Plan Review Details - Permit 16120365
Plan Review Stops For Permit 16120365
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-06 Cont ID  
Sent By rmcdouga Date 2017-03-06 Time 18:21 Rev Time 0.00
Received By rmcdouga Date 2017-03-06 Time 15:15 Sent To E
Notes
2017-03-06 18:23:53APPROVED WITH EXCEPTIONS
 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOFING
 MATERIALS. MUST BE APPROVED BY DESIGNER OF RECORD AND
 CITY HISTORIC PLANNER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-09 Cont ID  
Sent By rmcdouga Date 2017-01-09 Time 10:10 Rev Time 0.00
Received By rmcdouga Date 2017-01-06 Time 07:58 Sent To  
Notes
2017-01-09 09:56:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN EXPOSURE D AND HAS A MEAN
 ROOF HEIGHT OF ABOUT 23 FEET. THE WINDLOAD CALCULATIONS
 FROM AL-FAROOQ CORPORATION WERE DONE FOR EXPOSURE C
 WITH A MEAN ROOF HEIGHT OF 20 FEET. FBC - R301.2.1 &
 R301.2.1.4.3
  
 2) PROVIDE STRUCTURAL DRAWINGS AND DETAILS FOR THE NEW
 LANDING, STEPS AND BALUSTRADE ON THE PLANS. FBC 107.2.1
  
 3) SHOW COMPLIANCE WITH FBC-R314.3.1 ALTERATIONS,
 REPAIRS AND ADDITIONS. WHEN ALTERATIONS, REPAIRS OR
 ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE
 SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS.
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 CONCRETE ROOF TILE AND THE DOUBLE CASEMENT WINDOWS.
  
 5) THE PLANS SPECIFY NOA NO. 15-0416.02 FOR THE
 CASEMENT WINDOWS ON SHEET A-03. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED, NOA NO. 15-0416.01, IS FOR SINGLE
 CASEMENT WINDOWS. PLEASE CORRECT.
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-07 Cont ID  
Sent By vperez Date 2017-03-07 Time 08:08 Rev Time 0.00
Received By vperez Date 2017-03-07 Time 08:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-21 Cont ID  
Sent By mvaldes Date 2016-12-21 Time 11:22 Rev Time 0.00
Received By mvaldes Date 2016-12-21 Time 10:03 Sent To  
Notes
2016-12-21 11:23:09JOB PERMIT NUMBER: 16120365
 JOB ADDRESS: 257 GRANADA RD
 WEST PALM BEACH FLORIDA
 DATE: DECEMBER 21, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE RESIDENTIAL) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PLEASE LABEL EACH ROOM ON THE ELECTRICAL FLOOR PLANS
 TO DISTINGUISH PURPOSE IT SERVES. FBC 107
  
 2] IN DWELLING UNITS OCPD (BREAKERS) SHALL NOT BE
 LOCATED IN BATHROOMS. RELOCATE ACCORDINGLY PER FBC-R
 SECTION E3705.7
  
 3] SMOKE ALARMS REQUIRED PER FBC-R SECTIONS 314 & 315.
 SHOW LOCATION ON THE ELECTRICAL FLOOR PLAN.
  
 4] VERIFY THAT ALL BATHROOMS SHOW A GFCI RECEPTACLE
 WITHIN 3' OF THE SINK PER FBC-R SECTION E3901.6
  
 5] ALL PERMANENT INSTALLED LUMINAIRES SHALL BE 75 %
 HIGH EFFICIENT. FBC-E SECTION R404.1 (A NOTE WILL
 SUFFICE).
  
 6] RECESSED LIGHTING INSTALLED SHALL BE SEALED TO LIMIT
 AIR LEAKAGE BETWEEN CONDITIONED AND UNCONDITIONED
 SPACES. IF THE CANS ARE INSTALLED IN THERMAL INSULATION
 THE HOUSING SHALL BE LISTED IC-RATED. FBC-E SECTION
 402.4.4 (A NOTE WILL SUFFICE).
  
 7] PROVIDE A SITE SPECIFIC RISER DIAGRAM WITH WIRE &
 CONDUIT SIZES, GROUNDING DETAIL, COMPLETE LOAD
 CALCULATIONS, & A PANEL SCHEDULE WITH DESIGNATED
 CIRCUITS MATCHING THE FLOOR PLAN. FBC 107.3.5.3
  
 8] REFERENCE NEC TABLE 310.15(B)(7) ALLOWABLE
 AMPACITIES OF CONDUCTORS FOR DWELLING SERVICES &
 FEEDERS. THE # 1 AWG WIRE IS NOT RATED FOR 300 AMPS,
 ADJUST ACCORDINGLY.
  
 9] THE SERVICE DISCONNECTING MEANS MUST BE LOCATED
 NEAREST THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS. CLARIFY IF THE EQUIPMENT IS A METER MAIN &
 SHOW LOCATION ON THE ELECTRICAL FLOOR PLAN. NEC
 230.70(A)(1).
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-03-01 Cont ID  
Sent By fmittner Date 2017-03-01 Time 10:57 Rev Time 0.00
Received By fmittner Date 2017-03-01 Time 10:57 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-01-04 Cont ID  
Sent By fmittner Date 2017-01-04 Time 11:39 Rev Time 0.00
Received By fmittner Date 2016-12-22 Time 15:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-08 Cont ID  
Sent By lmarchan Date 2017-03-08 Time 08:19 Rev Time 0.00
Received By lmarchan Date 2017-02-08 Time 13:53 Sent To  
Notes
2017-02-21 13:53:29R02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-09 Cont ID  
Sent By rmcdouga Date 2017-01-09 Time 10:10 Rev Time 0.00
Received By rmcdouga Date 2016-12-09 Time 11:14 Sent To  
Notes
2016-12-13 11:14:13R23

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-07 Cont ID  
Sent By jvalido Date 2017-03-07 Time 17:09 Rev Time 0.00
Received By jvalido Date 2017-03-07 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-15 Cont ID  
Sent By jvalido Date 2016-12-15 Time 18:14 Rev Time 0.00
Received By jvalido Date 2016-12-15 Time 16:44 Sent To  
Notes
2016-12-15 17:56:21CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL NOTES WITH REQUIRED INFORMATION
 ON SCOPE OF WORK,
 (2) PROVIDE CFM VALUE FOR EACH SUPPLY OUTLET.
 (3) PROVIDE EQUIPMENT SCHEDULE ON PLANS.
 (4) PROVIDE LOCATION OF CONDENSERS.
 (5) PROVIDE CONDENSER TIE DOWN DETAIL.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (6) PROVIDE AHRI
 (7) PROVIDE A BALANCED AIR FLOW THROUGH ALL SUPPLY
 OUTLETS AS PER THE TOTAL CFM DESIGN VALUES OF AHU #1 &
 #2.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-03-06 Cont ID  
Sent By rmcdouga Date 2017-03-06 Time 18:12 Rev Time 0.00
Received By rmcdouga Date 2017-03-06 Time 18:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-06 Cont ID  
Sent By rmcdouga Date 2017-01-06 Time 14:11 Rev Time 0.00
Received By rmcdouga Date 2017-01-06 Time 14:10 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2017-03-06 Cont ID  
Sent By rmcdouga Date 2017-03-06 Time 16:44 Rev Time 0.00
Received By rmcdouga Date 2017-03-06 Time 16:44 Sent To  
Notes
2017-03-06 16:48:22NO PRODUCT APPROVALS WERE SUBMITTED FOR THE HANDMADE
 CLAY BARREL TILE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-01-09 Cont ID  
Sent By rmcdouga Date 2017-01-09 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2017-01-09 Time 10:50 Sent To  
Notes
2017-01-09 10:51:44PLANS SPECIFY A NEW TILE ROOF. NO PRODUCT APPROVALS
 WERE SUBMITTED FOR ROOFING.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-03-01 Cont ID  
Sent By fmittner Date 2017-03-01 Time 10:56 Rev Time 0.00
Received By fmittner Date 2017-03-01 Time 10:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-01-04 Cont ID  
Sent By fmittner Date 2017-01-04 Time 11:39 Rev Time 0.00
Received By fmittner Date 2017-01-04 Time 11:39 Sent To  
Notes
***NONE***