Plan Review Details - Permit 16111231
Plan Review Stops For Permit 16111231
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-09 Cont ID  
Sent By vperez Date 2016-12-09 Time 13:51 Rev Time 0.00
Received By vperez Date 2016-12-09 Time 13:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-05 Cont ID  
Sent By vperez Date 2016-12-05 Time 06:39 Rev Time 0.00
Received By vperez Date 2016-12-05 Time 06:39 Sent To  
Notes
2016-12-05 06:40:27PLEASE ADDRESS FIRE COMMENTS FOR A COMPLETE ELECTRICAL
 REVIEW.
  
 VAL PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-09 Cont ID  
Sent By pleduc Date 2016-12-09 Time   Rev Time 0.00
Received By pleduc Date 2016-12-09 Time 13:02 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-02 Cont ID  
Sent By pleduc Date 2016-12-02 Time   Rev Time 0.00
Received By pleduc Date 2016-12-01 Time 16:32 Sent To E
Notes
2016-12-01 16:48:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO EQUIPMENT SPECS PROVIDED WITH THIS
 SUMITTAL, BOTH FOR THE FUEL TANK AND THE GENERATOR.
  
 PLEASE PROVIDE THE SPECS FOR EACH, INCLUDE WHAT TYPE OF
 FUEL AND HOW IT WILL BE PROTECTED FROM VEHICLE IMPACT.
  
  
  
 2) HOW WILL THE POWER BE ACCESSED, A CABLE CROSS OVER
 IS INDICATED. IS THAT GROUND CABLEING, EXTENSION CORDS,
 OVERHEAD WIRES, ETC.
  
 HOW WILL THESE POWER LINES BE SUPPORTED AND/OR
 PROTECTED FROM PEDESTRIAN OR CONSTRUCTION EQUIPMENT
 IMPACT?
  
 WILL THE CONNECTIONS TO THE BUILDING BE TO PERMANENTLY
 INSTALLED ELECTRICAL EQUIPMENT OR TEMPORARY ?
  
 PLEASE PROVIDE DETAILS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-09 Cont ID  
Sent By vperez Date 2016-12-09 Time 13:58 Rev Time 0.00
Received By vperez Date 2016-12-09 Time 13:58 Sent To  
Notes
2016-12-07 13:00:04RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-05 Cont ID  
Sent By vperez Date 2016-12-05 Time 06:40 Rev Time 0.00
Received By vperez Date 2016-12-05 Time 06:40 Sent To  
Notes
2016-12-01 13:59:34ROUTED TO FIRE INBOX