Plan Review Details - Permit 16120736
Plan Review Stops For Permit 16120736
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-29 Cont ID  
Sent By lmarchan Date 2016-12-29 Time 09:30 Rev Time 0.00
Received By lmarchan Date 2016-12-28 Time 09:19 Sent To  
Notes
2016-12-29 09:19:33RESUB OF REVISION ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-22 Cont ID  
Sent By ccole Date 2016-12-22 Time 08:00 Rev Time 0.00
Received By ccole Date 2016-12-20 Time 10:21 Sent To  
Notes
2016-12-21 10:21:46REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-01-03 Cont ID  
Sent By ccole Date 2017-01-03 Time 07:44 Rev Time 0.00
Received By ccole Date 2017-01-03 Time 07:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-22 Cont ID  
Sent By ccole Date 2016-12-22 Time 08:00 Rev Time 0.00
Received By ccole Date 2016-12-22 Time 08:00 Sent To  
Notes
2016-12-22 08:10:431ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #16120736
 MASTER # 16041276
 12/22/16
  
 1) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETUIRN AIR
 SYSTEMS OF RTU'S 1-3 UNLESS MANUFACTURER'S
 SPECIFICATIONS SHOW THE UNITS CANNOT PRODUCE OVER 2000
 CFMS. PLEASE SHOW THE DETECTOR LOCATIONS AS REQUIRED BY
 606.2.1, AND INDICATE HOW THEY WILL BE SUPOERVISED PER
 SECTION 606.4.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  