| 2016-12-20 13:36:24 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. CANNOT VERIFY VALUE. PROVIDE FLOOR PLAN OUTLINING |
| | AREAS OF WORK WITH SQUARE FOOTAGE. |
| | 2. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE |
| | THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC |
| | 107. |
| | 3. STATE TYPE OF UNDERLAYMENT TO BE USED. |
| | 4. PROVIDE THE FOLLOWING ASTM'S FOR THE UNDERLAYMENT |
| | USED FOR THE INSTALLATION OF ENGINEERED WOOD PRODUCTS - |
| | ASTM E-84 (FLAME SPREAD), ASTM E-90 (AIORBOURNE SOUND) |
| | AND E-492 (IMAPCT SOUND). |
| | |
| | THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| | CONTRACTOR WOULD PROVIDE. |
| | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| | RENTAL TO VERIFY VALUE. |
| | |
| | FBC 603.1 FLAME SPREAD ? ASTM E-84 |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 49 |
| | |
| | |
| | |