| Notes |
| 2016-12-14 10:29:36 | PROVISO NOTES | | | | | | PROVIDE INTERSYSTEM BONDING TERMINAL NEC 250.94 | | | VERIFY IF SMOKE DETECTORS ARE EXISTING IN DWELLING, IF | | | NOT PROVIDE PER FBC RES 314-315 | | | EXISTING ROMEX INSTALLED INSIDE PVC CONDUIT SUBJECT TO | | | INSPECTORS APPROVAL AS THE INTERIOR OF CONDUIT IS | | | CONSIDERED A WET LOCATION. NEC 300.9- AND 310.10C | | | | | | VAL PEREZ | | | *6717 | | | |
|
|