| 2016-12-09 06:59:48 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16120249 |
| | ADD: 2 HARVARD CIRCLE SUITE # 300 |
| | CONT: WITTMANN BUILDING |
| | TEL: 561-366-8188 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. DEC. 09/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 DOOR 02 DOES NOT HAVE THE REQUIRED 18 |
| | INCHES ON THE LATCH SIDE OF THE DOOR. PLEASE SHOW |
| | COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE SECTION |
| | 404.2.4 AND FIGURE 404.2.4(A). |
| | |
| | 2A) SHEET A1 THE BREAK ROOM, THE BREAKROOM SINK THE |
| | SINK NEEDS TO BE SET (CENTERED) FOR A FRONT APPROACH |
| | AND EXCEPTION # 1 ALLOWS FOR A SIDE APPROACH. WHERE THE |
| | LOCATION IS NOW SHOWN A SIDE APPROACH IS NOT POSSIBLE. |
| | PLEASE PROVIDE ON THE PLANS WHICH OPTION IS TO BE USED, |
| | FRONT APPROACH OR SIDE APPROACH. SEE THE 2014 |
| | FBC-ACCESSIBILITY CODE 606.2. |
| | |
| | 2B) SHOW COMPLIANCE WITH THE 2014 ACCESSIBILITY CODE |
| | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 2C) SHOW COMPLIANCE WITH THE 2014 ACCESSIBILITY CODE |
| | SECTION 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL |
| | COMPLY WITH 309. HAND-OPERATED METERING FAUCETS SHALL |
| | REMAIN OPEN FOR 10 SECONDS MINIMUM. |
| | |
| | 2D) SHOW COMPLIANCE WITH THE 2014 ACCESSIBILITY CODE |
| | SECTION 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY |
| | AND DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES |
| | UNDER LAVATORIES AND SINKS. |
| | |
| | 3) SHEET A1 THE CORRIDOR IDENTIFIED AS 101 IS ALSO |
| | BEING USED AS A FILE ROOM. THE PLANS SHOW THIS ROOM AS |
| | PART OF THE EGRESS PATH THROUGH ADJOINING ROOMS. FBC-B |
| | SECTION 1014.2 (4) DOES NOT ALLOW FOR EGRESS THROUGH |
| | STORAGE ROOMS OR SPACES USED FOR SIMILAR PURPOSES. |
| | |
| | 4) SHEET A2 ONLY SHOWS THE 2 EXIT LIGHTS, THIS PLAN |
| | DOES NOT SHOW DIRECTIONAL SIGNAGE NOR EMERGENCY BACK UP |
| | LIGHTING, PLEAS SHOW COMPLIANCE WITH 2014 FBC-B 1006.3 |
| | EMERGENCY POWER FOR ILLUMINATION. |
| | |
| | 5A) THE PLANS DO NOT INDICATE WHERE COMPLIANCE WITH |
| | SECTION 703.2 OF THE ACCESSIBILITY CODE CAN BE FOUND. |
| | 703.2 RAISED CHARACTERS. |
| | RAISED CHARACTERS SHALL COMPLY WITH 703.2 AND SHALL BE |
| | DUPLICATED IN BRAILLE COMPLYING WITH 703.3. RAISED |
| | CHARACTERS SHALL BE INSTALLED IN ACCORDANCE WITH 703.4. |
| | |
| | 5B) 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND. |
| | TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES |
| | (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND |
| | SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST |
| | TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| | BASELINE OF THE HIGHEST TACTILE CHARACTER. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |