Plan Review Details - Permit 16120416
Plan Review Stops For Permit 16120416
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-28 Cont ID  
Sent By rmcdouga Date 2017-02-28 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2017-02-28 Time 16:11 Sent To HIST
Notes
2017-02-28 16:06:26APPROVED WITH EXCEPTIONS
  
 1) SUBMIT TWO SETS OF PRODUCT APPROVALS OR SITE
 SPECIFIC ENGINEERING FOR THE "EXISTING" UN-PERMITTED
 FRENCH DOOR AND SIDELIGHTS. FBC-R612.2 & R612.3.1
 2) SUBMIT TWO SETS OF AN INSTALLATION SCHEDULE AND
 PRODUCT APPROVALS FOR THE HURRICANE PANELS THAT WILL BE
 INSTALLED ON THE "EXISTING" FRENCH DOORS.
 FBC-R301.2.1.2
 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOFING
 MATERIALS FOR THE FLAT ROOF (INCLUDING SIGNED AND
 SEALED ENHANCED FASTENING CALCULATIONS) THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By rmcdouga Date 2017-02-15 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2017-02-14 Time 19:03 Sent To M
Notes
2017-02-15 18:30:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERMIT AND PLANS SPECIFY THAT THIS PROJECT IS AN
 EXISTING COTTAGE THAT WILL BE REMODELED AND HAVE AND
 ADDITION. ALTHOUGH, A PERMIT APPLICATION FOR THIS WORK
 WAS APPLIED FOR, A PERMIT WAS NEVER ISSUED TO CONVERT
 THIS DETACHED GARAGE INTO LIVING SPACE. THERE IS AN
 AFFIDAVIT ON FILE DATED APRIL 29, 2016 THAT STATES THE
 WORK ON THE GARAGE CONVERSION WAS NEVER DONE. ANY WORK
 THAT WAS DONE TO THE DETACHED GARAGE WAS DONE SO
 WITHOUT PERMITS OR INSPECTIONS. PLEASE BE ADVISED THE
 INSPECTOR MAY REQUIRE PREVIOUSLY COMPLETED WORK TO BE
 MADE ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE
 ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK
 PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 2) THIS IS ALSO A CHANGE OF OCCUPANCY WITH NO CHANGE OF
 OCCUPANCY CLASSIFICATION. FBC EXISTING BUILDING SECTION
 1001.2
  
 3) THE FRENCH DOOR THAT IS MARKED AS EXISTING DOOR ON
 THE PLANS WAS INSTALLED WITHOUT PERMITS OR INSPECTIONS.
 SUBMIT PRODUCT APPROVALS FOR THIS DOOR FOR REVIEW AS
 REQUIRED BY DCA RULE 9N-3.
  
 4) SUBMIT THE PRODUCT APPROVALS FOR THE WALL LOUVER
 ATTIC VENTS AND PROVIDE DOCUMENTATION OF THE NET FREE
 AREA OF THE VENTS. THE REQUIRED NET VENT AREA IS 3.06
 SQFT. SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED
 OR R806.5 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER
 ASSEMBLIES. FBC R806.1 ENCLOSED ATTICS AND ENCLOSED
 RAFTER SPACES FORMED WHERE CEILINGS ARE APPLIED
 DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL HAVE
 CROSS VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF
 RAIN OR SNOW. VENTILATION OPENINGS SHALL HAVE A LEAST
 DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH
 (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A LEAST
 DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING,
 HARDWARE CLOTH, OR SIMILAR MATERIAL WITH OPENINGS
 HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING
 MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF SECTION
 R802.1.8. REQUIRED VENTILATION OPENINGS SHALL OPEN
 DIRECTLY TO THE OUTSIDE AIR.
  
 5) THE ENERGY COMPLIANCE FORM R405-2014 THAT WAS
 SUBMITTED CONTAINS ERRORS AND OMISSIONS. THIS IS NOT A
 MODEL THAT WILL BE WITH DIFFERENT ORIENTATIONS. THIS IS
 A ONE OF A KIND STRUCTURE AND IT IS SITE SPECIFIC.
 THEREFORE, YOU CAN NOT USE THE WORST CASE ORIENTATION
 ON THE FORM. USE THE ACTUAL ORIENTATION OF THE BUILDING
 FOR ENERGY AND EQUIPMENT SIZING CALCULATIONS. THERE
 WILL BE NO ROTATE ANGLE. THERE IS NO KITCHEN ( NOT
 ALLOWED BY ZONING REGULATIONS ). FBC 107.2.1
  
 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRENCH DOORS HAS A NEGATIVE DESIGN PRESSURE THAT IS NOT
 ADEQUATE. THE PLANS REQUIRE +37.8, - 50.6 PSF AND THE
 PRODUCT IS RATED FOR +45, -45 PSF. FBC-R 301.2.1
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 ROOFING MATERIAL THAT WILL BE INSTALLED ON THE FLAT
 ROOF.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-27 Cont ID  
Sent By rmcdouga Date 2016-12-27 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2016-12-22 Time 18:48 Sent To  
Notes
2016-12-27 11:24:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERMIT AND PLANS SPECIFY THAT THIS PROJECT IS AN
 EXISTING COTTAGE THAT WILL BE REMODELED AND HAVE AND
 ADDITION. ALTHOUGH, A PERMIT APPLICATION FOR THIS WORK
 WAS APPLIED FOR, A PERMIT WAS NEVER ISSUED TO CONVERT
 THIS DETACHED GARAGE INTO LIVING SPACE. THERE IS AN
 AFFIDAVIT ON FILE DATED APRIL 29, 2016 THAT STATES THE
 WORK ON THE GARAGE CONVERSION WAS NEVER DONE. ANY WORK
 THAT WAS DONE TO THE DETACHED GARAGE WAS DONE SO
 WITHOUT PERMITS OR INSPECTIONS. PLEASE BE ADVISED THE
 INSPECTOR MAY REQUIRE PREVIOUSLY COMPLETED WORK TO BE
 MADE ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE
 ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK
 PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 2) ON SHEET 01 THE PROJECT IS INCORRECTLY SPECIFIED AS
 A LEVEL 2 ALTERATION. THIS IS A LEVEL 3 ALTERATION WITH
 AN ADDITION. FBC EXISTING BUILDING CHAPTER 5
  
 3) THIS IS ALSO A CHANGE OF OCCUPANCY WITH NO CHANGE OF
 OCCUPANCY CLASSIFICATION. FBC EXISTING BUILDING SECTION
 1001.2
  
 4) THE FRENCH DOOR THAT IS MARKED AS EXISTING DOOR ON
 THE PLANS WAS INSTALLED WITHOUT PERMITS OR INSPECTIONS.
 SUBMIT PRODUCT APPROVALS FOR THIS DOOR FOR REVIEW AS
 REQUIRED BY DCA RULE 9N-3.
  
 5) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED OR
 R806.5 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER
 ASSEMBLIES.
 FBC R806.1 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW.
 VENTILATION OPENINGS SHALL HAVE A LEAST DIMENSION OF
 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH (6.4 MM)
 MAXIMUM. VENTILATION OPENINGS HAVING A LEAST DIMENSION
 LARGER THAN 1/4 INCH (6.4 MM) SHALL BE PROVIDED WITH
 CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE
 CLOTH, OR SIMILAR MATERIAL WITH OPENINGS HAVING A LEAST
 DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH
 (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING MEMBERS
 SHALL CONFORM TO THE REQUIREMENTS OF SECTION R802.1.8.
 REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO
 THE OUTSIDE AIR.
  
 6) THE ENERGY COMPLIANCE FORM R405-2014 THAT WAS
 SUBMITTED CONTAINS ERRORS AND OMISSIONS. THIS IS NOT A
 MODEL THAT WILL BE WITH DIFFERENT ORIENTATIONS. THIS IS
 A ONE OF A KIND STRUCTURE AND IT IS SITE SPECIFIC.
 THEREFORE, YOU CAN NOT USE THE WORST CASE ORIENTATION
 ON THE FORM. USE THE ACTUAL ORIENTATION OF THE BUILDING
 FOR ENERGY AND EQUIPMENT SIZING CALCULATIONS. THERE
 WILL BE NO ROTATE ANGLE. THERE IS NO KITCHEN ( NOT
 ALLOWED BY ZONING REGULATIONS ). THE PLANS ARE NOT
 CLEAR IF THE ATTIC WILL BE VENTED OR NOT. FBC 107.2.1
  
 7) THE DOWNSPOUTS ARE REQUIRED TO DISCHARGE AT LEAST 1
 FOOT AWAY FROM THE STRUCTURE SIDEWALL. R318.5
 PROTECTION AGAINST DECAY AND TERMITES.
  
 8) THE AREA TABULATION ON SHEET 01 IS INCORRECT. THE
 EXISTING AREA IS 348 SQFT, THE ADDITION IS 112 SQFT AND
 THE TOTAL IS 460 SQFT. FBC 107.2.1
  
 9) THE 4" RECESS IN THE SLAB FOR THE SHOWER INDICATED
 ON SHEET 01 IS NOT SHOWN ON THE FOUNDATION PLAN. FBC
 107.2.1
  
 10) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRENCH DOORS HAS A NEGATIVE DESIGN PRESSURE THAT IS NOT
 ADEQUATE. THE PLANS REQUIRE +37.8, - 50.6 PSF AND THE
 PRODUCT IS RATED FOR +45, -45 PSF. FBC-R 301.2.1
  
 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 ROOFING MATERIAL THAT WILL BE INSTALLED ON THE FLAT
 ROOF.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-28 Cont ID  
Sent By vperez Date 2017-02-28 Time 15:29 Rev Time 0.00
Received By vperez Date 2017-02-28 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-02-01 Cont ID  
Sent By vperez Date 2017-02-01 Time 12:18 Rev Time 0.00
Received By vperez Date 2017-02-01 Time 12:18 Sent To  
Notes
2017-02-01 12:24:06PLEASE NOTE THAT THE CALCULATION FOR SUBPANEL SUBMITTED
 IS 112AMPS, EXISTING PANEL IS RATED AT 100AMP. PANEL
 SCHEDULE SHOWS A 200 AMP PANEL. AT THIS TIME A COMPLETE
 SERVICE CALCULATION IS TO BE SUBMITTED REFLECTING THE
 OVERCURRENT PROTECTION LANDED AT MAIN 200 PANEL FEEDING
 SUBPANEL LOADS. CALCULATION CANNOT EXCEED RATED BUS
 SIZE AMP. COORELATE RISER DIAGRAM AND PANEL SCHEDULES
 TO MATCH ACTUAL INSTALLATION. FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-28 Cont ID  
Sent By vperez Date 2016-12-28 Time 08:26 Rev Time 0.00
Received By vperez Date 2016-12-28 Time 07:24 Sent To  
Notes
2016-12-28 08:30:35PLEASE NOTE THAT A SECOND METER ON THIS PROPERTY IS NOT
 PERMITTED. POWER TO COTTAGE WILL NEED TO ORIGINATE FROM
 MAIN SERVICE.
 SHOW COTTAGE BEING FED FROM MAIN HOUSE. A COMPLETE
 REVIEW WILL BE PERFORMED UPON RESUBMITTAL.
  
 VAL PEREZ
 *6717

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-03-01 Cont ID  
Sent By fmittner Date 2017-03-01 Time 13:36 Rev Time 0.00
Received By fmittner Date 2017-03-01 Time 13:36 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-01-30 Cont ID  
Sent By fmittner Date 2017-01-30 Time 14:27 Rev Time 0.00
Received By fmittner Date 2017-01-30 Time 14:27 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-12-15 Cont ID  
Sent By fmittner Date 2016-12-15 Time 16:33 Rev Time 0.00
Received By fmittner Date 2016-12-15 Time 16:33 Sent To  
Notes
2016-12-15 16:34:20WINDOWS DO NOT REFLECT VERTICAL ORIENTAION OR GRID
 PATTERN OF EXISITNG ONES. EXPLAINED DEIGN GUIDELINES TO
 JOE SCIONTI.
  
 QUESTIONS, CONTACT:
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 (561) 822-1457
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-01 Cont ID  
Sent By rmcdouga Date 2017-03-01 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2017-02-27 Time 15:09 Sent To  
Notes
2017-02-27 15:10:16R14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-22 Cont ID  
Sent By cpuell Date 2017-02-22 Time 15:21 Rev Time 0.00
Received By cpuell Date 2017-01-18 Time 09:26 Sent To  
Notes
2017-01-19 09:27:18R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-28 Cont ID  
Sent By vperez Date 2016-12-28 Time 08:30 Rev Time 0.00
Received By vperez Date 2016-12-28 Time 08:30 Sent To  
Notes
2016-12-12 16:27:07R21 SPLIT FROM 16111187 AS THIS IS A SEPARATE STRUCTURE
 WITH DESIGN BY DIFFERENT DESIGNER.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-02-28 Cont ID  
Sent By rmcdouga Date 2017-02-28 Time 16:13 Rev Time 0.00
Received By rmcdouga Date 2017-02-28 Time 16:13 Sent To  
Notes
2017-02-28 16:18:53MU-2017-5336, NO FEES WERE DUE. WILLIE SWOOPE WAS
 CALLED TO VERIFY AND INDICATED THAT FEES HAD BEEN PAID
 IN 2005 FOR ADDITIONAL SPACE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-12-22 Cont ID  
Sent By rmcdouga Date 2016-12-22 Time 18:48 Rev Time 0.00
Received By rmcdouga Date 2016-12-22 Time 18:48 Sent To  
Notes
2016-12-22 18:49:25BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-02-28 Cont ID  
Sent By rmcdouga Date 2017-02-28 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2017-02-28 Time 14:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-02-21 Cont ID  
Sent By jvalido Date 2017-02-21 Time 18:41 Rev Time 0.00
Received By jvalido Date 2017-02-21 Time 17:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-15 Cont ID  
Sent By jvalido Date 2016-12-15 Time 17:31 Rev Time 0.00
Received By jvalido Date 2016-12-15 Time 17:08 Sent To  
Notes
2016-12-15 17:21:17CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE RETURN AIR FOR BEDROOM. RETURN AIR CANNOT
 BE THROUGH A BEDROOM.
 (2) PROVIDE EQUIPMENT SCHEDULE ON PLANS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (3) PROVIDE APPROVED HEAT LOAD CALCULATION. HEAT LOAD
 SUMMARY CAN BE ADDED IN ADDITION BUT CANNOT TAKE THE
 PLACE OF A HEAT LOAD CALCULATION.
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN
 SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER
 SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR
 OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM
 SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY
 LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS
 STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS.
  
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-02-28 Cont ID  
Sent By rmcdouga Date 2017-02-28 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2017-02-28 Time 14:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-02-02 Cont ID  
Sent By gjohnson Date 2017-02-01 Time 11:58 Rev Time 0.00
Received By gjohnson Date 2017-02-01 Time 16:48 Sent To  
Notes
2017-02-01 17:04:291ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. UNDER SCOPE OF WORK IT STATES THE ADDITION OF A
 KITCHEN THE PLAN DO NOT SHOW A KITCHEN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-12-21 Cont ID  
Sent By gjohnson Date 2016-12-21 Time 11:05 Rev Time 0.00
Received By gjohnson Date 2016-12-21 Time 11:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2017-02-28 Cont ID  
Sent By rmcdouga Date 2017-02-28 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2017-02-28 Time 15:52 Sent To  
Notes
2017-02-28 15:54:09THE CONTRACTOR HAS REQUESTED TO DEFER THE SUBMITTAL OF
 ROOFING MATERIALS FOR THE FLAT ROOF.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By rmcdouga Date 2017-02-15 Time 18:31 Rev Time 0.00
Received By rmcdouga Date 2017-02-15 Time 18:31 Sent To  
Notes
2017-02-15 18:31:28NO PRODUCT APPROVALS FOR ROOFING WERE SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-12-22 Cont ID  
Sent By rmcdouga Date 2016-12-22 Time 18:50 Rev Time 0.00
Received By rmcdouga Date 2016-12-22 Time 18:50 Sent To  
Notes
2016-12-22 18:53:23NO PRODUCT APPROVALS FOR ROOFING WERE SUBMITTED.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-30 Cont ID  
Sent By fmittner Date 2017-01-30 Time 14:27 Rev Time 0.00
Received By fmittner Date 2017-01-30 Time 14:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-12-15 Cont ID  
Sent By fmittner Date 2016-12-15 Time 16:35 Rev Time 0.00
Received By fmittner Date 2016-12-15 Time 16:35 Sent To  
Notes
2016-12-15 16:35:40ADDITION REQUIRES SUBMITTAL OF A DIMENSIONED SITE PLAN.
  
 QUESTIONS, CONTACT:
 FRIEDERIKE MITTNER, CITY HSITORIC PRESERVATION PLANNER
 (561) 822-1457
 [email protected]