Plan Review Details - Permit 16120096
Plan Review Stops For Permit 16120096
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-23 Cont ID  
Sent By cthroop Date 2017-01-23 Time 14:45 Rev Time 0.00
Received By cthroop Date 2017-01-23 Time 14:45 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-13 Cont ID  
Sent By cthroop Date 2017-01-13 Time 09:21 Rev Time 0.00
Received By cthroop Date 2017-01-13 Time 09:21 Sent To  
Notes
2017-01-13 09:25:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SPECIFY FLOORING TO BE INSTALLED.
 2. PROVIDE ASTM E-90, ASTM E-492 AND IF WOOD FLOORING
 ASTM E-84 (FLAMESPREAD) FOR FLOORING UNDERLAYMENT.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 49
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-14 Cont ID  
Sent By cthroop Date 2016-12-14 Time 12:51 Rev Time 0.00
Received By cthroop Date 2016-12-14 Time 12:17 Sent To E
Notes
2016-12-14 13:02:46BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. STATE GOVERNING CODES ON PLANS.
 2. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC
 107.
 3. STATE R VALUE OF INSULATION AT EXT. WALLS.
 4. PROVIDE ASTM'S FOR FLOORING UNDERLAYMENT. (E-84
 FLAME SPREAD), (E-90 AIRBORNE SOUND) & (E-492 IMPACT
 SOUND).
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 49
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-11 Cont ID  
Sent By mvaldes Date 2017-01-11 Time 17:43 Rev Time 0.00
Received By mvaldes Date 2017-01-11 Time 16:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-14 Cont ID  
Sent By mvaldes Date 2016-12-14 Time 16:22 Rev Time 0.00
Received By mvaldes Date 2016-12-14 Time 16:08 Sent To P
Notes
2016-12-14 16:28:301ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] THE SCOPE OF WORK, JOB ADDRESS & APPLICABLE CODE
 SHALL APPEAR ON THE DRAWING ALONG WITH THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 CITY AMENDMENTS TO FBC 107.2.1.
  
 2] A MINIMUM 20 AMP CIRCUIT IS REQUIRED FOR THE
 BATHROOM. NEC 210.11(C)(3)
  
 3] SHOW A GFCI PROTECTED RECEPTACLE OUTLET WITHIN 3' OF
 BATH SINK EDGE. NEC 210.52 (D) & 210.8(A)(1).

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-01 Cont ID  
Sent By gjohnson Date 2017-02-01 Time 13:34 Rev Time 0.00
Received By gjohnson Date 2017-01-17 Time 11:12 Sent To  
Notes
2017-01-18 11:13:06RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-13 Cont ID  
Sent By cthroop Date 2017-01-13 Time 09:21 Rev Time 0.00
Received By cthroop Date 2017-01-11 Time 14:29 Sent To  
Notes
2017-01-11 14:29:44B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-22 Cont ID  
Sent By gjohnson Date 2016-12-22 Time 14:46 Rev Time 0.00
Received By gjohnson Date 2016-12-05 Time 13:29 Sent To  
Notes
2016-12-05 13:30:16BLDG MISC 2

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-02-01 Cont ID  
Sent By gjohnson Date 2017-02-01 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2017-02-01 Time 13:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 12:51 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 12:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-22 Cont ID  
Sent By gjohnson Date 2016-12-22 Time 14:45 Rev Time 0.00
Received By gjohnson Date 2016-12-22 Time 14:40 Sent To  
Notes
2016-12-22 14:45:201ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. PROVIDE DETAILED SCOPE OF PLUMBING WORK INCLUDING
 PLUMBING RISER. PER WPB AMEND TO FBC 107.2.1
  
 2. COMPLY WITH BUILDING AND ELECTRICAL COMMENTS. PER
 WPB AMEND TO FBC 107.2.1