Plan Review Details - Permit 16111259
Plan Review Stops For Permit 16111259
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-04 Cont ID  
Sent By shill Date 2017-08-04 Time 17:36 Rev Time 0.00
Received By shill Date 2017-08-04 Time 17:36 Sent To  
Notes
2017-08-04 17:37:12SEE PROVISOS UNDER PERMIT APPLICATION #16111261
  
 **********************************
 BUILDING SUMMARY
  
 16111261 BLDG 1 (NORTH)
 16111265 BLDG 2 (SOUTH)
 16111259 CLUBHOUSE
  
 SEE REVIEWS UNDER PERMIT APPLICATION #16111261
  
 **************************
 BUILDING SUMMARY
  
 16111261 BLDG 1 (NORTH)
 16111265 BLDG 2 (SOUTH)
 16111259 CLUBHOUSE
  
 16111259 BUILDING DATA FOR C.O./REPORTING
 USC-404 TYPE 434 - ALT RESIDENTIAL
 SQUARE FEET - 2801
  
 CONSTRUCTION TYPE: 14-3-B
 UNITS: 1
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 2801
 SQ FT FOOTPRINT: 2801
 SQ FT ROOF: 2801
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: CLUBHOUSE
 SPRINKLER SYS?
 SPRK REQ'D?
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B (AND A3)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-06-28 Cont ID  
Sent By shill Date 2017-06-28 Time 14:02 Rev Time 0.00
Received By shill Date 2017-06-28 Time 10:30 Sent To  
Notes
2017-06-28 15:04:18SEE REVIEWS UNDER PERMIT APPLICATION #16111261
  
 **************************
 BUILDING SUMMARY
  
 16111261 BLDG 1 (NORTH)
 16111265 BLDG 2 (SOUTH)
 16111259 CLUBHOUSE
  
 16111259 BUILDING DATA FOR C.O./REPORTING
 USC-404 TYPE 434 - ALT RESIDENTIAL
 SQUARE FEET - 2801
  
 CONSTRUCTION TYPE: 14-3-B
 UNITS: 1
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 2801
 SQ FT FOOTPRINT: 2801
 SQ FT ROOF: 2801
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: CLUBHOUSE
 SPRINKLER SYS?
 SPRK REQ'D?
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-28 Cont ID  
Sent By shill Date 2017-03-28 Time 16:32 Rev Time 0.00
Received By shill Date 2017-03-27 Time 16:22 Sent To  
Notes
2017-03-28 16:32:39SEE REVIEWS UNDER PERMIT APPLICATION #16111261
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-07 Cont ID  
Sent By ccole Date 2016-12-07 Time 10:29 Rev Time 0.00
Received By shill Date 2016-12-09 Time 16:24 Sent To  
Notes
2016-12-09 16:24:31SEE REVIEWS UNDER PERMIT APPLICATION #16111261
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By vperez Date 2017-03-27 Time 07:12 Rev Time 0.00
Received By vperez Date 2017-03-27 Time 07:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-31 Cont ID  
Sent By vperez Date 2017-01-31 Time 10:00 Rev Time 0.00
Received By vperez Date 2017-01-31 Time 10:00 Sent To  
Notes
2017-01-31 10:01:21FAILED BY MARIO VALDES-
2017-01-31 09:59:58JOB PERMIT NUMBER: 16111261
 JOB ADDRESS: 2100 NORTH AUSTRALIAN AVE
 WEST PALM BEACH FLORIDA
 DATE: JANUARY 4, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] FIRE ALARM, LOW VOLTAGE, & SITE LIGHTING SHALL BE
 SUBMITTED UNDER A SEPARATE PERMIT WITH SEPARATE SHOP
 DRAWINGS.
  
 2] A MINIMUM OF 75% OF PERMANENTLY INSTALLED LUMINAIRES
 SHALL BE HIGH EFFICIENT & RECESSED LIGHTS INSTALLED IN
 BUILDING THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR
 LEAKAGE BETWEEN CONDITIONED & UN-CONDITIONED SPACES,
 THE HOUSING CANS IF IN CONTACT WITH THERMAL INSULATION
 SHALL BE LISTED IC-RATED. FBC-ENERGY SECTIONS R402.4.4
 & R404.1 (ADD A NOTE ON SHEET E0.1)
  
 3] OPENINGS AROUND ELECTRICAL PENETRATIONS INTO OR
 THROUGH FIRE RESISTANT WALLS, PARTITIONS, FLOORS, &
 CEILINGS SHALL BE FIRE STOPPED USING APPROVED METHODS
 TO MAINTAIN THE FIRE RATING. NEC 300.21 THIS APPLIES TO
 HALLWAY CORRIDORS IN SHEETS E1.1, E1.2, E1.3. (ADD A
 NOTE)
  
 4] DEPENDING ON CONDUIT ROUTING PLEASE REFERENCE NEC
 310.15 FOR TEMPERATURE ADJUSTMENT & CORRECTIONS FOR
 CONDUCTORS BEING RAN ON THE ROOFTOP EXPOSED TO DIRECT
 SUNLIGHT. ADD A NOTE ON SHEET E1.4.
  
 5] PROVIDE AFCI PROTECTION TO NEW OR MODIFIED CIRCUITS
 IN ACCORDANCE WITH NEC 210.12(A)(B). ADD A NOTE ON
 SHEET E2.1, E2.2, E2.3.
  
 6] PROVIDE ILLUMINATION FOR THE PANELBOARD ON BEDROOM 1
 PER NEC 110.26(D).
  
 7] CLARIFY IF DISTRIBUTION PANELS ARE ACCESSIBLE TO
 TENANT'S OR IS THEIR MAINTENANCE PERSONNEL WITH KEY
 LOCK ACCESS IN ACCORDANCE WITH NEC 240.24(B).
  
 8] PROVIDE EMERGENCY LIGHTING IN MEN'S/WOMAN'S BATHROOM
 & MECHANICAL ROOM FOR MEANS OF EGRESS ILLUMINATION PER
 FBC 1006.
  
 9] SHOW IDENTIFICATION ON THE RISER DIAGRAM OF UNIT #'S
 ON THE MAIN DISCONNECTS & THE DISTRIBUTION PANELS SHALL
 HAVE THE SOURCE OF SUPPLY MARKING PER NEC 225.37,
 408.4(B).
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-05-31 Cont ID  
Sent By pleduc Date 2017-05-31 Time   Rev Time 0.00
Received By pleduc Date 2017-05-31 Time 12:13 Sent To  
Notes
2017-05-31 12:13:41THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-29 Cont ID  
Sent By pleduc Date 2017-03-29 Time   Rev Time 0.00
Received By pleduc Date 2017-03-29 Time 14:57 Sent To  
Notes
2017-03-29 14:59:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-16 Cont ID  
Sent By pleduc Date 2016-12-16 Time   Rev Time 0.00
Received By pleduc Date 2016-12-16 Time 09:34 Sent To  
Notes
2016-12-16 09:37:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PLEASE REFER TO COMMENTS OF PERMIT # 16111261.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-10-02 Cont ID  
Sent By tklarge Date 2017-10-02 Time 12:28 Rev Time 0.00
Received By tklarge Date 2017-09-26 Time 15:51 Sent To  
Notes
2017-09-27 15:51:21RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-08-30 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-01 Time 09:58 Sent To  
Notes
2017-08-02 09:59:13C36

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-28 Cont ID  
Sent By shill Date 2017-06-28 Time 14:03 Rev Time 0.00
Received By shill Date 2017-05-25 Time 12:04 Sent To  
Notes
2017-05-26 12:07:03C37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-25 Cont ID  
Sent By gjohnson Date 2017-04-25 Time 16:39 Rev Time 0.00
Received By gjohnson Date 2017-03-23 Time 14:00 Sent To  
Notes
2017-03-24 14:05:26C33
 *TRAVELLING TOGETHER 16111259, 16111261, 16111265*

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-31 Cont ID  
Sent By vperez Date 2017-01-31 Time 10:01 Rev Time 0.00
Received By vperez Date 2017-01-31 Time 10:01 Sent To  
Notes
2016-12-02 10:28:11C29
 **TRAVELLING WITH 16111261 & 16111265**

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-12-12 Cont ID  
Sent By shill Date 2016-12-12 Time 14:24 Rev Time 0.00
Received By shill Date 2016-12-12 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-08-30 Cont ID  
Sent By ccole Date 2017-08-30 Time 12:26 Rev Time 0.00
Received By ccole Date 2017-08-30 Time 11:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-06-08 Cont ID  
Sent By ccole Date 2017-06-08 Time 16:51 Rev Time 0.00
Received By ccole Date 2017-06-08 Time 16:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-29 Cont ID  
Sent By ccole Date 2017-03-29 Time 10:16 Rev Time 0.00
Received By ccole Date 2017-03-29 Time 09:54 Sent To  
Notes
2017-03-29 10:40:062ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16111259
 3/29/17
  
 1) SHEET M3.2: INDICATE THE NUMBER OF CLIPS TO BE
 INSTALLED ON THE CONDENSER UNITS. PROVIDE TWO COPIES OF
 FL. PRODUCT APPROVAL #19731 WITH A SHOP DRAWING
 APPROVAL STAMP BY THE ARCHITECT OF RECORD. THE
 ARCHITECT MUST ALSO CIRCLE, HIGHLIGHT, OR OTHERWISE
 MARK ALL APPLICABLE ANCHORING DETAILS, NOTES, DESIGN
 PRESSURES ETC. ON THE PRODUCT APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2017-03-29 10:31:42 
  
  
2017-03-29 10:09:12 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-07 Cont ID  
Sent By ccole Date 2016-12-07 Time 10:29 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 17:48 Sent To  
Notes
2016-12-07 10:44:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16111259
 12/7/16
  
 1) SHEET M1.1: PROVIDE THE EFFICIENCY RATING OF THE
 10-TON UNIT IN THE SCHEDULE.
  
 2) SUBMIT AN AC CHANGEOUT FORMS FOR THE REPLACED
 SYSTEM. THE FORM CAN BE FOUND ON THE DEVELOPMENT
 SERVICES WEBSITE- WWW.CITYOFWPB.COM.
  
 3) ENERGYGAUGE COMPLIANCE FORM: A) CORRECT THE SYSTEM
 NUMBER TO SYSTEM 4 TO MATCH THE PLANS. B) COMPLETE THE
 MANDATORY REQUIREMENTS CHECKLIST ON PAGE 7.
  
 4) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR
 ANCHORING THE NEW CU.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2017-10-02 Cont ID  
Sent By tklarge Date 2017-10-02 Time 12:28 Rev Time 0.00
Received By tklarge Date 2017-10-02 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2017-08-25 Cont ID  
Sent By tklarge Date 2017-08-25 Time 14:50 Rev Time 0.00
Received By tklarge Date 2017-08-25 Time 13:56 Sent To  
Notes
2017-08-25 13:56:561) SHT. P1.1 - PLUMBING NOTES - THERE IS A NOTE STATING
 THAT PVC IN THE PLENUM CLOSET IS TO BE WRAPPED WITH
 PLENUM RATED ARMAFLEX. PVC IS NOT RATED FOR USE WITHIN
 A PLENUM. THE ARMAFLEX MAY BE APPROVED FOR USE IN A
 PLENUM BUT THE PVC WITHIN THE PLENUM IS STILL A
 VIOLATION. THE ARMAFLEX DOES NOT PROTECT THE PVC FROM
 IGNITION AND DOES NOT MEET THE INTENT OF THE CODE.
 COMPLY WITH 2014 FBC - MECHANICAL SEC.602.2.
 2) REMOVE SHEETS P3.8 & P3.9 AS NOTED IN NARRATIVE FROM
 DESIGN PROFESSIONAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-06-28 Cont ID  
Sent By tklarge Date 2017-06-28 Time 06:03 Rev Time 0.00
Received By tklarge Date 2017-06-28 Time 03:12 Sent To  
Notes
2017-06-28 04:29:321) SHOW THE DIMENSIONS (LXW) OF THE REQUIRED CLEAR
 FLOOR SPACE FOR THE WATER CLOSETS, LAVATORIES, KITCHEN
 SINKS & SHOWERS IN THE UFAS UNITS. THE REQUIRED CLEAR
 FLOOR SPACE FOR THE FIXTURES SHALL COMPLY WITH UFAS
 SECS.4.34.5.2 THROUGH 4.34.6.5.
 2) SUBMIT DETAILS FOR THE REQUIRED REINFORCEMENT FOR
 GRAB BARS FOR THE WATER CLOSETS & SHOWERS. COMPLY WITH
 UFAS SECS. 4.34.5.2 (3), 4.34.5.5 (3) & FIGURES 47 (B)
 & FIG. 49. SHOW THE MINIMUM AND MAXIMUM MEASUREMENTS
 FROM THE FLOOR AND THE MINIMUM LENGTHS AND DIMENSIONS
 OF THE REINFORCING ON SHTS. A5.2, A5.3 & A5.4.
 3) SUBMIT AN ELEVATION DETAIL OF THE HILO DRINKING
 FOUNTAIN.COMPLY WITH UFAS SECS. 4.1.6, 4.4.1.2, 4.15.
 4) SHT.A5.4 - DETAIL #1 - SHOW THE DIMENSIONS OF THE
 CLEAR FLOOR SPACES REQUIRED FOR THE ACCESSIBLE
 LAVATORIES AND WATER CLOSETS.
 5) SHT. A5.4 - DETAILS A,B,C & D SHOWS A GRAB BAR IN
 THE TOILET ROOM ACCESSIBLE STALL MOUNTED IN THE
 VERTICAL POSITION BUT UFAS SEC.4.17.6 AND FIG. (A) SHOW
 THE GRAB BARS ONLY IN A HORIZONTAL POSITION. GRAB BARS
 INSTALLED IN A VERRTICAL POSITION DO NOT APPEAR TO
 COMPLY WITH UFAS. CLARIFY.
 6) SHT. A5.4 - ELEVATION DETAILS "A" & "B" DO NOT
 APPEAR TO CORRELATE WITH THE PLAN VIEW ON DETAIL #1 -
 CLARIFY.
 7) A6.4 - DETAIL #1 - THE HEIGHT OF THE SINK IN THE
 CLUBHOUSE ACTIVITY ROOM SHALL BE A MAXIMUM OF 34 INCHES
 ABOVE THE FINISH FLOOR. UFAS SEC. 4.24.2.
 8) SHT. P1.1 - PLUMBING NOTES - THERE IS A NOTE STATING
 THAT PVC IN THE PLENUM CLOSET IS TO BE WRAPPED WITH
 PLENUM RATED ARMAFLEX. PVC IS NOT RATED FOR USE WITHIN
 A PLENUM. SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATIONS FOR THE PLENUM RATED ARMAFLEX AND
 DETAILS AS TO HOW THE ARMAFLEX WILL BE INSTALLED ON THE
 PVC PIPE.WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHT. P1.1 - WATER HEATER DETAIL - HEAT TRAPS ARE
 REQUIRED ON THE HOT AND COLD WATER LINES OF THE WATER
 HEATER. 2014 FBC-ENERGY SEC.C404.4,
 10) SHT. P2.2 - SHUTOFF VALVES ARE REQD. AT THE BASE OF
 THE WATER RISERS. 2014 FBC-PLUMBIING SEC.606.1 (4).
 11) SHTS. P3.1, P3.2, P3.3, & P3.5 - THE HUB DRAIN
 SHALL CONNECT TO THE SANITARY SYSTEM DOWNSTREAM OF THE
 WATER CLOSET.
 12) SHT. P3.8 THE NOTE UNDER THE TAG FOR RISER S-8
 REFERS TO SHT. P3.7 S-8 RISER IS NOT SHOWN ON P3.7.
 PLEASE PROVIDE.
 13) SHT P3.8 WATER CLOSET IN HALF BATH IS NOT VENTED IT
 SHALL BE VENTED BEFORE IT CONNECTS TO THE BUILDING
 DRAIN. PER FBC-PLBG. SEC.901.2.1
 14) SHT. P3.7 + P3.9 APEAR TO BE THE SAME PLAN.PLEAS
 CLARIFY. WPB AMEND TO FBC 107.2.1.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-04-25 Cont ID  
Sent By gjohnson Date 2017-04-25 Time 16:16 Rev Time 0.00
Received By gjohnson Date 2017-04-25 Time 16:16 Sent To  
Notes
2017-04-25 16:38:482ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. P3.4 THE HUB DRAIN SHALL CONNECT TO THE WET
 VENT DOWN STREAM OF BRANCH DRAIN OF WATER CLOSET. FBC
 PL 912.1
  
 2. SHT. P3.2 THE HUB DRAIN SHALL CONNECT TO THE WET
 VENT DOWN STREAM OF BRANCH DRAIN OF THE LAVATORY. FBC
 PL 912.1
  
 3.SHT. P3.8 THE NOTE UNDER THE TAG FOR RISER S-8 REFERS
 TO SHT. P3.7 S-8 RISER IS NOT SHOWN ON P3.7 PLEASE
 PROVIDE.
  
 4. SHT P3.8 WATER CLOSET IN HALF BATH IS NOT VENTED IT
 SHALL BE VENTED BEFORE IT CONNECTS TO THE BUILDING
 DRAIN. PER FBC PL901.2.1
  
 5. SHT. P3.7 + P3-9 APEAR TO BE THE SAME PLEAS CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-22 Cont ID  
Sent By gjohnson Date 2016-12-22 Time 13:22 Rev Time 0.00
Received By gjohnson Date 2016-12-22 Time 13:22 Sent To  
Notes
2016-12-22 13:22:181ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW WHEELCHAIR TURNING SPACE IN ACCESSIBLE
 BATHROOMS. PER UFAS 4.2.3 AND 4.23.3
  
 2. PROVIDE DIMENSIONS FOR THE SHOWER CONTROLS OFF THE
 FRONT OF THE SHOWER STALL. PER UFAS 4.34.5.5(4)
  
 3. SHOW TRAP PRIMERS FOR HUB DRAINS ON RISER DIAGRAMS.
 PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. P3.2 AND P3.4 RISER DETAIL W1 AND W2 ARE NAMED
 AS SANITARY RISER PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 5. SHT. P3.2 AND P3.4 RISER DETAIL W1 AND W2 ARE THESE
 EXISTING TO REMAIN OR ARE THEY NEW PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 6. SHT. P3.7 RISER S7 AND P3.8 WC1 IN POWDER ROOM
 SHOULD BE VENTED BY LAV STACK IN POWDER ROOM. FBC PL
 901.2.1
  
 7. SHT P3.8 WATER RISER W3 IS IT EXISTING TO REMAIN OR
 ARE THEY NEW PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 8. SHT. P3.8 S7 THE WATER CLOSETS ON THE FIRST FLOOR
 ARE NOT VENTED SHALL COMPLY WITH FBC PL 901.2.1
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-12-12 Cont ID  
Sent By shill Date 2016-12-12 Time 08:55 Rev Time 0.00
Received By shill Date 2016-12-12 Time 08:55 Sent To  
Notes
2016-12-12 08:56:47GAF SHINGLES PRODUCT APPROVAL 10124
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-06-08 Cont ID  
Sent By llouie Date 2017-06-08 Time   Rev Time 0.00
Received By llouie Date 2017-06-08 Time   Sent To  
Notes
2017-06-08 08:39:58- INTERIOR/EXTERIOR RENOVATIONS ONLY TO BUILDING #1, #2
 AND CLUBHOUSE.
  
 - DOES NOT INCLUDE SITE MODIFICATIONS (I.E. MONUMENT
 SIGN, FENCE, TOT LOT AND PARKING AREA STRIPING).
  
 CONTACT LINDA LOUIE @ 561-822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-04-03 Cont ID  
Sent By llouie Date 2017-04-03 Time   Rev Time 0.00
Received By llouie Date 2017-04-03 Time   Sent To  
Notes
2017-04-03 13:02:48- INTERIOR/EXTERIOR BUILDING RENOVATIONS ONLY (BUILDING
 #1, #2 AND CLUBHOUSE).
  
 - DOES NOT INCLLUDE SITE MODIFICATIONS (I.E. MONUMENT
 SIGN, FENCE, TOT LOT AND PARKING AREA STRIPING).
 SEPARATE PERMITS REQUIRED.
  
 - CONTACT LINDA LOUIE @ 561-822-1458 IF THERE AREA
 QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-01-19 Cont ID  
Sent By llouie Date 2017-01-19 Time   Rev Time  
Received By llouie Date 2017-01-19 Time   Sent To  
Notes
2017-01-19 17:01:31 
 ** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY. THE
 SURVEY MUST BE LESS THAN 1 YEAR OLD.
  
 2.) THE SCOPE OF WORK DESCRIBED IN THE PERMIT
 APPLICATION INDICATES THAT ONLY INTERIOR WORK TO THE
 EXISTING RESIDENTIAL BUILDINGS AND THE CLUBHOUSE WILL
 BE DONE; HOWEVER, THE SITE PLAN (SHEET SP 1.1) ALSO
 SHOWS THAT EXTERIOR MODIFICATIONS PROPOSED FOR THE
 EXISTING RESIDENTIAL COMPLEX. SEPARATE PERMIT
 APPLICATIONS AND REVIEWS WILL BE REQUIRED FOR THE
 PROPOSED WORK (I.E. FREESTANDING SIGNAGE, NEW SHUFFLE
 BOARD COURT, NEW PLAYGROUND, PERIMETER FENCING,
 ENTRANCE GATES, ETC.).
  
 3.) THERE SEEMS TO BE A PROPOSED "CAR CARE AREA." THE
 CAR CARE AREA CANNOT BE PROVIDED UNLESS ADEQUATE
 PARKING IS PROVIDED FOR THE RESIDENTIAL DEVELOPMENT.
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE NUMBER OF
 EXISTING PARKING SPACES AND IF THE EXISTING PARKING
 MEETS CURRENT ZONING AND LAND DEVELOPMENT REGULATIONS
 REQUIREMENT FOR THE USE. THIS INFORMATION SHOULD BE
 DETAILED IN TABLE FORM IN THE SITE PLAN.
  
 4.) PROVIDE DETAILS FOR THE PROPOSED FENCE AND GATE
 SYSTEM.
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.