Plan Review Details - Permit 16111232
Plan Review Stops For Permit 16111232
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-12-05 Cont ID  
Sent By mgonzale Date 2016-12-05 Time   Rev Time 1.00
Received By mgonzale Date 2016-12-05 Time   Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-09 Cont ID  
Sent By pleduc Date 2016-12-09 Time   Rev Time 0.00
Received By pleduc Date 2016-12-09 Time 12:59 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-02 Cont ID  
Sent By pleduc Date 2016-12-02 Time   Rev Time 0.00
Received By pleduc Date 2016-12-01 Time 16:53 Sent To M
Notes
2016-12-01 17:32:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PLANS INDICATE PAGE NUMBERS 11, 12, 13
 OF 18.
  
 PAGES 1 - 10 ARE MISSING. PLEASE CLARIFY AND/OR
 CORRECT.
  
  
  
 2) SHEET 11 OF 18 - UNDER THE PROPOSED LEGEND A FIRE
 SERVICE LINE IS INDICATED. THIS LINE IS NOT INDICATED
 ANYWHERE ON THIS OR ANY SHEET.
  
 PLEASE CLARIFY AND/OR CORRECT.
  
  
  
 3) THERE IS NO INDICATION ON ANY SHEET THAT THE
 SUBMITTED PLAN WILL BE INSTALLED PER THE REQUIRMENTS OF
 NFPA 24, INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND
 THEIR APPURTENANCES, 2010 EDITION
  
 ENSURE SUBMITTED PLAN IS IN COMPLAINCE AND PLEASE
 PROVIDE A NOTE WITH THE APPLICABLE CODE.
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1* PLANS.
 4.1.1 WORKING PLANS SHALL BE SUBMITTED FOR APPROVAL TO
 THE AUTHORITY HAVING JURISDICTION BEFORE ANY EQUIPMENT
 IS INSTALLED OR REMODELED.
 4.1.2 DEVIATION FROM APPROVED PLANS SHALL REQUIRE
 PERMISSION OF THE AUTHORITY HAVING JURISDICTION.
 4.1.3 WORKING PLANS SHALL BE DRAWN TO AN INDICATED
 SCALE ON SHEETS OF UNIFORM SIZE, WITH A PLAN OF EACH
 FLOOR AS APPLICABLE, AND SHALL INCLUDE THE FOLLOWING
 ITEMS THAT PERTAIN TO THE DESIGN
 OF THE SYSTEM:
 (1) NAME OF OWNER
 (2) LOCATION, INCLUDING STREET ADDRESS
 (3) POINT OF COMPASS
 (4) A GRAPHIC REPRESENTATION OF THE SCALE USED ON ALL
 PLANS
 (5) NAME AND ADDRESS OF CONTRACTOR
 (6) SIZE AND LOCATION OF ALL WATER SUPPLIES
 (7) SIZE AND LOCATION OF STANDPIPE RISERS, HOSE
 OUTLETS, HAND HOSE, MONITOR NOZZLES, AND RELATED
 EQUIPMENT
 (8) THE FOLLOWING ITEMS THAT PERTAIN TO PRIVATE FIRE
 SERVICE MAINS:
 (A) SIZE
 (B) LENGTH
 (C) LOCATION
 (D) WEIGHT
 (E) MATERIAL
 (F) POINT OF CONNECTION TO CITY MAIN
 (G) SIZES, TYPES, AND LOCATIONS OF VALVES, VALVE
 INDICATORS, REGULATORS, METERS, AND VALVE PITS
 (H) DEPTH AT WHICH THE TOP OF THE PIPE IS LAID BELOW
 GRADE
 (I) METHOD OF RESTRAINT
 (9) THE FOLLOWING ITEMS THAT PERTAIN TO HYDRANTS:
 (A) SIZE AND LOCATION, INCLUDING SIZE AND NUMBER OF
 OUTLETS AND WHETHER OUTLETS ARE TO BE EQUIPPED WITH
 INDEPENDENT GATE VALVES
 (B) WHETHER HOSE HOUSES AND EQUIPMENT ARE TO BE
 PROVIDED, AND BY WHOM
 (C) STATIC AND RESIDUAL HYDRANTS USED IN FLOW
 (D) METHOD OF RESTRAINT
 (10) SIZE, LOCATION, AND PIPING ARRANGEMENT OF FIRE
 DEPARTMENT CONNECTIONS
  
  
 4) THERE ARE NO MANUAFACTURES SPEC'S PROVIDED WITH THIS
 SUBMITTAL.
  
 4.1.4 THE WORKING PLAN SUBMITTAL SHALL INCLUDE THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR ANY
 SPECIALLY LISTED EQUIPMENT, INCLUDING DESCRIPTIONS,
 APPLICATIONS, AND LIMITATIONS FOR ANY DEVICES, PIPING,
 OR FITTINGS.
  
 PLEASE PROVIDE THE APPLICABLE MANUFACTURES SPEC FOR
 THIS INSTALLATION.
  
  
  
 5) THE INSTALLATION CONTRACTOR SHALL BE A LICENSED
 UNDERGROUND CONTRACTOR BY THE STATE OF FLORIDA.
  
  
 4.2 INSTALLATION WORK.
 4.2.1 INSTALLATION WORK SHALL BE PERFORMED BY FULLY
 EXPERIENCED AND RESPONSIBLE PERSONS.
  
 THE INSTALLING CONTRACTOR DOES NOT APPEAR TO BE
 LICENSED TO INTALL UNDERGROUND FIRE LINE IN THE STATE
 OF FLORIDA.
  
 FLORIDA STATUTE
  
 633.541-1 IT IS UNLAWFUL FOR ANY ORGANIZATION OR
 INDIVIDUAL TO ENGAGE IN THE BUSINESS OF LAYOUT,
 FABRICATION, INSTALLATION, INSPECTION, ALTERATION,
 REPAIR OR SERVICE OF A FIRE PROTECTION SYSTEM...WITHOUT
 BEING DULY CERTIFIED AND HOLDING A VALID AND EXISTING
 CERTIFICATE, EXCEPT AS HEREINAFTER PROVIDED.?
  
 PLEASE PROVIDE APPLICABLE CERTIFICATION.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-09 Cont ID  
Sent By ccole Date 2016-12-09 Time 14:12 Rev Time 0.00
Received By ccole Date 2016-12-09 Time 14:12 Sent To  
Notes
2016-12-07 13:01:31RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-05 Cont ID  
Sent By skennedy Date 2016-12-05 Time 17:18 Rev Time 0.00
Received By skennedy Date 2016-11-30 Time 13:56 Sent To  
Notes
2016-12-01 13:56:35ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-09 Cont ID  
Sent By ccole Date 2016-12-09 Time 14:12 Rev Time 0.00
Received By ccole Date 2016-12-09 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-05 Cont ID  
Sent By ccole Date 2016-12-05 Time 12:05 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 12:05 Sent To P
Notes
2016-12-05 12:06:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16111232
 12/5/16
  
 1) COMPLY WITH FIRE DEPT. REVIEW COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  