Plan Review Details - Permit 16120008
Plan Review Stops For Permit 16120008
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-12 Cont ID  
Sent By cthroop Date 2016-12-12 Time 10:41 Rev Time 0.00
Received By cthroop Date 2016-12-12 Time 10:41 Sent To  
Notes
2016-12-12 10:47:13BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PROVIDE DETAIL OF FOUNDATIONS. INCLUDE ELEVATION TO
 GRADE AND REINFORCING.
 2. PROVIDE DEMENSIONS OF LUMBER - WIDTH X HEIGHT X
 LENGTH.
 3. PROVIDE DESIGN WIND LOADS FOR PERGOLA.
 4. PROVIDE FASTENER SCHEDULE. FASTENERS SHALL MEET OR
 EXCEED DESIGN REQUIREMENTS.
 5. STATE GOVERNING CODES ON PLANS.
 6. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC
 107.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-12 Cont ID  
Sent By cthroop Date 2016-12-12 Time 10:41 Rev Time 0.00
Received By cthroop Date 2016-12-01 Time 09:27 Sent To  
Notes
2016-12-02 09:27:56ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status F Date 2016-12-06 Cont ID  
Sent By njwira Date 2016-12-06 Time 15:55 Rev Time 0.00
Received By njwira Date 2016-12-02 Time 13:48 Sent To B
Notes
2016-12-06 15:56:4512/6/16- FAILED
  
 SF-7 SINGLE FAMILY LOW DENSITY HISTORIC
 0FT. SIDE SETBACK DOESN'T MEET 5FT. REQUIREMENT
 25FT. REAR SETBACK MEETS 5FT. REQUIREMENT
 DOESN'T EXCEED 25FT HIGH
 NO TREES BEING REMOVED
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  