| Plan Review Stops For Permit 16120734 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-03-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-01 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-03-01 |
Time |
13:54 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-01-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-24 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-20 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2017-01-24 13:10:46 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO (2) SETS OF PRODUCT | | | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA | | | RULE 9N-3 THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE | | | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING | | | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES | | | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, | | | WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR | | | DOOR TYPES. ONLY ONE SET OF PRODUCT APPROVALS WERE | | | SUBMITTED. | | | | | | 2) A PRODUCT APPROVAL WAS SUBMITTED FOR EXTERIOR DOORS, | | | HOWEVER, THERE WAS NO MENTION OF EXTERIOR DOOR | | | REPLACEMENT ON THE PLANS. PLEASE CLARIFY. FBC 107.2.1 | | | | | | 3) THE COVERSHEETS WITH THE FLORIDA PRODUCT APPROVAL | | | NUMBERS ARE MISSING FROM THE JELDWEN CONTOURS STEEL | | | DOOR ( DRAWING NUMBER S-2104 ) AND THE AWP SERIES 2500 | | | ALUMINUM SINGLE HUNG WINDOWS ( DRAWING NUMBER W15-60 ). | | | SUBMIT TWO SETS WITH THE FL NUMBERS. FBC 107.3.4 | | | | | | 4) PRODUCT APPROVALS WERE SUBMITTED FOR TWO DIFFERENT | | | SERIES OF SINGLE HUNG WINDOWS. INDICATE ON THE PLANS | | | THE LOCATIONS OF EACH OF THE DIFFERENT WINDOW TYPES. | | | FBC 107.2.1 | | | | | | 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-03-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-03-02 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-03-02 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-01-05 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2017-01-05 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2017-01-05 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-14 |
Time |
19:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-03-13 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2017-03-14 13:57:31 | IMPACT FEES ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-03-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-02 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-17 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2017-02-21 13:50:32 | RESUB ROUTED TO VPEREZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-01-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-24 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-12-20 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2017-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-14 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-03-14 |
Time |
19:04 |
Sent To |
|
|
| Notes |
| 2017-03-14 19:07:22 | MU2017-6598 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2017-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-28 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-28 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2017-02-28 18:55:49 | BEFORE A PERMIT CAN BE ISSUED, IMPACT FEES MUST BE PAID | | | TO PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF PLANS | | | SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY | | | FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE | | | STAMP AND A COPY OF THE PAID RECEIPT MUST BE RETURNED | | | TO THE CITY BUILDING DEPARTMENT BEFORE THE BUILDING | | | PERMIT CAN BE ISSUED. FOR INFORMATION CALL PALM BEACH | | | COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-01-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-24 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-24 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2017-01-24 10:59:28 | BEFORE A PERMIT CAN BE ISSUED, IMPACT FEES MUST BE PAID | | | TO PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF PLANS | | | SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY | | | FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE | | | STAMP AND A COPY OF THE PAID RECEIPT MUST BE RETURNED | | | TO THE CITY BUILDING DEPARTMENT BEFORE THE BUILDING | | | PERMIT CAN BE ISSUED. FOR INFORMATION CALL PALM BEACH | | | COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-14 |
Time |
19:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-03-14 |
Time |
19:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-03-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-03-01 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-28 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2017-02-28 19:00:00 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | FORMS. FBC ENERGY CONSERVATION SECTION R103.1.1.2 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-01-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-24 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-20 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2017-01-24 10:30:14 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE OWNER'S NAME ON THE ENERGY FORM R405-2014, DIEGO | | | BREITFELD, DOES NOT MATCH THE PERMIT APPLICATION, OWNER | | | BUILDER AFFIDAVIT OR THE PROPERTY APPRAISER. OUR | | | RECORDS SHOW ELIZABETH VICAINO IS THE OWNER. PLEASE | | | CORRECT. | | | | | | 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | FORMS. FBC ENERGY CONSERVATION SECTION R103.1.1.2 | | | | | | 3) PROVIDE TWO SETS OF CONDENSER ANCHORING | | | DETAILS.FBCR-M1307.2 ANCHORAGE OF APPLIANCES. | | | APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE | | | FASTENED OR ANCHORED IN AN APPROVED MANNER. | | | | | | 4) THE EQUIPMENT SIZING CALCULATIONS HAVE A REQUIRED | | | TOTAL COOLING OF 23,017 BTUS OR 1.92 TONS. THE ACTUAL | | | LISTED IS FOR 27,600 BTUS OR 2.3 TONS. THE PLANS | | | SPECIFY A 2.5 TON UNIT WITH 27,600 BTUS. BASED ON THE | | | SIZING CALCULATIONS A 2 TON UNIT WITH 24,000 BTUS | | | SHOULD BE USED. FBC ENERGY CONSERVATION SECTION | | | R403.6.1.1 COOLING EQUIPMENT CAPACITY. COOLING ONLY | | | EQUIPMENT SHALL BE SELECTED SO THAT ITS TOTAL CAPACITY | | | IS NOT LESS THAN THE CALCULATED TOTAL LOAD, BUT NOT | | | MORE THAN 1.15 TIMES GREATER THAN THE TOTAL LOAD | | | CALCULATED ACCORDING TO THE PROCEDURE SELECTED IN | | | SECTION 403.6, OR THE CLOSEST AVAILABLE SIZE PROVIDED | | | BY THE MANUFACTURER'S PRODUCT LINES. THE CORRESPONDING | | | LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE LESS THAN | | | THE CALCULATED LATENT LOAD. | | | | | | |
|
|