Plan Review Details - Permit 16120712
Plan Review Stops For Permit 16120712
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-12 Cont ID  
Sent By rmcdouga Date 2017-01-12 Time 11:26 Rev Time 0.00
Received By rmcdouga Date 2017-01-12 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-28 Cont ID  
Sent By rmcdouga Date 2016-12-28 Time 15:45 Rev Time 0.00
Received By rmcdouga Date 2016-12-28 Time 11:35 Sent To  
Notes
2016-12-28 15:45:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ONE SET OF THE REVISED PLANS IS MISSING SHEET A-1.
 TWO IDENTICAL SETS OF REVISED PLANS ARE REQUIRED TO BE
 SUBMITTED. FBC 107.1
  
 2) ONE SET OF REVISED PLANS HAS TWO DIFFERENT A-3
 SHEETS THAT BOTH HAVE THE SAME REVISION DATE. PLEASE
 REMOVE THE ONE THAT DOES NOT CONTAIN THE CORRECT
 INFORMATION. FBC 107.2.1
  
 3) ON SHEET A-1.1 THE WINDOW ID TAGS FOR THE REVISED
 WINDOWS ARE STILL SHOWN AS D. THESE ARE NOW SINGLE
 WINDOWS AND ARE NOT 60" WIDE SLIDER TYPE. FBC 107.2.1
  
 4) THE DESIGN PRESSURES FOR THE ROOF IN THE TABLE ON
 SHEET S-2 ARE INCORRECT. THE PRESSURES ARE LOW AND DO
 NOT CORRESPOND WITH THE CORRECT PRESSURES THAT LISTED
 ON SHEET S-1. FBC-R 301.2.1
  
 5) THE REVISED PLANS SHOW A DOOR THAT OPENS FROM THE
 GARAGE INTO THE GUEST BEDROOM WHICH IS NOT ALLOWED BY
 CODE. FBC-R302.5.1 OPENING PROTECTION.
 OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM
 USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED.
 OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL
 BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8
 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB-CORE
 STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR
 20-MINUTE FIRE-RATED DOORS, EQUIPPED WITH A
 SELF-CLOSING DEVICE.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-12-27 Cont ID  
Sent By vperez Date 2016-12-27 Time 15:43 Rev Time 0.00
Received By skennedy Date 2016-12-27 Time 15:43 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-01-10 Cont ID  
Sent By rmcdouga Date 2017-01-12 Time 11:26 Rev Time 0.00
Received By destabro Date 2017-01-10 Time 08:43 Sent To B
Notes
2017-01-10 08:44:341/10/2017 - APPLICANT SPOKE WITH MS. FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER, REGARDING
 THE REDESIGN OF THE REAR ELEVATION WINDOWS.
 FENESTRATION DEEMED COMPATIBLE. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-12-27 Cont ID  
Sent By destabro Date 2016-12-27 Time 16:00 Rev Time 0.00
Received By destabro Date 2016-12-27 Time 16:00 Sent To B
Notes
2016-12-27 16:05:1312/27/2016 - PLEASE REVIEW APPROVED CHANGES PER HPB
 CASE 15-47. PLANS PRESENTED WITH PERMIT ALTER THE
 WINDOW PATTERN AT THE WEST ELEVATION AND REQUEST THE
 REMOVAL OF OTHER WINDOW SPACES PREVIOUSLY APPROVED ON
 OTHER ELEVATIONS. REQUESTED CHANGES DO NOT MATCH PLANS
 PRESENTED AND APPROVED BY HPB. PLEASE CALL FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER AT
 561.822.1457 TO DISCUSS PROPOSED REVISIONS TO PLAN AND
 APPROPRIATE WINDOW REPLACEMENT STYLES. DLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-12 Cont ID  
Sent By rmcdouga Date 2017-01-12 Time 11:26 Rev Time 0.00
Received By rmcdouga Date 2017-01-06 Time 10:38 Sent To HIST
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-28 Cont ID  
Sent By rmcdouga Date 2016-12-28 Time 15:45 Rev Time 0.00
Received By rmcdouga Date 2016-12-20 Time 15:14 Sent To  
Notes
2016-12-21 15:14:44R12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-12-27 Cont ID  
Sent By rmcdouga Date 2016-12-27 Time 15:43 Rev Time 0.00
Received By skennedy Date 2016-12-27 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-12-27 Cont ID  
Sent By tklarge Date 2016-12-27 Time 15:43 Rev Time 0.00
Received By skennedy Date 2016-12-27 Time 15:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-10 Cont ID  
Sent By destabro Date 2017-01-10 Time 08:42 Rev Time 0.00
Received By destabro Date 2017-01-10 Time 08:42 Sent To B
Notes
2017-01-10 08:43:191/10/2017 - A/C INSTALLATION ON EXISTING PAD. DLE
2017-01-09 17:04:33ROUTED TO DESIREE ESTABROOK

Review Stop Z ZONING
Rev No 1 Status F Date 2016-12-27 Cont ID  
Sent By destabro Date 2016-12-27 Time 16:14 Rev Time 0.00
Received By destabro Date 2016-12-27 Time 16:14 Sent To B
Notes
2016-12-27 16:18:2112/27/2016 - VARIANCE (HPB CASE NO. 15-46) APPROVED
 4'6" SETBACK FOR NEW CONSTRUCTION, BUT NOT FOR THE A/C
 UNIT. RELOCATED A/C UNIT MUST COMPLY WITH SETBACK
 REQUIREMENTS FOR THE REAR OF THE PROPERTY (15', OR 11'
 WITH 4' ENCROACHMENT) OR BE RELOCATED TO THE NORTH OR
 SOUTH SIDE OF THE NEW CONSTRUCTION. PLEASE DIRECT
 QUESTIONS TO FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER AT 561.822.1457.