Plan Review Details - Permit 16120500
Plan Review Stops For Permit 16120500
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-28 Cont ID  
Sent By cthroop Date 2017-02-28 Time 09:49 Rev Time 0.00
Received By cthroop Date 2017-02-28 Time 09:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-11 Cont ID  
Sent By cthroop Date 2017-01-11 Time 13:13 Rev Time 0.00
Received By cthroop Date 2017-01-10 Time 15:07 Sent To P
Notes
2017-01-11 13:20:39BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLUMBING PERMIT REQUIRED.
 2. SPECIAL INSPECTOR AGREEMENT REQUIRED.
  
 THRESHOLD BUILDINGS
 1. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
 2. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
 3. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 4. PROVIDE STRUCTURAL INSPECTION PLAN.
 5. THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD
 BUILDING F.S. 553.71 (12)
 ?THRESHOLD BUILDING? ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND HAS AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 5A) THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS PURSUANT TO
 A STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT.
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S.
 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE
 FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN
 CONRAD, MANAGER OF SPECIAL INSPECTOR PROGRAM AT (561)
 805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY
 BE ISSUED.
 5C) MISSING STATEMENT. THRESHOLD BUILDING, REQUIRED.
 W.P.B. AMENDMENT 110.3.7.4.4. ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, ?TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 F.S.?
 FBC 3309 FIRE EXTINGUISHERS
 [F] 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 5D) NOT COMPLETED. FOR THE SPECIAL INSPECTOR &
 DESIGNATED JOB INSPECTORS - PLEASE PROVIDE A RESUME? OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS. THE RESUME?
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME?. AFTER THE RESUME? IS REVIEWED, AN
 INTERVIEW MAY BE SCHEDULED.
 5E) JOB INSPECTOR ? FBC 110.3.7.6 THE BUILDING
 DEPARTMENT MAY ALLOW A SPECIAL INSPECTOR TO CONDUCT THE
 MINIMUM STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS
 REQUIRED BY THIS CODE, SECTION 553.73,FLORIDA STATUTES,
 WITHOUT DUPLICATIVE INSPECTION BY THE BUILDING
 DEPARTMENT. THE BUILDING OFFICIAL IS RESPONSIBLE FOR
 ENSURING THAT ANY PERSON CONDUCTING INSPECTIONS IS
 QUALIFIED AS A BUILDING INSPECTOR UNDER PART XII OF
 CHAPTER 468, FLORIDA STATUTES, OR CERTIFIED AS A
 SPECIAL INSPECTOR UNDER CHAPTER 471 OR 481, FLORIDA
 STATUTES. INSPECTIONS OF THRESHOLD BUILDINGS REQUIRED
 BY SECTION 553.79(5), FLORIDA STATUTES, ARE IN ADDITION
 TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 5F) NOT COMPLETED. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 5G) NOT COMPLETED. NOTE FOR PAPER PLANS, 3 SETS OF
 DOCUMENTS ARE REQUIRED.
 5H) 110.3.7.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION
 OF THE BUILDING AND PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY OR COMPLETION, FILE A SIGNED
 AND SEALED STATEMENT WITH THE ENFORCEMENT AGENCY IN
 SUBSTANTIALLY THE FOLLOWING FORM: ?TO THE BEST OF MY
 KNOWLEDGE AND BELIEF, THE CONSTRUCTION OF ALL
 STRUCTURAL LOAD-BEARING COMPONENTS DESCRIBED IN THE
 THRESHOLD INSPECTION PLAN COMPLIES WITH THE PERMITTED
 DOCUMENTS AND THE SPECIALTY SHORING DESIGN PROFESSIONAL
 ENGINEER HAS ASCERTAINED THAT THE SHORING AND RESHORING
 CONFORMS WITH THE SHORING AND RESHORING PLANS SUBMITTED
 TO THE ENFORCEMENT AGENCY?.
 5I) 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN ALTERNATE
 STRUCTURAL PRODUCT OR SYSTEM TO WHICH BUILDING CODES
 APPLY SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 REVIEW FOR COMPLIANCE WITH THE CODES AND MADE PART OF
 THE ENFORCEMENT AGENCY?S RECORDED SET OF PERMIT
 DOCUMENTS. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 5J) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTION LINE @ (561)
 805-6700 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS. WITHOUT THIS, THE PERMIT EXPIRES
 IN 6 MONTHS WHICH WILL RESULT IN ?ABANDONMENT OF JOB,
 NO INSPECTION ACTIVITY?. THE PERMIT WILL BECOME
 EXPIRED.
 6) PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY
 LINES, CONSTRUCTION AREAS, STAGING AREAS, HOW THE
 OCCUPANTS OF THE BUILDING WILL BE SAFE GUARDED DURING
 THEIR ENTRY AND EXIT OF THE BUILDING. SHOW COMPLIANCE
 WITH 2014 FBC 3306.7 ? COVERED WALKWAYS, INCLUDING
 LIGHTING FOR THE EXIT DISCHARGE. 2014 FBC 3310.2 ?
 MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF
 EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
 CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS AND
 ADDITIONS TO ANY BUILDING.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-28 Cont ID  
Sent By cthroop Date 2017-02-28 Time 09:49 Rev Time 0.00
Received By cthroop Date 2017-02-10 Time 14:21 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 18:02 Rev Time 0.00
Received By gjohnson Date 2016-12-14 Time 14:04 Sent To  
Notes
2016-12-15 14:04:49ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-27 Cont ID  
Sent By gjohnson Date 2017-02-27 Time 09:59 Rev Time 0.00
Received By gjohnson Date 2017-02-27 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 17:58 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 17:58 Sent To  
Notes
2017-01-12 18:02:211ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE A STORM RISER DIAGRAM WITH PIPE SIZES SQ FT
 BEING DRAINED AND INDICATE EXISTING AND NEW. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-02-14 Cont ID  
Sent By cthroop Date 2017-02-28 Time 09:49 Rev Time 0.00
Received By kmartin Date 2017-02-14 Time 08:58 Sent To B
Notes
2017-02-13 15:49:11ROUTED TO KEVIN MARTIN

Review Stop Z ZONING
Rev No 1 Status P Date 2016-12-22 Cont ID  
Sent By njwira Date 2016-12-22 Time 14:11 Rev Time 0.00
Received By kmartin Date 2016-12-30 Time 09:52 Sent To B
Notes
2016-12-22 14:11:53ROUTED TO KEVIN MARTIN