| 2016-12-08 08:59:56 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16111217 |
| | ADD: 2000 CONTINENTAL DR. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ??????? NO CONTACT INFO. |
| | E-MAIL: ?????? NO CONTACT INFO. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. DEC. 08/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A2.0 DETAIL # 2 MEZZANINE LEVEL. THE PLANS |
| | INDICATE THE SHADED AREA INDICATES AREA OF INCIDENTAL |
| | STORAGE 646 GROSS SQUARE FEET. THE AREA OF THE |
| | MEZZANINE IS LESS THAN 2/3RDS OF THE AGGREGATE STORAGE |
| | AREA OPEN TO THE BELOW. |
| | |
| | THE DESIGNER OF RECORD APPEARS THAT THE AREA |
| | LIMITATIONS ARE BEING TAKEN ON THE TYPE OF OCCUPANCY. |
| | PLEASE BE AWARE OF THE AREA LIMITATIONS FOUND IN |
| | SECTION 505.2.1 OF THE 2014 FBC-B. 2014 505.2.1 AREA |
| | LIMITATION. THE AGGREGATE AREA OF A MEZZANINE OR |
| | MEZZANINES WITHIN A ROOM SHALL BE NOT GREATER THAN |
| | ONE-THIRD OF THE FLOOR AREA OF THAT ROOM OR SPACE IN |
| | WHICH THEY ARE LOCATED. THE ENCLOSED PORTION OF A ROOM |
| | SHALL NOT BE INCLUDED IN A DETERMINATION OF THE FLOOR |
| | AREA OF THE ROOM IN WHICH THE MEZZANINE IS LOCATED. IN |
| | DETERMINING THE ALLOWABLE MEZZANINE AREA, THE AREA OF |
| | THE MEZZANINE SHALL NOT BE INCLUDED IN THE FLOOR AREA |
| | OF THE ROOM. |
| | |
| | THE EXCEPTION #1 IS FOR SPECIAL INDUSTRIAL OCCUPANCIES |
| | IS A CARRY OVER FROM THE 2007 FBC-B FOR F-3 OCCUPANCIES |
| | LIKE STEEL MILLS, PAPER PLANTS AND GENERATING PLANTS, |
| | AND AGAIN THE CODE READS NOT GREATER THAN TWO-THIRDS OF |
| | THE FLOOR AREA OF THE ROOM. NOT FOR STORAGE |
| | OCCUPANCIES. |
| | EXCEPTION # 2 IS FOR TYPE I OR II CONSTRUCTION AND THE |
| | LIMITATION IS NOT GREATER THAN ONE-HALF OF THE FLOOR |
| | AREA OF THE ROOM IN BUILDINGS AND STRUCTURES EQUIPPED |
| | THROUGHOUT WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM |
| | IN ACCORDANCE WITH SECTION 903.3.1.1 AND AN APPROVED |
| | EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN |
| | ACCORDANCE WITH SECTION 907.5.2.2. AGAIN THE CODE |
| | STATES WITHIN THE ROOM THE MEZZANINE IS LOCATED. |
| | EXCEPTION # 3 IS FOR TYPE III BUILDING IS FOR S2 |
| | OCCUPANCY 505.2.1 AREA LIMITATION IS TAKEN FOR THE AREA |
| | OF THE ROOM IN WHICH THE MEZZANINE IS TAKEN, THIS IS A |
| | VERY SPECIFIC INCREASE FOR WAREHOUSE TYPE OCCUPANCIES. |
| | PLEASE CONSIDER THE AREA ABOVE THE 1ST FLOOR NOT A |
| | MEZZANINE BUT A TRUE 2ND FLOOR AND DESIGN FROM THAT |
| | PREMISE. I HAVE CONSULTED WITH THE BUILDING OFFICIAL ON |
| | THIS MATTER. |
| | |
| | 2) SHEET A6.1 DETAIL 11 & 12 SECTIONS THROUGH THE |
| | FLOOR/ CEILING ASSEMBLY , THE FLOOR ASSEMBLY IS UL L524 |
| | THAT PROVIDES A ONE HOUR FIRE RATED ASSEMBLY, WHEN |
| | REVIEWING THE UL L524 FLOOR ASSEMBLY THE SUBMITTED |
| | DETAIL HAS LEFT OUT THE FINISH FLOOR SYSTEM, THERE ARE |
| | 16 FLOOR SYSTEMS LISTED UNDER THIS ONE UL LISTING. |
| | AS SHOWN WITH ? INCH T& G PLYWOOD HOW WILL THE FLOOR |
| | SYSTEM WITHSTAND THE LOADING FOR STORAGE LOADS, 125 PSF |
| | LIGHT OR 250 PSF HEAVY SEE FBC-B TABLE 1607.1. |
| | |
| | 2A) PLEASE SHOW COMPLIANCE WITH 106.1 LIVE LOADS |
| | POSTED. WHERE THE LIVE LOADS FOR WHICH EACH FLOOR OR |
| | PORTION THEREOF OF A COMMERCIAL OR INDUSTRIAL BUILDING |
| | IS OR HAS BEEN DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), |
| | SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY |
| | THE OWNER IN THAT PART OF EACH STORY IN WHICH THEY |
| | APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO |
| | REMOVE OR DEFACE SUCH NOTICES. |
| | |
| | 2B) 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A |
| | CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 |
| | SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, |
| | REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | 2C) 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL |
| | TO PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON |
| | ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION |
| | THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS |
| | CODE. |
| | |
| | 2D) SHEET S-1 PROVIDES THE DESIGN CRITERIA FOR THE |
| | MEZZANINE/ 2ND FLOOR BUT THERE IS NO STRUCTURAL |
| | COMPONENTS FOR THE MEZZANINE/ 2ND FLOOR FRAMING MEMBERS |
| | NOR FOR THE COLUMNS NOR WALL CONNECTIONS TO THE |
| | EXISTING WALL. THE PLANS DO NOT INDICATE IF THERE ARE |
| | FOUNDATIONS REQUIRED FOR THE NEW STEEL POST THAT WILL |
| | BE SUPPORTING THE NEW 2ND FLOOR STORAGE AREA. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | FOUNDATION |
| | WALL SYSTEMS |
| | FLOOR SYSTEMS |
| | STAIR SYSTEMS |
| | GUARDRAIL & HANDRAIL SYSTEMS |
| | |
| | 3A) SHEET A2.0 INDICATES A NEW 42 INCH ENTRY DOOR, |
| | PLEASE SHOW COMPLIANCE WITH : |
| | / 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS , |
| | |
| | 3B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |