Plan Review Details - Permit 16120462
Plan Review Stops For Permit 16120462
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-28 Cont ID  
Sent By jgomez Date 2017-02-28 Time 14:39 Rev Time 0.00
Received By jgomez Date 2017-02-28 Time 10:44 Sent To  
Notes
2017-02-28 10:48:42BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- GARAGE DOOR STRUCTURAL BUCK: PROVIDE COMPLETE DETAIL
 AND SPECIFICATIONS FOR THE ATTACHMENT OF THE STRUCTURAL
 BUCK TO THE SUPPORTING STRUCTURE. SPECIFY BUCK SIZE,
 FASTENER TYPE, SIZE AND SPACING. DETAIL #11 ON SHEET
 12D DOESN'T PROVIDE THIS INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-17 Cont ID  
Sent By jgomez Date 2017-01-17 Time 20:09 Rev Time 0.00
Received By jgomez Date 2017-01-13 Time 14:56 Sent To  
Notes
2017-01-17 20:09:29NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENT.
 CODE; FBC 5TH EDITION (2014).
  
 1- SHEET CS1: REVISE THE EXPOSURE CATEGORY. ACCORDING
 TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS BUILDINGS
 LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED AND
 REVISE THE DESIGN PRESSURES ON SHEET 6A. ALSO, CLARIFY
 WHY THE DESIGN PRESSURES FOR WINDOW #002 IS -00.00?
  
 2- DETAILS 3 AND 6 OF SHEET 9D DON'T COMPLY WITH THE
 INSPECTION FOR TERMITES CLEARANCE AS REQUIRED BY SEC.
 R318.7 FBC-RESIDENTIAL. REVISE AS REQUIRED TO COMPLY.
  
 3- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL.
 SPECIFY STRUCTURAL BUCK SIZE AND FASTENER TYPE AND
 SPACING. SEC. R301.1 FBC-RESIDENTIAL.
  
 4- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) CALCULATIONS SUBMITTED ARE DONE FOR WORST CASE
 SCENARIO. PROVIDE COMPLETE CALCULATIONS FOR EACH
 ORIENTATION AS REQUIRED BY THE EXCEPTION OF SEC.
 R405.4.2 FBC-ENERGY CONSERVATION OR PROVIDE ENERGY
 CALCULATIONS FOR THE ACTUAL ORIENTATION OF THE
 BUILDING.
  
 B) REVISE/CLARIFY DOOR TYPE INFORMATION SHOWN ON PAGE 3
 OF 4. WHERE ARE THE WOOD DOORS. PRODUCT APPROVAL FOR
 ENTRY DOORS IS FOR GLAZED FIBERGLASS DOOR. THIS DOOR
 NEEDS TO BE ENTERED IN THE WINDOW AREA AS REQUIRED BY
 SEC. R405.5.3.3 FBC-ENERGY CONSERVATION.
  
 C) REVISE THE WALL TYPE SPECIFIED ON PAGE 3 OF 4 FOR
 THE GARAGE AREA. ACCORDING TO THE WCI/PLAN STANDARDS ON
 SHEET 6A ALL INTERIOR WALLS ARE METAL NOT WOOD. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) IT LOOKS LIKE THE THE NOTARY PUBLIC IS SIGNING FOR
 THE OWNER ON THE FRONT PAGE OF THE ENERGY CALCULATIONS
 AND FOR THE BUILDER ON THE EPL DISPLAY CARD. ENERGY
 CALCULATIONS MAY BE SIGNED BY AN AGENT LEGALLY
 DESIGNATED BY THE OWNER AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION. PROVIDE PROOF THAT OWNER
 ASSIGNED THIS AGENT.
 ON THE OTHER HAND, WHY IS THE NOTARY PUBLIC SIGNING FOR
 THE BUILDER?. BUILDER NEEDS TO SIGN.
  
 ******PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-23 Cont ID  
Sent By rlecky Date 2017-02-23 Time 14:25 Rev Time 0.00
Received By rlecky Date 2017-02-21 Time 14:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-12 Cont ID  
Sent By mvaldes Date 2017-01-12 Time 10:10 Rev Time 0.00
Received By mvaldes Date 2017-01-09 Time 15:32 Sent To B
Notes
2017-01-12 10:11:28JOB PERMIT NUMBER: 16120462
 JOB ADDRESS: 10543 STARLING WAY
 WEST PALM BEACH FLORIDA
 DATE: JANUARY 12, 2017
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014,
 (RESIDENTIAL FLORIDA BUILDING CODE) AS WELL AS THE CITY
 OF WEST PALM BEACH AMENDMENTS. SEE BELOW A LIST OF
 ITEMS NOTED.
  
 1] CLARIFY ON RISER DIAGRAM IF THE FEEDER CONDUIT IS
 METALLIC RMC, IMC, OR EMT? IF NOT PLEASE SHOW AN EGC
 PER FBC-R SECTION E3908.8.
  
 2] PLEASE CORRECT NOTE # 25, FBC-E SECTION 404.1 STATES
 A MINIMUM OF 75% OF LAMPS IN PERMANENTLY INSTALLED
 LUMINAIRES SHALL BE HIGH EFFICACY LAMPS.
  
 3] SINCE GAS APPLIANCES ARE PRESENT PLEASE ADD A NOTE
 THEY SHALL BE BONDED IN ACCORDANCE WITH FBC-E SECTION
 E3609.7.
  
 4] RECESSED LIGHTS INSTALLED IN BUILDING ENVELOPE SHALL
 BE SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED &
 UN-CONDITIONED SPACES. IN ADDITION IF HOUSING CANS ARE
 INSTALLED IN THERMAL INSULATION THEY SHALL BE LISTED
 IC-RATED PER FBC-E SECTION R402.4.4, A NOTE WILL
 SUFFICE.
  
 5] LOW VOLTAGE SHALL BE UNDER A SEPARATE PERMIT.
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-20 Time 13:17 Rev Time 0.00
Received By gjohnson Date 2017-01-20 Time 13:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-28 Cont ID  
Sent By jgomez Date 2017-02-28 Time 14:56 Rev Time 0.00
Received By jgomez Date 2017-02-14 Time 10:31 Sent To  
Notes
2017-02-15 10:32:00R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-20 Time 13:18 Rev Time 0.00
Received By gjohnson Date 2016-12-13 Time 14:37 Sent To  
Notes
2016-12-14 14:37:59R32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2017-01-17 Cont ID  
Sent By jgomez Date 2017-01-17 Time 20:25 Rev Time 0.00
Received By jgomez Date 2017-01-17 Time 20:25 Sent To  
Notes
2017-01-17 20:26:44$10,003.08 PAID. MU-2016-30227.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-01-19 Cont ID  
Sent By jvalido Date 2017-01-19 Time 16:49 Rev Time 0.00
Received By jvalido Date 2017-01-19 Time 16:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-20 Time 13:17 Rev Time 0.00
Received By gjohnson Date 2017-01-20 Time 13:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-01-17 Cont ID  
Sent By jgomez Date 2017-01-17 Time 20:27 Rev Time 0.00
Received By jgomez Date 2017-01-17 Time 20:26 Sent To  
Notes
2017-01-17 20:28:01A) ROOF TILE NOA 16-0314.08
 B) ROOF TILE UNDERLAYMENT NOA 15-0410.04.
 C) ROOF VENTS FL16588-R1 AND NOA 13-0122.07
 D) ROOF TILE ADHESIVE FL6332-R5.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-12-21 Cont ID  
Sent By nwair Date 2016-12-21 Time 19:08 Rev Time 0.00
Received By njwira Date 2016-12-21 Time 17:21 Sent To L
Notes
2016-12-21 19:10:2612/21/16- PASSED
  
 IBIS PLANNED DEVELOPMENT
 NON-ZERO LOT LINE
  
 FRONT SETBACK IS 15.9FT. MEETING THE 15FT. REQUIREMENT
 SIDE SETBACK IS 20FT. MEETING 7.5FT. REQUIREMENT
 REAR SETBACK IS 42.32FT. MEETING THE 15FT. REQUIREMENT
 ONE KITCHEN PLUS ONE(1)OUTDOOR GRILLING SPACE
 ONE STORY PERMITTED
  
 PLEASE CONTACT