Plan Review Details - Permit 16111217
Plan Review Stops For Permit 16111217
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-16 Cont ID  
Sent By jwitmer Date 2017-02-15 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2017-02-15 Time   Sent To  
Notes
2017-02-15 13:44:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16111217
 ADD: 2000 CONTINENTAL DR.
 CONT: TBD/ TO BE DETERMINED
 TEL: ??????? NO CONTACT INFO.
 E-MAIL: WINKEL-CONSTRUCTION.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. FEB. 16/ 2017
 ACTION: PASSED
  
 1) I RECEIVED AN E-MAIL SEE ATTACHMENT FROM THE SENIOR
 PROJECT MANAGER THEA WATTERS THE MEZZANINE WAS
 COMPLETELY REMOVED FROM THE PROJECT. I'VE REDLINED
 SHEET A2.2 AND ATTACHED A COPY OF LETTER FROM CKA AND
 ASSOCIATES THAT THE MEZZANINE HAS BEEN REMOVED FROM THE
 PROJECT.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-03 Cont ID  
Sent By jwitmer Date 2017-02-03 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2017-02-03 Time 06:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By jwitmer Date 2016-12-08 Time 14:05 Rev Time  
Received By jwitmer Date 2016-12-08 Time 06:15 Sent To  
Notes
2016-12-08 08:59:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16111217
 ADD: 2000 CONTINENTAL DR.
 CONT: TBD/ TO BE DETERMINED
 TEL: ??????? NO CONTACT INFO.
 E-MAIL: ?????? NO CONTACT INFO.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. DEC. 08/ 2016
 ACTION: DENIED
  
 1) SHEET A2.0 DETAIL # 2 MEZZANINE LEVEL. THE PLANS
 INDICATE THE SHADED AREA INDICATES AREA OF INCIDENTAL
 STORAGE 646 GROSS SQUARE FEET. THE AREA OF THE
 MEZZANINE IS LESS THAN 2/3RDS OF THE AGGREGATE STORAGE
 AREA OPEN TO THE BELOW.
  
 THE DESIGNER OF RECORD APPEARS THAT THE AREA
 LIMITATIONS ARE BEING TAKEN ON THE TYPE OF OCCUPANCY.
 PLEASE BE AWARE OF THE AREA LIMITATIONS FOUND IN
 SECTION 505.2.1 OF THE 2014 FBC-B. 2014 505.2.1 AREA
 LIMITATION. THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL BE NOT GREATER THAN
 ONE-THIRD OF THE FLOOR AREA OF THAT ROOM OR SPACE IN
 WHICH THEY ARE LOCATED. THE ENCLOSED PORTION OF A ROOM
 SHALL NOT BE INCLUDED IN A DETERMINATION OF THE FLOOR
 AREA OF THE ROOM IN WHICH THE MEZZANINE IS LOCATED. IN
 DETERMINING THE ALLOWABLE MEZZANINE AREA, THE AREA OF
 THE MEZZANINE SHALL NOT BE INCLUDED IN THE FLOOR AREA
 OF THE ROOM.
  
 THE EXCEPTION #1 IS FOR SPECIAL INDUSTRIAL OCCUPANCIES
 IS A CARRY OVER FROM THE 2007 FBC-B FOR F-3 OCCUPANCIES
 LIKE STEEL MILLS, PAPER PLANTS AND GENERATING PLANTS,
 AND AGAIN THE CODE READS NOT GREATER THAN TWO-THIRDS OF
 THE FLOOR AREA OF THE ROOM. NOT FOR STORAGE
 OCCUPANCIES.
 EXCEPTION # 2 IS FOR TYPE I OR II CONSTRUCTION AND THE
 LIMITATION IS NOT GREATER THAN ONE-HALF OF THE FLOOR
 AREA OF THE ROOM IN BUILDINGS AND STRUCTURES EQUIPPED
 THROUGHOUT WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM
 IN ACCORDANCE WITH SECTION 903.3.1.1 AND AN APPROVED
 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN
 ACCORDANCE WITH SECTION 907.5.2.2. AGAIN THE CODE
 STATES WITHIN THE ROOM THE MEZZANINE IS LOCATED.
 EXCEPTION # 3 IS FOR TYPE III BUILDING IS FOR S2
 OCCUPANCY 505.2.1 AREA LIMITATION IS TAKEN FOR THE AREA
 OF THE ROOM IN WHICH THE MEZZANINE IS TAKEN, THIS IS A
 VERY SPECIFIC INCREASE FOR WAREHOUSE TYPE OCCUPANCIES.
 PLEASE CONSIDER THE AREA ABOVE THE 1ST FLOOR NOT A
 MEZZANINE BUT A TRUE 2ND FLOOR AND DESIGN FROM THAT
 PREMISE. I HAVE CONSULTED WITH THE BUILDING OFFICIAL ON
 THIS MATTER.
  
 2) SHEET A6.1 DETAIL 11 & 12 SECTIONS THROUGH THE
 FLOOR/ CEILING ASSEMBLY , THE FLOOR ASSEMBLY IS UL L524
 THAT PROVIDES A ONE HOUR FIRE RATED ASSEMBLY, WHEN
 REVIEWING THE UL L524 FLOOR ASSEMBLY THE SUBMITTED
 DETAIL HAS LEFT OUT THE FINISH FLOOR SYSTEM, THERE ARE
 16 FLOOR SYSTEMS LISTED UNDER THIS ONE UL LISTING.
 AS SHOWN WITH ? INCH T& G PLYWOOD HOW WILL THE FLOOR
 SYSTEM WITHSTAND THE LOADING FOR STORAGE LOADS, 125 PSF
 LIGHT OR 250 PSF HEAVY SEE FBC-B TABLE 1607.1.
  
 2A) PLEASE SHOW COMPLIANCE WITH 106.1 LIVE LOADS
 POSTED. WHERE THE LIVE LOADS FOR WHICH EACH FLOOR OR
 PORTION THEREOF OF A COMMERCIAL OR INDUSTRIAL BUILDING
 IS OR HAS BEEN DESIGNED TO EXCEED 50 PSF (2.40 KN/M2),
 SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY
 THE OWNER IN THAT PART OF EACH STORY IN WHICH THEY
 APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO
 REMOVE OR DEFACE SUCH NOTICES.
  
 2B) 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111
 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS,
 REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 2C) 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL
 TO PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON
 ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION
 THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS
 CODE.
  
 2D) SHEET S-1 PROVIDES THE DESIGN CRITERIA FOR THE
 MEZZANINE/ 2ND FLOOR BUT THERE IS NO STRUCTURAL
 COMPONENTS FOR THE MEZZANINE/ 2ND FLOOR FRAMING MEMBERS
 NOR FOR THE COLUMNS NOR WALL CONNECTIONS TO THE
 EXISTING WALL. THE PLANS DO NOT INDICATE IF THERE ARE
 FOUNDATIONS REQUIRED FOR THE NEW STEEL POST THAT WILL
 BE SUPPORTING THE NEW 2ND FLOOR STORAGE AREA.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 FOUNDATION
 WALL SYSTEMS
 FLOOR SYSTEMS
 STAIR SYSTEMS
 GUARDRAIL & HANDRAIL SYSTEMS
  
 3A) SHEET A2.0 INDICATES A NEW 42 INCH ENTRY DOOR,
 PLEASE SHOW COMPLIANCE WITH :
 / 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,
  
 3B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-17 Cont ID  
Sent By vperez Date 2017-02-17 Time 15:30 Rev Time 0.00
Received By vperez Date 2017-02-17 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-02-08 Cont ID  
Sent By albarran Date 2017-02-08 Time 12:46 Rev Time 0.00
Received By albarran Date 2017-02-07 Time 14:20 Sent To I
Notes
2017-02-08 12:46:39ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: CONTINENTAL DIALYSIS CARE CENTER RENO.
 JOB ADDRESS: 2000 CONTINENTAL DRIVE
 DESCRIPTION: ADD 15 DIALYSIS TREATMENT STATIONS TO
 EXISTING AS PER PERMIT
 MASTER PERMIT: 16111217
  
 BELOW PLEASE FIND A RESPONSE TO YOUR CORRECTIONS AS
 PRESENTED AND ADDITIONAL ITEMS PREVIOUSLY OVERLOOKED BY
 THE REVIEWER. ADDITIONAL CORRECTIONS MAY BE REQUIRED
 AFTER REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WHEN YOU RESUBMIT, PLEASE REARRANGE THE PLANS SO
 THAT THE NEW ?T? SHEET APPEARS AT THE BEGINNING RATHER
 THAN MIXED IN THE PLAN SET.
 2. YOUR NOTE TO THE CODE REFERENCE DOES NOT NECESSARILY
 MEET THE REQUIREMENTS. YOU NEED TO SHOW THE ACTUAL
 WIREWAY SIZE ON THE PLANS. AN ERROR HERE CAN BE A VERY
 COSTLY REPAIR.
 3. PROVIDE THE DISTANCE OF ALL THE SERVICES (UTILITY &
 GENERATOR) TO DETERMINE COMPLIANCE WITH THE VOLTAGE
 DROP REQUIREMENTS OF THE FBC-EC405.7.3.
 4. WHEN YOU FACTOR IN THE REQUIRED ADJUSTMENTS FOR NEC
 310.15(B)(3)(A) FOR MORE THAN THREE CURRENT CARRYING
 CONDUCTORS INSIDE THE RACEWAY AND THE CORRECTION PER
 NEC 310.15(B)(2)(A) FOR THE ABOVE GROUND RACEWAYS
 EXPOSED TO DIRECT SUNLIGHT THE SPECIFIED CONDUCTORS ARE
 NOT ADEQUATE TO CARRY THE PROJECTED LOAD.
 5. THE PROVIDED RISER DIAGRAM IS CONFUSING WHEN
 REFERRING TO THE PROPOSED RACEWAY PROPERTIES, YOU
 INDICATE PVC AND ON THE SAME DESCRIPTION YOU STATE RMC.
 6. YOU SHALL PROVIDE MANUFACTURER SPECS FOR THE
 PROPOSED GENERATOR (THE GENERATOR REQUIRES A SEPARATE
 PERMIT AND SUBMITTAL PACKAGE).
 7. WHEN SUBMITTING THE CORRECTION HEREIN MENTIONED,
 PLEASE INCLUDE THE NOTE PER NEC 110.16 FOR THE
 ARC-FLASH WARNING.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-19 Cont ID  
Sent By mvaldes Date 2016-12-19 Time 10:27 Rev Time 0.00
Received By mvaldes Date 2016-12-15 Time 09:39 Sent To  
Notes
2016-12-19 10:29:17JOB PERMIT NUMBER: 16111217
 JOB ADDRESS: 2000 CONTINENTAL DRIVE
 WEST PALM BEACH FLORIDA
 DATE: DECEMBER 19, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] THE APPLICABLE NFPA 101 LIFE SAFETY CODE IN EFFECT
 IS THE 2012 EDITION. PLEASE CORRECT NOTE.
  
 2] SHOW THE WIRE-WAY SIZE IN ACCORDANCE WITH NEC 376 &
 378.
  
 3] PROVIDE FPL AVAILABLE FAULT CURRENT & SHOW AIC
 CALCULATIONS TO VERIFY SHORT-CIRCUIT RATING OF
 ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9.
  
 4] MARK EXTERIOR GFCI RECEPTACLE OUTLET AS WP/WR PER
 NEC 406.9(B).
  
 5] ADD A NOTE FOR ARC-FLASH WARNING LABEL ON ELECTRICAL
 EQUIPMENT PER NEC 110.16.
  
 6] PROVIDE EXIT/EMERGENCY COMBO IN NORTH EGRESS DOOR
 LEADING TO PUBLIC WAY PARKING. FBC 1006 & 1011.
  
 7] FIRE ALARM & LOW VOLTAGE SHALL BE UNDER A SEPARATE
 PERMIT. A NOTE SHALL SUFFICE.
  
 8] WHEN YOU RE-SUBMIT PLEASE FILL OUT " COMPLETION
 AGREEMENT & CONDITIONAL / PHASED OCCUPANCY REQUEST"
 FORM,
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-02-15 Cont ID  
Sent By wjolin Date 2017-02-15 Time 15:51 Rev Time 0.00
Received By wjolin Date 2017-02-15 Time 15:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-27 Cont ID  
Sent By wjolin Date 2017-01-27 Time 16:14 Rev Time 0.00
Received By wjolin Date 2017-01-27 Time 16:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-20 Cont ID  
Sent By wjolin Date 2016-12-20 Time 13:47 Rev Time 0.00
Received By wjolin Date 2016-12-20 Time 12:31 Sent To  
Notes
2016-12-20 13:47:102000 CONTINENTAL DRIVE
 PERMIT #16111217
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TITLE SHEET: PLANS INDICATE THIS OCCUPANCY TO BE A
 BUSINESS OCCUPANCY; HOWEVER, THIS APPEARS TO BE AN
 AMBULATORY HEALTHCARE OCCUPANCY PER NFPA 101 SECTION
 3.3.188.1 AMBULATORY HEALTH CARE OCCUPANCY. AN
 OCCUPANCY USED TO PROVIDE SERVICES OR TREATMENT
 SIMULTANEOUSLY TO FOUR OR MORE PATIENTS THAT PROVIDES,
 ON AN OUTPATIENT BASIS, ONE OR MORE OF THE FOLLOWING:
 (1) TREATMENT FOR PATIENTS THAT RENDERS THE PATIENTS
 INCAPABLE OF TAKING ACTION FOR SELFPRESERVATION UNDER
 EMERGENCY CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS;
 (2) ANESTHESIA THAT RENDERS THE PATIENTS INCAPABLE OF
 TAKING ACTION FOR SELF-PRESERVATION UNDER EMERGENCY
 CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS; (3)
 EMERGENCY OR URGENT CARE FOR PATIENTS WHO, DUE TO THE
 NATURE OF THEIR INJURY OR ILLNESS, ARE INCAPABLE OF
 TAKING ACTION FOR SELF-PRESERVATION UNDER EMERGENCY
 CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS.
  
 TITLE SHEET: PLANS INDICATE THE APPLICABLE CODE AS
 "2000 NFPA 101 LIFE SAFETY CODE - CHAPTER 21." PLEASE
 JUSTIFY THE USE OF THIS CODE IN LIEU OF THE 5TH EDITION
 OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 CIVIL SHEET 1: PLAN INDICATES A NEW UNDERGROUND
 FIRELINE FOR A NEW FIRE SPRINKLER SYSTEM; HOWEVER, THE
 TITLE SHEET MAKES NO MENTION OF THE INTENT TO PROTECT
 THE BUILDING WITH AUTOMATIC SPRINKLERS. PER NFPA 24
 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE
 MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN
 BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 FIRE SPRINKLER DESIGN: ENGINEERED FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. PER SECTION 105.3.1.2(2)
 OF THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 SHEET LS2.0: MEZZANINE SIZE APPEARS TO BE A SECOND
 FLOOR. PER NFPA 101 SECTION 8.6.10.2 AREA LIMITATIONS.
 THE AGGREGATE AREA OF MEZZANINES LOCATED WITHIN A ROOM
 SHALL NOT EXCEED ONE-THIRD THE OPEN AREA OF THE ROOM IN
 WHICH THE MEZZANINES ARE LOCATED. ENCLOSED SPACE SHALL
 NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE
 ROOM IN WHICH THE MEZZANINE IS LOCATED.
  
 NOTE: A SEPARATE PERMIT (UG FIRELINE) IS NEEDED FOR THE
 INSTALLATION OF A PRIVATE FIRE MAIN IN ACCORDANCE WITH
 NFPA 24.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-17 Cont ID  
Sent By vperez Date 2017-02-17 Time 15:35 Rev Time 0.00
Received By vperez Date 2017-02-17 Time 15:35 Sent To  
Notes
2017-02-09 10:29:14B38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-08 Cont ID  
Sent By albarran Date 2017-02-08 Time 13:03 Rev Time 0.00
Received By albarran Date 2017-01-24 Time 11:36 Sent To  
Notes
2017-02-08 13:35:05I SPOKE W/DENNIS OF WINKEL CONSTRUCTION N THE MATTER. I
 EXPLAINED THE ELECTRICAL CONCERNS AND PER HIS REQUEST I
 EMAILED HIM A COPY OF MY NOTES. HE WILL BE COMING IN TO
 SEE GJOHNSON TOMORROW TO SUBMIT PLUMBING SHEETS. FILE
 PLACED ON GJ'S DESK. MA
2017-01-25 11:37:27B38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-09 Cont ID  
Sent By gjohnson Date 2017-01-09 Time 12:13 Rev Time 0.00
Received By gjohnson Date 2016-11-30 Time 11:05 Sent To  
Notes
2016-12-01 11:05:18B38

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-12-08 Cont ID  
Sent By jwitmer Date 2016-12-08 Time 14:06 Rev Time  
Received By jwitmer Date 2016-12-08 Time 06:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-02-13 Cont ID  
Sent By ccole Date 2017-02-13 Time 16:00 Rev Time 0.00
Received By ccole Date 2017-02-13 Time 17:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-01-31 Cont ID  
Sent By ccole Date 2017-01-31 Time 16:19 Rev Time 0.00
Received By ccole Date 2017-01-31 Time 16:19 Sent To  
Notes
2017-01-31 16:33:562ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16111217
 1/31/17
  
 1) M2.0: IT APPEARS FROM THE DRAWING THAT INADEQUATE
 MAKEUP AIR IS BEING PROVIDED FOR THE MEDICAL WASTE ROOM
 EXHAUST. REFER TO SECTION 601.2 EXCEPTION 1 AND PROVIDE
 A CALCULATION USING THE CFMS OF O/A BEING PROVIDED TO
 CORRIDOR 120.
  
 2) M2.0: PLEASE INDICATE THE EXACT DISCHARGE LOCATION
 OF THE FC-1 CONDENSATE DRAINAGE PIPING. PLEASE NOTE
 THAT IT SHALL NOT DRAIN INTO THE CITY SANITARY SYSTEM
 PER SECTION 90-126 CITY OF WEST PALM BEACH CODE OF
 ORDINANCES.
  
 3) M2.1: 2ND REQUEST FOR THE WIND LOAD DESIGN CRITERIA
 FOR INSTALLATION OF THE ROOFTOP STAND AND CONDENSER
 UNIT- SEE SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By ccole Date 2016-12-08 Time 09:31 Rev Time 0.00
Received By ccole Date 2016-12-08 Time 09:31 Sent To  
Notes
2016-12-08 09:52:371ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16111217
 12/8/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR, AND SHOW THE AMOUNTS PER
 EACH AIR HANDLER.
  
 2) PROVIDE AN EXHAUST FAN SCHEDULE ON THE PLAN.
  
 3) MED WASTE ROOM FAN: A) PROVIDE A SIZING CALCULATION.
 B) INDICATE HOW MAKEUP AIR IS BEING PROVIDED. C)
 INDICATE THE SEQUENCE OF OPERATION FOR THE FAN.
  
 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AIR HANDLERS AND DUCTLESS SYSTEM- SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
  
 5) SHEET M2.0: CHANGE THE SD LABEL TO FD IN THE MED
 RECORDS ROOM.
  
 6) M3.0: PROVIDE MORE INFORMATION ABOUT THE USE OF THE
 VOLUME DAMPERS FOR TEMORARY SHUTDOWN OF THE SIR SUPPLY
 IN THE EXPANDED STATIONS ROOM. WHICH CODE, STANDARD,
 REGULATION, OR GUIDELINE ETC, IS REQUIRING THIS
 PROCEDURE?
  
 7) PROVIDE A MECHANICAL ROOF PLAN INDICATING ALL
 REQUIRED CLEARANCE DISTANCE MEASUREMENTS FOR THE AIR
 INTAKES AS REQUIRED BY SECTION 401.4.
  
 8) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS FOR THE NEW AIR HANDLERS- SECTION 307.
  
 9) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE NEW
 AC CONDNENSERS TO THE SLABS- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-02-09 Cont ID  
Sent By gjohnson Date 2017-02-09 Time 10:54 Rev Time 0.00
Received By gjohnson Date 2017-02-09 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-02-09 Cont ID  
Sent By gjohnson Date 2017-02-07 Time 10:04 Rev Time 0.00
Received By gjohnson Date 2017-02-07 Time 08:36 Sent To  
Notes
2017-02-07 10:08:56THE PLUMBING PAGES NEED TO BE REPLACED PER ARCHITECT
 2/7/17 GPJ

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-09 Cont ID  
Sent By gjohnson Date 2017-01-09 Time 11:20 Rev Time 0.00
Received By gjohnson Date 2017-01-06 Time 15:13 Sent To  
Notes
2017-01-09 12:13:251ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS TO BE MEASURE FROM FINISHED FLOOR TO TOP
 OF GRIPPING SURFACE. PER FBC PL 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 2.TWO WATER FOUNTAINS ARE REQUIRED THE PLAN IS ONLY
 SHOWING A SINGLE. PER FBC PL [B] 410.2
 MINIMUM NUMBER.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 FBC ACC 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 3. TEMPERED WATER REQUIRED AT THE LAVATORY IN
 BATHROOMS. PER FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 4. SHT. P2.0 THE DEVELOPED LENGTH OF THE VENT FOR P-3
 AND P-16 IN THE NORTH WEST CORNET OF ROOM 131 APPEARS
 TO BE OVER 40' IT SHALL BE SIZED ACCORDING TO FBC PL
 906.2
 VENTS EXCEEDING 40 FEET (12 192 MM) IN DEVELOPED LENGTH
 SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE
 ENTIRE DEVELOPED LENGTH OF THE VENT PIPE.
  
 5. SHT. P3-0 THE NOTE ON THE PLAN FOR THE CONTINUATION
 OF THE BICARB AND RO SYSTEM IS ON ME-1 BUT THERE NOT IN
 THE PLAN SET PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 6. THE VENT FOR P-15 AND P-3 IN ROOM 139 CAN NOT RUN
 HORIZONTAL BELOW THE FLOOD LEVEL RIM OF THE FIXTURE IT
 CAN RUN AT A 45 ANGLE OR USE A AAV. PER FBC PL 905.4
 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-26 Cont ID  
Sent By ajones Date 2017-01-26 Time 10:37 Rev Time 0.00
Received By ajones Date 2017-01-26 Time 10:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-12-06 Cont ID  
Sent By ajones Date 2016-12-06 Time 14:52 Rev Time 0.00
Received By ajones Date 2016-12-06 Time 14:52 Sent To  
Notes
***NONE***