Plan Review Details - Permit 16111255
Plan Review Stops For Permit 16111255
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-04-27 Cont ID  
Sent By shill Date 2017-04-27 Time 15:19 Rev Time 0.00
Received By shill Date 2017-04-27 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-04-25 Cont ID  
Sent By shill Date 2017-04-25 Time 07:11 Rev Time 0.00
Received By shill Date 2017-04-24 Time 18:01 Sent To  
Notes
2017-04-24 18:04:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
  
 1. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB. THIS MAY BE SENT VIA EMAIL.
  
 2. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 PROVISO: FOR RACK STORAGE OVER 5 FOOT 9 INCHES TALL
 REQUIRES A SEPARATE PERMIT, PLANS AND ASSOCIATED FEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-06 Cont ID  
Sent By jwitmer Date 2017-04-06 Time 16:17 Rev Time 0.00
Received By jwitmer Date 2017-04-06 Time 11:01 Sent To  
Notes
2017-04-06 16:11:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16111255
 ADD: 2025 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 407-654-2521
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. APRIL 06/ 2017
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3A) SEMI-COMPLIED. SUBMITTED A FLORIDA APPROVAL FL17690
 FOR CURTAIN WALL CONSTRUCTION. THIS IS A 36 PAGE
 DOCUMENT, PLEASE CIRCLE (IDENTIFY) THE FOLLOWING :
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE., 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 3B) SUBMITTED A FLORIDA APPROVAL FL17693 EXTERIOR DOOR
 IS A 26 PAGE DOCUMENT, PLEASE CIRCLE (IDENTIFY) THE
 FOLLOWING :
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE., 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 1ST ROUND COMMENTS. SHEET A6 THE ELEVATIONS SHOW NEW
 GLAZING BEING INSTALLED, FL 17690 STOREFRONT PRODUCT
 APPROVAL WAS SUBMITTED FOR THIS REVIEW. PLEASE COMPLY
 WITH;
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) PROVISO: FOR RACK STORAGE OVER 5 FOOT 9 INCHES TALL
 REQUIRES A SEPARATE PERMIT, PLANS AND ASSOCIATED FEES.
  
 5) NEW COMMENT ALSO DEALS WITH THE MECHANICAL PLANS
 EXAMINERS COMMENTS SHEET M2 DETAIL 2 RTU ANCHORING.
 PLEASE NOTE THIS DESIGN IS FOR SEISMIC ZONES. WE ARE
 NOT IN A SEISMIC ZONE BUT A 170 MPH 3 SECOND GUST VULT
 WIND ZONE, EXPOSURE C AND A MEAN ROOF HEIGHT ABOVE 20
 FEET. PLEASE PROVIDE AN ANALYSIS FOR THE ANCHORING OF
 THE RTU TO THE CURB. 2014 FBC-B 1604.4 ANALYSIS. LOAD
 EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS
 SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS
 THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY,
 GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-12 Cont ID  
Sent By jwitmer Date 2016-12-12 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time 09:42 Sent To  
Notes
2016-12-12 11:50:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16111255
 ADD: 2025 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 407-654-2521
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 12/2016
 ACTION: DENIED
  
 1) THE TITLE SHEET T1 IN THE BOTTOM RIGHT CORNER OF THE
 PLAN SHOWS AN EGRESS PLAN WITH (2) REAR EXITS
 AND (1) FRONT EGRESS SET OF DOORS. THE TITLE SHEET ALSO
 STATES THERE IS 2,097 SQUARE FEET OF SUPPORT AREA, AND
 1,488 SQUARE FEET OF LOADING AND STORAGE AREA. THE
 TITLE SHEET A1 NOR A3 SHOW WHERE THE STORAGE/ LOADING
 AREAS ARE LOCATED AND WHERE THE (2) EGRESS AISLES ARE
 LOCATED WITHIN THESE AREAS. CODE COMPLIANCE WITH
 SECTION 1014.2 EGRESS THROUGH INTERVENING SPACES. 4.
 EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS,
 CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
  
 EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 2) SHEET A6 THE ELEVATIONS SHOW NEW GLAZING BEING
 INSTALLED, THE DOOR PRODUCT APPROVAL FL17693. PLEASE
 COMPLY WITH:
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) SHEET A6 THE ELEVATIONS SHOW NEW GLAZING BEING
 INSTALLED, FL 17690 STOREFRONT PRODUCT APPROVAL WAS
 SUBMITTED FOR THIS REVIEW. PLEASE COMPLY WITH;
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 4) NOTICE RACK STORAGE OVER 5 FOOT 9 INCHES TALL
 REQUIRES A SEPARATE PERMIT, PLANS AND ASSOCIATED FEES.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-04-25 Cont ID  
Sent By rlecky Date 2017-04-25 Time 11:54 Rev Time 0.00
Received By rlecky Date 2017-04-25 Time 11:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-28 Cont ID  
Sent By rlecky Date 2017-03-28 Time 11:02 Rev Time 0.00
Received By rlecky Date 2017-03-28 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-13 Cont ID  
Sent By rlecky Date 2016-12-13 Time 13:39 Rev Time 0.00
Received By rlecky Date 2016-12-13 Time 12:21 Sent To  
Notes
2016-12-13 13:40:1616111255
 2025 OKEECHOBEE BLVD.
 WEST PALM BEACH
 COMMERCIAL INTERIOR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE INTERIOR LIGHTING DETAIL/CALCULATION VERIFYING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405
  
 VERIFY THERE ARE GFCI PROTECTED RECEPTACLES LOCATED ON
 THE ROOF TOP FOR SERVICING THE AIR CONDITIONING
 EQUIPMENT. NEC 210.8, 210.63
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By scaldero Date 2017-03-27 Time 10:37 Rev Time 0.00
Received By scaldero Date 2017-03-27 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-05 Cont ID  
Sent By scaldero Date 2016-12-05 Time 11:12 Rev Time 0.00
Received By scaldero Date 2016-12-05 Time 10:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-27 Cont ID  
Sent By shill Date 2017-04-27 Time 15:19 Rev Time 0.00
Received By shill Date 2017-04-19 Time 13:26 Sent To  
Notes
2017-04-20 13:30:12C34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-06 Cont ID  
Sent By jwitmer Date 2017-04-06 Time 16:17 Rev Time 0.00
Received By jwitmer Date 2017-03-23 Time 13:42 Sent To  
Notes
2017-03-24 13:45:37C07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-21 Cont ID  
Sent By gjohnson Date 2016-12-21 Time 15:46 Rev Time 0.00
Received By gjohnson Date 2016-11-30 Time 14:08 Sent To  
Notes
2016-12-02 14:09:07C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-12-12 Cont ID  
Sent By jwitmer Date 2016-12-12 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time 11:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-04-24 Cont ID  
Sent By ccole Date 2017-04-24 Time 15:00 Rev Time 0.00
Received By ccole Date 2017-04-24 Time 15:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-28 Cont ID  
Sent By ccole Date 2017-03-28 Time 15:08 Rev Time 0.00
Received By ccole Date 2017-03-28 Time 15:08 Sent To  
Notes
2017-03-28 15:34:362ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16111255
 3/28/17
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, THE AC
 COOLING AND HEATING CALCULATIONS REQUIRE AN ENGINEER'S
 SIGNATURE AND SEAL- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION. PLEASE NOTE THAT THE AC SUMMARY
 CALCULATIONS THAT HAVE BEEN PREPARED BY GREG CHEROK,
 ARE SEPARATE DOCUMENTS FROM THE ENERGYGAUGE COMPLIANCE
 SUBMITTAL.
  
 2) SHEET M2: PROVIDE AN APPROVED SUBMITTAL FOR THE
 SEISMIC BRACKETS THAT ARE CONNECTING THE RTU TO THE
 CURB. PLEASE NOTE THAT ANCHORAGE OF ROOFTOP MECHANICAL
 IS TO BE DESIGNED IN ACCORDANCE WITH SECTION 1609 WIND
 LOADS FBC-14 BUILDING. THIS PROJECT IS NOT IN A SEISMIC
 ZONE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By ccole Date 2016-12-08 Time 13:54 Rev Time 0.00
Received By ccole Date 2016-12-08 Time 13:54 Sent To  
Notes
2016-12-08 14:33:051ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #1611255
 12/8/16
  
 1) CORRECT THE ENERGYGAUGE FORM TO SHOW THE CORRECT
 DATA FOR THE 4-TON HEAT PUMP SYSTEM. THE FORM IS
 INDICATING IT TO BE A10-TON SYSTEM.
  
 2) THE HEAT PUMP COOLING AND HEATING CALCULATIONS MUST
 BEAR THE SIGNATURE AND SEAL OF THE ENGINEER OF RECORD-
 SECTION C403.2.1 FBC-14 FBC-14 ENERGY CONSERVATION.
  
 3) COMMISSIONING IS REQUIRED IN ACCORDANCE WITH SECTION
 C408.1 FBC-14. PLEASE SUBMIT A COMMISSIONING PLAN OR
 PROVIDE AN OUTLINE ON THE PLAN DETAILING THE
 PROCEDURES. PLEASE NOTE THAT FINAL CO OF THE PROJECT IS
 CONTINGENT ON SUBMITTAL OF THE FINAL COMMISSIONING
 REPORT TO THE BUILDING OWNER
  
 4) DEMAND CONTROLLED VENTILATION IS REQUIRED PER
 SECTION C403.2.5.1. THE PLAN IS INDICATING ONLY RTU-4
 TO BE IN COMPLIANCE.
  
 5) PLEASE PROVIDE A SUBMITTAL FOR THE CO SENSOR WITH AN
 APPROVAL STAMP BY THE EOR.
  
 6) PROVIDE COMPLETE ENGINEERING FOR INSTALLATION OF THE
 RTU'S INCLUDING THE WIND DESIGN CRITERIA, AND
 ATTACHMENT AND FASTENING DETAILS- SECTION 301.15.
  
 7) SHOW THE LOCATION(S) OF THE UNIT HEATER ON THE
 PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-12-21 Cont ID  
Sent By gjohnson Date 2016-12-21 Time 15:46 Rev Time 0.00
Received By gjohnson Date 2016-12-21 Time 15:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-03-29 Cont ID  
Sent By llouie Date 2017-03-29 Time   Rev Time 0.00
Received By llouie Date 2017-03-29 Time   Sent To  
Notes
2017-03-29 15:55:57* ZONED GC. RETAIL USE (AUTO PARTS AND SUPPLIES)
 PERMITTED IN THE GC ZONING DISTRICT.
  
 * INTERIOR MODIFICATIONS ONLY (INCLUDES STOREFRONT
 MODIFICATIONS - GLAZING).
  
 * SIGNAGE TO BE PERMITTED WITH A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-12-16 Cont ID  
Sent By llouie Date 2016-12-16 Time   Rev Time  
Received By llouie Date 2016-12-16 Time   Sent To  
Notes
2016-12-16 14:51:00- ZONED GC. RETAIL USE (AUTO PARTS AND SUPPLIES)
 PERMITTED IN THE GC ZONING DISTRICT.
  
 - INTERIOR MODIFICATION ONLY (INCLUDES STOREFRONT
 MODIFICATIONS - GLAZING).