| 2016-12-20 16:30:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE IS INSUFFICIENT INFORMATION CONTAINED IN THIS |
| | SUBMITTAL TO COMPLETE ANY KIND OF FORMAL REVIEW OF THE |
| | LIFE SAFETY SYSTEM PUMP REPLACEMENT OF THIS HEALTHCARE |
| | OCCUPANCY. |
| | |
| | THE FOLLOWING IS A BRIEF REVIEW OF THE LIMITED |
| | INFORMATION PROVIDED. |
| | |
| | |
| | THIS IS A LIFE SAFETY SYSTEM THAT FALLS UNDER THE SCOPE |
| | OF FS 61G AND SHALL FOLLOW THE REQUIREMENTS OF THE EOR. |
| | |
| | THIS PROPOSED REPLACEMENT BECOMES THE PUMP OF RECORD |
| | FOR THIS OCCUPANCY AND SHALL BE DOCUMENTED ON OFFICIAL |
| | PLAN SET DRAWINGS ON OFFICIAL TITLE BOLCK SETS OF THE |
| | INSTALLING CONTRACTOR. |
| | |
| | THE SUBMITTED INFORMATION, AT BEST, CAN BE ACCEPTED AS |
| | SUPPLEMENTAL INFORMATION OF THE PROPOSED INSTALLATION. |
| | |
| | |
| | 1) ONLY ONE SET OF INFORMATION WAS SUBMITTED. A MINIMUM |
| | OF TWO SETS SHALL BE SUBMITTED. EACH SET SHALL INCLUDE |
| | AN OFFICIAL TITLE BLOCK, PUMP ROOM AND PUMP DRAWING |
| | LAYOUT OF ALL EQUIPMENT AND WATER DISTRIBUTION PIPING, |
| | INCLUDING A DEMO DRAWING AND THE LOCATION OF EXIT |
| | DOORS, THE MAIN PUMP, JOCKEY PUMP, CONTROLLER PANEL AND |
| | ANY OTHER EQUIPMENT WITHIN THE PUMP ROOM |
| | |
| | PLEASE PROVIDE AN ADDITIONAL SET WITH ALL THE |
| | APPLICABLE INFORMATION. |
| | |
| | |
| | |
| | 2) THERE IS NO REFERENCE OF COMPLIANCE WITH ANY FIRE |
| | CODE. THE INSTALLATION SHALL COMPLY WITH ALL APPLICABLE |
| | NFPA CODE, INCUDING BUT NOT LIMITED TO, NFPA 20, |
| | STANDARD FOR THE |
| | INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION |
| | 2010 EDITION |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE AND ENSURE COMPLIANCE |
| | IS MEET BY DESIGN AND INSTALLATION. |
| | |
| | |
| | |
| | |
| | 3) THE EXISTING PUMP PICTURES INDICATED SOME UNREADABLE |
| | INFORMATION. |
| | |
| | PLEASE PROVIDE EXISTING AND PROPOSED INFORMATION IN A |
| | CLEAR AND READABLE FORMAT. |
| | |
| | |
| | |
| | 4) THE IS NO DRAWING DETAIL OF THE EXISTING AND/OR |
| | PROPOSED PIPING LAYOUT, WATER DISTRIBUTION SYSTEM AND |
| | JOCKEY PUMP |
| | |
| | PER NFPA 20 |
| | |
| | 4.2* APPROVAL REQUIRED. |
| | 4.2.1 STATIONARY PUMPS SHALL BE SELECTED BASED ON THE |
| | CONDITIONS UNDER WHICH THEY ARE TO BE INSTALLED AND |
| | USED. |
| | |
| | 4.2.3 A COMPLETE PLAN AND DETAILED DATA DESCRIBING |
| | PUMP, DRIVER, CONTROLLER, POWER SUPPLY, FITTINGS, |
| | SUCTION AND DISCHARGE CONNECTIONS, AND LIQUID SUPPLY |
| | CONDITIONS SHALL BE PREPARED FOR APPROVAL. |
| | |
| | PLEASE PROVIDE THE APPLICABLE AND ACCURATE INFORMATION. |
| | |
| | |
| | |
| | 5) THERE IS NO INDICATION OF PROVIDING FOR THE |
| | TEMPORARY SUPPORT OF THE SPRINKLER SYSTEM WHILE THE |
| | INSTALLATION IS UNDERWAY UNTIL COMPLETION AND TESTING. |
| | |
| | PLEASE PROVIDE A DETAILED LIFE SAFETY REVIEW OF THE |
| | INSTALLTION AND THE CONTINUE OPERATION AND MAINTENANCE |
| | OF THE CURRENT LIFE SAFETY SYSTEM. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |