Plan Review Details - Permit 16120356
Plan Review Stops For Permit 16120356
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-22 Cont ID  
Sent By rmcdouga Date 2017-02-22 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2017-02-22 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-09 Cont ID  
Sent By rmcdouga Date 2017-01-09 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2017-01-06 Time 18:54 Sent To  
Notes
2017-01-09 16:24:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE SEVERAL REFERENCES MADE TO THE 2010 FBC ON
 SHEET A-1.0. THIS PROJECT IS UNDER THE 2014 FBC. PLEASE
 CORRECT.
  
 2) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THE
 WINDSPEED IS 170 MPH VULT ( 132 MPH VASD ) AND THE
 EXPOSURE CATEGORY IS C. FBC R301.2.1
  
 3) THE WINDOW AND DOOR ID MARKS THAT ARE LISTED IN THE
 SCHEDULES ON SHEET A-2.0 ARE NOT SPECIFIED ON THE FLOOR
 PLAN. FBC 107.2.1
  
 4) THE SHOP DRAWINGS FOR THE ALUMINUM CANOPIES ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD FOR THE PROJECT. FBC 107.3.4.1
  
 5) THE SPACING OF THE ALUMINUM COLUMNS ON SHEET A-3.0
 DOES NOT CORRESPOND WITH THE SPACING ON SHEET 1 OF THE
 ALUMINUM CANOPY PLAN. PLEASE CORRECT. FBC 107.2.1
  
 6) SHEET 1 OF THE ALUMINUM CANOPY PLAN SPECIFIES 3" X
 .032 X 2 # FOAM PANELS AND THE 3" X .032 X 1 # EPS
 PANEL IS MARKED UP ON THE PRODUCT APPROVAL DRAWING.
 PLEASE CLARIFY. FBC 107.2.1
  
 7) THE DEFLECTION FOR COMPOSITE PANELS IS L/120. THE
 VALUE IN THE L/80 COLUMN IS MARKED ON PRODUCT APPROVAL
 SPAN CHART. PLEASE CORRECT. AAF GUIDE TO ALUMINUM
 CONSTRUCTION IN HIGH WIND AREAS
  
 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 IMPACT RATED HORIZONTAL SLIDING WINDOWS, STRUCTURAL
 MULLIONS AND EXTERIOR FRENCH DOORS.
  
 9) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-14 Cont ID  
Sent By rlecky Date 2017-02-14 Time 11:07 Rev Time 0.00
Received By rlecky Date 2017-02-14 Time 10:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-03 Cont ID  
Sent By rlecky Date 2017-01-03 Time 11:54 Rev Time 0.00
Received By rlecky Date 2016-12-29 Time 14:15 Sent To  
Notes
2017-01-03 11:55:41 
 16120356
 1021 AVON ROAD
 SF RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE NOTES ON THE PLANS REQUIRE SOME CLARIFICATION. THEY
 REFER TO SUB PANELS AND NEW PANELS WHICH ARE NOT SHOWN.
 THE NOTES REFER TO A CARBON MONOXIDE (CO) DETECTOR BUT
 THE PLANS ONLY SHOW SMOKE DETECTORS. ARE THERE GAS
 APPLIANCES ON THIS JOB?
  
 IS THIS A NEW SERVICE OR AN EXISTING SERVICE? THE LOAD
 CALCULATION SHOWS A 200 AMP MAIN BREAKER PANEL BUT THE
 RISER AND PANEL SCHEDULE ARE SHOWING SOMETHING
 DIFFERENT.
  
 PROVIDE A DETAIL FOR THE EXISTING ELECTRICAL SERVICE
 MAST WHERE IT PENETRATES THE NEW ALUMINUM CANOPY TO
 CONNECT TO THE OVERHEAD SERVICE CONDUCTORS. THERE ARE
 SOME SAFETY CLEARANCES IN THE ELECTRICAL CODE THAT NEED
 TO BE FOLLOWED. NEC 230.24
  
 ARC FAULT CIRCUITS ARE NOT LIMITED TO BEDROOMS ONLY.
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-22 Cont ID  
Sent By rmcdouga Date 2017-02-22 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2017-02-13 Time 14:54 Sent To  
Notes
2017-02-13 14:54:55RLECKY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-09 Cont ID  
Sent By rmcdouga Date 2017-01-09 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2016-12-09 Time 13:20 Sent To  
Notes
2016-12-12 13:20:51R01

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-22 Cont ID  
Sent By rmcdouga Date 2017-02-22 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2017-02-22 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-09 Cont ID  
Sent By rmcdouga Date 2017-01-09 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2017-01-06 Time 18:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-12-15 Cont ID  
Sent By awooten Date 2016-12-15 Time 10:20 Rev Time 0.00
Received By awooten Date 2016-12-15 Time 08:50 Sent To  
Notes
***NONE***