| Plan Review Stops For Permit 16120061 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-10 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-10 |
Time |
07:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-06 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-06 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2017-02-06 17:30:35 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THERE ARE SOME ISSUES WITH THE ENERGY FORMS R405 - | | | 2014 THAT WERE SUBMITTED. PLEASE CORRECT. FBC ENERGY | | | CONSERVATION RESIDENTIAL PROVISIONS | | | B) THE OWNER/AGENT'S SIGNATURE IS REQUIRED ON THE FORM | | | PER FBC ENERGY CONSERVATION SECTION R103.1.1.2. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-01-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-20 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-19 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2017-01-20 14:35:22 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE 6 FT HIGH FENCE SHOWN IN DETAIL 4 ON AS-1, | | | SPECIFIES A 4 X 4 X 6' PT. POST. THE POSTS FOR THE 6 FT | | | FENCE WILL HAVE TO BE 8 FT IN ORDER TO HAVE 2 FT IN THE | | | GROUND. PLEASE CORRECT. FBC 107.2.1 | | | | | | 2) THERE IS A NOTE THAT SPECIFIES HARDIPLANK SIDING ON | | | THE GABLE END ON WALL SECTION 2 ON S1.1. THE REST OF | | | THE PLANS INDICATE THAT THE GABLE WILL BE STUCCO WITH | | | SIMULATED 6" HORIZONTAL LAPS. PLEASE CLARIFY. FBC | | | 107.2.1 NOTE: IF HARDI PLANK IS USED, SUBMIT TWO SETS | | | OF PRODUCT APPROVALS FOR IT PER FBC 107.3.4.1. | | | | | | 3) THERE ARE SOME ISSUES WITH THE ENERGY FORMS R405 - | | | 2014 THAT WERE SUBMITTED. PLEASE CORRECT. FBC ENERGY | | | CONSERVATION RESIDENTIAL PROVISIONS | | | A) THERE WERE TWO ENERGY FORMS SUBMITTED WITH DIFFERNT | | | INFORMATION. THE NUMBER OF OCCUPANTS AND THE ATTIC VENT | | | RATIO ARE DIFFERENT. PLEASE CLARIFY AND REMOVE THE ONE | | | THAT IS NOT SPECIFIC TO THIS PROJECT. FBC 107.2.1 | | | B) THE OWNER/AGENT'S SIGNATURE IS REQUIRED ON THE FORM | | | PER FBC ENERGY CONSERVATION SECTION R103.1.1.2. | | | C) THE FORM LISTS A 50 GAL. WATER HEATER AND A 40 GAL. | | | WATER HEATER IS SPECIFIED ON PLAN SHEET P-1.0. | | | D) THE FORM SPECIFIES A HIP ROOF AND THE PLANS SHOW A | | | GABLE ROOF. | | | E) THE PERMIT OFFICE IS WEST PALM BEACH AND THE | | | JURISDICTION IS 604700. THESE WERE LEFT BLANK ON THE | | | FORM. | | | | | | 4) THE PLANS SPECIFY LOMANCO 700 SERIES LOUVERED STATIC | | | ROOF VENTS. THE PRODUCT APPROVAL NUMBER ON THE PLANS | | | AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR | | | LOMANCO WHIRLYBIRD WIND TURBINES (NOA NO. 15-0831.08). | | | THE PRODUCT APPROVAL FOR THE LOMANCO 700 SERIES VENTS | | | IS NOA NO. 16-0510.28. NOTE: IF YOU USE THE WIND | | | TURBINES PLEASE BE ADVISED THAT THE TAS 110 (A) | | | STANDARD TO WHICH THEY WERE TESTED REQUIRES THAT THE | | | TURBINE UNIT BE REMOVED AND REPLACED WITH A STORM CAP | | | WHEN TESTING FOR WINDSPEED AND WATER SPRAY ABOVE A 70 | | | MPH WINDSPEED. FBC TEST PROTOCALS FOR HIGH VELOCITY | | | HURRICANE ZONES (TAS) NO. 100(A)-95 | | | | | | 5) THE VALUATION HAS BEEN ADJUSTED FROM $130,000.00 TO | | | $146,586.71 BASED ON CURRENT ICC VALUATION DATA. FBC | | | 109.3. | | | | | | 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-01-30 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2017-01-30 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2017-01-30 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-01-12 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2017-01-12 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2017-01-12 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2017-01-12 15:15:53 | JOB PERMIT NUMBER: 16120061 | | | JOB ADDRESS: 1110 18TH STREET | | | WEST PALM BEACH FLORIDA | | | DATE: JANUARY 12, 2017 | | | ELECTRICAL PLAN REVIEW COMMENTS | | | | | | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC | | | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, | | | (RESIDENTIAL FLORIDA BUILDING CODE) AS WELL AS THE CITY | | | OF WEST PALM BEACH AMENDMENTS. SEE BELOW A LIST OF | | | ITEMS NOTED. | | | | | | 1] PROVIDE A MAIN DISCONNECT OUTSIDE NEAREST THE POINT | | | OF ENTRANCE OF THE SERVICE CONDUCTORS IN ACCORDANCE | | | WITH FBC-R SECTION E3601.6.2. | | | | | | 2] PROVIDE A SWITCHED LIGHTING OUTLET FOR EXTERIOR | | | EGRESS ILLUMINATION ON THE STORAGE SHED PER FBC-R | | | SECTION E3903.3. | | | | | | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | | MENTIONED ITEMS. IF YOU HAVE FURTHER QUESTIONS, PLEASE | | | DON'T HESITATE TO CONTACT ME DIRECTLY. | | | | | | 1ST REVIEW | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-10 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-09 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-06 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-26 |
Time |
12:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-01-25 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-01-25 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-12-14 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-19 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-19 |
Time |
18:39 |
Sent To |
|
|
| Notes |
| 2017-01-19 18:39:53 | MU-2016-29588, PAID $9,585.84 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-10 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-10 |
Time |
07:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-06 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-06 |
Time |
17:31 |
Sent To |
|
|
| Notes |
| 2017-02-06 17:31:56 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS. M1401.3 SIZING. HEATING AND | | | COOLING EQUIPMENT AND APPLIANCES SHALL BE SIZED IN | | | ACCORDANCE WITH ACCA MANUAL S BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-01-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-20 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-20 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2017-01-20 13:37:56 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS. M1401.3 SIZING. HEATING AND | | | COOLING EQUIPMENT AND APPLIANCES SHALL BE SIZED IN | | | ACCORDANCE WITH ACCA MANUAL S BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-19 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-19 |
Time |
17:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2017-01-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-20 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-20 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2017-01-20 09:10:29 | OWENS CORNING ASPHALT ROOF SHINGLES FL10674-R12 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2017-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-10 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-10 |
Time |
07:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2017-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-02-06 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-02-06 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2017-02-06 17:37:24 | THE FOLLOWING CONSTRUCTION DOCUMENTS ARE REQUIRED TO | | | HAVE THE SEAL AND ORIGINAL SIGNATURE OF THE FLORIDA | | | LICENSED ENGINEER OR SURVEYOR ON THEM. THE SOIL REPORT, | | | THE SURVEY THE TRUSS DRAWINGS AND TRUSS LAYOUT. | | | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL | | | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL | | | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT | | | APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE | | | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE | | | REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15 | | | FLORIDA ADMINISTRATIVE CODE, CHAPTER 472, FLORIDA | | | STATUTES OR CHAPTER 481, FLORIDA STATUTES & 61G1 | | | FLORIDA ADMINISTRATIVE CODE. WHERE SPECIAL CONDITIONS | | | EXIST, THE BUILDING OFFICIAL IS AUTHORIZED TO REQUIRE | | | ADDITIONAL CONSTRUCTION DOCUMENTS TO BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA | | | DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE | | | BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF | | | SUBMITTALS. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2017-01-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-01-20 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-01-20 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2017-01-20 13:58:25 | THE FOLLOWING CONSTRUCTION DOCUMENTS ARE REQUIRED TO | | | HAVE THE SEAL AND ORIGINAL SIGNATURE OF THE FLORIDA | | | LICENSED ENGINEER OR SURVEYOR ON THEM. THE SOIL REPORT, | | | THE SURVEY THE TRUSS DRAWINGS AND TRUSS LAYOUT. | | | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL | | | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL | | | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT | | | APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE | | | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE | | | REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15 | | | FLORIDA ADMINISTRATIVE CODE, CHAPTER 472, FLORIDA | | | STATUTES OR CHAPTER 481, FLORIDA STATUTES & 61G1 | | | FLORIDA ADMINISTRATIVE CODE. WHERE SPECIAL CONDITIONS | | | EXIST, THE BUILDING OFFICIAL IS AUTHORIZED TO REQUIRE | | | ADDITIONAL CONSTRUCTION DOCUMENTS TO BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA | | | DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE | | | BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF | | | SUBMITTALS. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2017-01-05 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-01-05 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-01-05 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2017-01-05 14:55:33 | 1/5/17- PASSED | | | | | | FRONT SETBACK MEETS CONTEXTUAL SETBACK OF THE | | | NEIGHBORHOOD | | | REAR SETBACK IS 22.6FT. MEETING THE 10FT. REQUIREMENT | | | SIDE SETBACK IS 5FT. MINIMUM 14FT. TOTAL MEETING THE | | | 5FT. MINIMUM 10FT. TOTAL REQUIREMENT | | | ONE PARKING SPACE | | | MEETS 40FT. HEIGHT LIMIT | | | MEETS ARCHITECTURAL STANDARDS | | | | | | PLEASE CONTACT | | | NATHAN WIRA | | | [email protected] | | | (561)822-1442 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-12-30 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-12-30 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-12-30 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2016-12-30 12:14:28 | 12/30/16- FAILED | | | | | | SF-11 SINGLE FAMILY LOW DENSITY RESIDENTIAL | | | APPROVED LANDSCAPE PLANS REQUIRED | | | | | | FAILED | | | 1. CORNER SETBACK IS 9.17FT. WHICH DOESN'T MEET THE | | | 12FT. REQUIREMENT | | | 2. FRONT SETBACK IS 6.23FT. WHICH DOESN'T MEET THE | | | 25FT. REQUIREMENT | | | 3. SIDE SETBACK DOESN'T MEET THE 5FT. MINIMUM 15FT. | | | TOTAL | | | | | | PASSED | | | 1. ONE KITCHEN MAKES THIS ONE(1)UNIT | | | 2. BUILDING HEIGHT IS 14FT. 4 AND 1/2IN. | | | | | | PLEASE CONTACT | | | NATHAN WIRA | | | [email protected] | | | (561)822-1442 | | | |
|
|