Plan Review Details - Permit 16120544
Plan Review Stops For Permit 16120544
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-13 Cont ID  
Sent By cpuell Date 2017-01-13 Time 08:01 Rev Time 0.00
Received By cpuell Date 2017-01-11 Time 08:25 Sent To  
Notes
2017-01-12 08:26:04RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-06 Cont ID  
Sent By lmarchan Date 2017-01-06 Time 09:54 Rev Time 0.00
Received By lmarchan Date 2017-01-04 Time 14:25 Sent To  
Notes
2017-01-05 14:26:14RESUB TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-05 Cont ID  
Sent By lmarchan Date 2017-01-05 Time 14:25 Rev Time 0.00
Received By lmarchan Date 2016-12-14 Time 09:44 Sent To  
Notes
2016-12-15 09:45:01ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-12 Cont ID  
Sent By jvalido Date 2017-01-12 Time 18:30 Rev Time 0.00
Received By jvalido Date 2017-01-12 Time 18:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-01-05 Cont ID  
Sent By jvalido Date 2017-01-05 Time 17:24 Rev Time 0.00
Received By jvalido Date 2017-01-05 Time 17:15 Sent To  
Notes
2017-01-05 17:23:55CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 FLORIDA ENERGY CODE FBC 2014
  
 (1) FORM R405-2014 MUST HAVE OWNER/AGENT SIGNATURE.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-15 Cont ID  
Sent By jvalido Date 2016-12-15 Time 16:32 Rev Time 0.00
Received By jvalido Date 2016-12-15 Time 17:14 Sent To  
Notes
2016-12-15 16:25:44CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS SHOWING CFM VALUES FOR ALL
 SUPPLY OUTLETS IN ALL AREAS OF HOME (EXISTING AND NEW)
 (2) CONFIRM AHU TOTAL DESIGN CFM QUANTITY MATCHES TOTAL
 CFM FOR ALL SUPPLY OUTLETS IN ENTIRE HOME.
 (3) BATHROOM EXHAUST IS 50 CFM MINIMUM ( SEE TABLE
 M1507.4 BELOW)
  
 TABLE M1507.4 MINIMUM REQUIRED LOCAL EXHAUST RATES FOR
 ONE- AND TWO-FAMILY DWELLINGS
  
 AREA TO BE EXHAUSTED EXHAUST RATES
 KITCHENS 100 CFM INTERMITTENT OR 25 CFM CONTINUOUS
 BATHROOMS-TOILET ROOMS MECHANICAL EXHAUST CAPACITY OF
 50 CFM
 INTERMITTENT OR 20 CFM CONTINUOUS
  
 FLORIDA ENERGY CODE FBC 2014
  
 (4) REVISE FORM R405-2014. PROVIDE CORRECT INFORMATION
 FOR HVAC.
 (5) REVISE HEAT LOAD CALCULATIONS SHOW ENTIRE HOME.
 (6) PROVIDE AHRI
 (7) PROVIDE CONDENSER TIE DOWN DETAIL
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  