVIDE PRODUCT APPROVALS FOR BOTH A QUICK
 SEARCH ON THE FLORIDA WEBSITE IT DIDN?T APPEAR THEY
 WERE LISTED. PLEASE PROVIDE APPROVALS. IF NOT THEN
 LOCAL APPROVALS WILL BE REQUIRED. IF THIS PRODUCT HAS
 NOT ACHIEVED EITHER STATE APPROVAL, THEN THE
 MANUFACTURER WOULD BE REQUIRED TO SUBMIT ON THE WEST
 PALM BEACH LOCAL/ SITE SPECIFIC PRODUCT APPROVAL FORMS.
 PLEASE RESPOND WITH AN E-MAIL ADDRESS IF THE LOCAL
 PRODUCT APPROVAL FORMS AND REQUIREMENTS CAN BE E-MAILED
 TO YOU AND RETURNED TO THE BUILDING DEPARTMENT FOR
 REVIEW AND APPROVAL.
 2014 FBC-B 1710.5.1 EXTERIOR WINDOWS AND DOORS.
 EXTERIOR WINDOWS AND DOORS SHALL BE TESTED BY AN
 APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE
 LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF
 ONE OF THE FOLLOWING SPECIFICATIONS: ANSI/AAMA/NWWDA
 101/I.S. 2 OR ANSI/ AAMA/WDMA/101/I.S.2/NAFS OR
 AAMA/WDMA/ CSA101/I.S.2/A440 OR TAS 202 (HVHZ SHALL
 COMPLY WITH TAS 202 UTILIZING ASTM E 1300 OR SECTION
 2404).
  
 13) 084400-02 YKK20D NARROW STYLE OUTSWING ENTRANCE
 DOOR HASN?T PROVIDED IF THIS PRODUCT IS COVERED UNDER
 EITHER A FLORIDA STATE APPROVAL OR A MIAMI-DADE NOA.
 PLEASE PROVIDE OR SUBMIT FOR A LOCAL PRODUCT APPROVAL.
 2014 FBC-B 1710.5.1 EXTERIOR WINDOWS AND DOORS.
 EXTERIOR WINDOWS AND DOORS SHALL BE TESTED BY AN
 APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE
 LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF
 ONE OF THE FOLLOWING SPECIFICATIONS: ANSI/AAMA/NWWDA
 101/I.S. 2 OR ANSI/ AAMA/WDMA/101/I.S.2/NAFS OR
 AAMA/WDMA/ CSA101/I.S.2/A440 OR TAS 202.
 14) 084400-04 YKK 45 FS NOA_HKS MONOLITHIC ? NON-IMPACT
 GLASS/ ? INCH TEMP. GLAZING. THE INSTALLATION OF THIS
 PRODUCT IS UNKNOWN, INTERIOR OR EXTERIOR LOCATION? NO
 PLANS SUBMITTED. IF EXTERIOR THEN SHOW COMPLIANCE WITH:
 2014 FBC-B 1710.5.1 EXTERIOR WINDOWS AND DOORS.
 EXTERIOR WINDOWS AND DOORS SHALL BE TESTED BY AN
 APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE
 LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF
 ONE OF THE FOLLOWING SPECIFICATIONS: ANSI/AAMA/NWWDA
 101/I.S. 2 OR ANSI/ AAMA/WDMA/101/I.S.2/NAFS OR
 AAMA/WDMA/ CSA101/I.S.2/A440 OR TAS 202.
 15) 084400-07 YKK YES 45 TU NON-RATED GLAZING /
 TEMPERED IS THIS INTERIOR OR EXTERIOR GLAZING SYSTEM.
 2014 FBC-B 1710.5.1 EXTERIOR WINDOWS AND DOORS.
 EXTERIOR WINDOWS AND DOORS SHALL BE TESTED BY AN
 APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE
 LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF
 ONE OF THE FOLLOWING SPECIFICATIONS: ANSI/AAMA/NWWDA
 101/I.S. 2 OR ANSI/ AAMA/WDMA/101/I.S.2/NAFS OR
 AAMA/WDMA/ CSA101/I.S.2/A440 OR TAS 202. (
  
 16) 085656-01 BULLET PROOF GLASS SHOP DRAWINGS QUIKSERV
 PLEASE PROVIDE COMPLIANCE WITH : 2014 FBC-B 1710.5.1
 EXTERIOR WINDOWS AND DOORS. EXTERIOR WINDOWS AND DOORS
 SHALL BE TESTED BY AN APPROVED INDEPENDENT TESTING
 LABORATORY, AND SHALL BE LABELED TO INDICATE COMPLIANCE
 WITH THE REQUIREMENTS OF ONE OF THE FOLLOWING
 SPECIFICATIONS: ANSI/AAMA/NWWDA 101/I.S. 2 OR ANSI/
 AAMA/WDMA/101/I.S.2/NAFS OR AAMA/WDMA/
 CSA101/I.S.2/A440 OR TAS 202.
  
 17A) 085656-04 TICKET WINDOW INTERCOM SYSTEM. ON THE
 CUT SHEET 3 OF 6 THE SHEET INDICATES THE USE OF A CALL
 BUTTON, MICROPHONE, AND SPEAKER PLEASE PROVIDE DETAILS
 SHOWING COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE
 308 REACH RANGES FOR FRONT AND SIDE APPROACH AS WELL AS
 SECTION 309.1-4 OPERABLE PARTS.
  
 17B) 085656-04 TICKET WINDOW INTERCOM SYSTEM. 2014
 FBC-ACCESSIBILITY ASSISTIVE LISTING SYSTEMS, EXCEPTION.
 WHERE TICKET OFFICES OR WINDOWS ARE PROVIDED, SIGNS
 SHALL NOT BE REQUIRED AT EACH ASSEMBLY AREA PROVIDED
 THAT SIGNS ARE DISPLAYED AT EACH TICKET OFFICE OR
 WINDOW INFORMING PATRONS OF THE AVAILABILITY OF
 ASSISTIVE LISTENING SYSTEMS.
  
 18) 089100-001 & 089100-002 MECHANICAL LOUVERS
 ESD-635DE NO PRODUCT APPROVALS WERE SUBMITTED, NEITHER
 HAS THE DESIGNER OR CONTRACTOR INDICATED IF THE LOUVER
 IS A CHANNEL FRAME OR FLANGED SLEEVE.
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) PANEL WALLS: WALL LOUVERS,
  
 19) 092400-10 THIS SUBMITTAL INDICATES THE USE OF STO
 ESSENCE IFIS SYSTEMS ARE TO BE INSTALLED. PLEASE
 PROVIDE COMPLIANCE WITH: 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(C) PANEL WALLS: EFIS SYSTEMS
  
 20A)233400-006 THIS SUBMITTAL INDICATES THE USE OF ROOF
 TOP EXHAUST FANS CCD. PLEASE PROVIDE COMPLIANCE WITH:
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOF TOP VENTILATORS & CURBS
  
 20B) NO ROOF PLANS WERE SUBMITTED SHOWING THE LOCATION
 OF THE ROOF TOP FANS, ROOF ZONES AND ASSOCIATED
 PRESSURES. 107.3.5.1.1 MINIMUM CRITERIA FOR COMMERCIAL
 PLAN REVIEW (8) ROOF PLAN & SYSTEMS.
  
 21A) EXHAUST FAN FOR MASCOT ROOM SUB# 233400-006
 EXHAUST FAN MODEL G-065-YG. PLEASE PROVIDE COMPLIANCE
 WITH: 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOF TOP VENTILATORS & CURBS
  
 21B) NO ROOF PLANS WERE SUBMITTED SHOWING THE LOCATION
 OF THE ROOF TOP FANS, ROOF ZONES AND ASSOCIATED
 PRESSURES. 107.3.5.1.1 MINIMUM CRITERIA FOR COMMERCIAL
 PLAN REVIEW (8) ROOF PLAN & SYSTEMS.
  
 22) GOOSENECK CURB CAP/ SEE SHEET 8OF 11 VERSES SHEET 9
 OF 11. SHEET 9 INDICATES THE GREENHECK ROOF TOP CAP
 DOES HAVE BOTH A MIAMI-DADE NOA AND FL STATE APPROVAL W
 PRESSURES OF +/- 70 PSF . PLEASE PROVIDE COMPLIANCE
 WITH: 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
  
 23) REPORT ROOFTOP UNIT CURBS/ CURB TECHNOLOGIES BY
 MOHAMAD MAAMOURI P. E. SIGNATURE IS NOT A DIGITAL
 SIGNATURE. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 24) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-01-22 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-20 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2016-12-28 Time 16:04 Rev Time 0.00
Received By lmarchan Date 2016-12-21 Time 12:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-01-22 Cont ID  
Sent By jwitmer Date 2018-01-22 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2018-01-22 Time   Sent To  
Notes
***NONE***