Plan Review Details - Permit 16120057
Plan Review Stops For Permit 16120057
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-12-12 Cont ID  
Sent By mvaldes Date 2016-12-12 Time 14:09 Rev Time 0.00
Received By mvaldes Date 2016-12-12 Time 12:46 Sent To  
Notes
2016-12-12 14:11:481ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1] BOND LOW VOLTAGE METAL RACKS WITH MINIMUM 6 AWG. NEC
 645.15, 250.134-136.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-12 Cont ID  
Sent By mvaldes Date 2016-12-12 Time 14:09 Rev Time 0.00
Received By mvaldes Date 2016-12-02 Time 15:05 Sent To  
Notes
2016-12-05 15:06:07ROUTED TO ELECTRICAL INBOX