Plan Review Details - Permit 16120359
Plan Review Stops For Permit 16120359
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-13 Cont ID  
Sent By tklarge Date 2016-12-13 Time 03:21 Rev Time 0.00
Received By tklarge Date 2016-12-09 Time 13:07 Sent To  
Notes
2016-12-12 13:07:36ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-13 Cont ID  
Sent By tklarge Date 2016-12-13 Time 03:21 Rev Time 0.00
Received By tklarge Date 2016-12-13 Time 02:37 Sent To  
Notes
2016-12-13 03:14:571) SUBMIT A SANITARY RISER DIAGRAM THAT CLEARLY
 REFLECTS THE ENTIRE SCOPE OF PLUMBING WORK TO BE DONE.
 SHOW ALL PIPE SIZES INCLUDING VENTS,LOCATION OF
 CLEANOUTS,
 2) THE PLAN APPEARS TO SHOW THAT THE EXISTING BATHROOM
 IS BEING RELOCATED FROM ITS EXISTING LOCATION.IF SO,
 THIS SUBMITTAL SHOULD BE ACCOMPANIED BY A FULL SET OF
 PLANS FOR WALLS, ELECTRIC, ETC.
 3) IF THIS IS A NEW TOILET ROOM SUBMIT A FLOOR PLAN
 SHOWING ALL PLUMBING FIXTURE CLEARANCES. COMPLY WITH
 2014 FBCR SEC.P2705.
 4) SHOW THE CLEAR INSIDE DIMENSIONS OF THE SHOWER ON
 THE PLANS. COMPLY WITH 2014 FBCR SEC. P2708.1.
 5) THE CEILING HEIGHT OF THE BATHROOM( IF NEW) SHALL
 COMPLY WITH 2014 FBCR SEC.R305.1.
  
 NOTE: A COMPREHENSIVE PLAN REVIEW COULD NOT BE DONE DUE
 TO THE PLANS LACKING INFORMATION. ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED DURING THE SECOND
 REVIEW.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW