Plan Review Details - Permit 16111142
Plan Review Stops For Permit 16111142
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-21 Cont ID  
Sent By jgomez Date 2017-02-21 Time 17:09 Rev Time 0.00
Received By jgomez Date 2017-02-21 Time 14:15 Sent To  
Notes
2017-02-21 15:04:54***NOTE:
 ADDRESS WAS CHANGED FROM 428 30TH ST. TO 432 30TH ST.
 BECAUSE THERE ARE 5 BUILDINGS IN THIS LOT AND THIS IS
 THE BUILDING WHERE WORK IS PERFORMED. JG.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- THE AVIARY STRUCTURE WAS REMOVED FROM THE PLANS, BUT
 IT'S ALREADY BUILT. THIS STRUCTURE WAS BUILT WITHOUT
 PERMIT. PROVIDE COMPLETE PLANS AND SPECIFICATIONS FOR
 THE CONSTRUCTION OF THE AVIARY UNDER A SEPARATE PERMIT.
 2- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE FRAMING TO RECEIVE THE NEW STOREFRONT WINDOWS
 SHOWN ON PLANS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS.
 3- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE FRAMING OF THE NEW ENTRY DOOR SHOWN ON PLANS.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-22 Cont ID  
Sent By jgomez Date 2016-12-20 Time 16:17 Rev Time 0.00
Received By jgomez Date 2016-12-20 Time 12:33 Sent To  
Notes
2016-12-20 12:43:49RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 ***NOTE:
 ADDRESS WAS CHANGED FROM 428 30TH ST. TO 432 30TH ST.
 BECAUSE THERE ARE 5 BUILDINGS IN THIS LOT AND THIS IS
 THE BUILDING WHERE WORK IS PERFORMED. JG.
  
  
 1- PLANS SUBMITTED SHOW AN "EXISTING AVIARY". PLANS
 SHOW A LARGE STRUCTURE. ACCORDING TO CITY RECORDS THERE
 ARE NO PERMITS FOR THIS STRUCTURE. PROVIDE COMPLETE
 PLANS, ELEVATIONS, DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THIS STRUCTURE AS
 REQUIRED BY SEC. R301.2.1.1.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 NOTE: COORDINATE WITH ZONING PROPOSED USE OF THE
 STRUCTURE.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ELEVATOR ENTRY DOOR AS SHOWN ON PLANS.
  
 B) LANAI ENTRY DOOR TO BE REPLACED AS SHOWN ON PLANS.
  
 C) ELEVATOR STOREFRONT SYSTEM AS SHOWN ON PLANS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 RE-FRAMING AND REINFORCEMENT AT THE CORNER AREA WHERE
 NEW ELEVATOR SHAFT IS GOING TO BE BUILT. NOTE: THIS
 APPLIES TO FIRST FLOOR, SECOND FLOOR AND ROOF AREA.
 SPECIFY ALL FRAMING MEMBER AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE FRAMING DETAILS DETAILS AND
 SPECIFICATIONS FOR THE FRAMING OF THE ELEVATOR
 HOISTWAY. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE FRAMING OF THE NEW STOREFRONT WINDOWS SHOWN ON
 PLANS. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 7- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE FRAMING OF THE NEW ENTRY DOOR SHOWN ON PLANS.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 8- STRUCTURAL NOTES ON SHEET S-1:
 A) REVISE THE WIND LOAD REFERENCE. THE CURRENT ASCE-7
 IS THE 2010 EDITION NOT 2014. REVISE AS REQUIRED.
 CHAPTER 553 F.S.
  
 B) CLEARLY SPECIFY THE WIND LOAD. WHAT IS THE 140 MPH
 WIND LOAD?. SPECIFY THE ULTIMATE WIND LOAD AND THE
 NOMINAL WIND LOAD. SEC. R301.2.1.3 FBC-RESIDENTIAL. .
 NOTE: THE CITY ULTIMATE WIND SPEED IS 170 MPH.
  
 C) UPDATE ALL THE CODES REFERENCED. SEE CHAPTER 46 OF
 FBBC-RESIDENTIAL FOR THE CURRENT EDITION OF THE
 REFERENCED STANDARDS AND REVISE AS REQUIRED.
  
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-09 Cont ID  
Sent By skennedy Date 2017-02-09 Time 10:05 Rev Time 0.00
Received By skennedy Date 2017-02-09 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-19 Cont ID  
Sent By mvaldes Date 2016-12-19 Time 17:10 Rev Time 0.00
Received By mvaldes Date 2016-12-19 Time 15:24 Sent To  
Notes
2016-12-19 17:11:58JOB PERMIT NUMBER: 16111142
 JOB ADDRESS: 428 30TH ST
 WEST PALM BEACH FLORIDA
 DATE: DECEMBER 19, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] CORRECT EXISTING PANEL SCHEDULE CIRCUIT #24, #26 FOR
 THE CLOTHES DRYER TO A 10 AWG WITH A 30 AMP BKR
 (TYPICAL). FBC-107.3.5.3
  
 2] ADD GENERAL ELECTRICAL NOTES FOR AFCI PROTECTION &
 TAMPER RESISTANT RECEPTACLES. FBC-R SECTIONS E3902.13 &
 E4002.14
  
 3] RECESSED LIGHTING IN THE BUILDING THERMAL ENVELOPE
 SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UN-CONDITIONED SPACES (IF INSTALLED IN
 THERMAL INSULATION THE HOUSING SHALL BE LISTED
 IC-RATED). FBC-E SECTION R402.4.4 A NOTE WILL SUFFICE.
  
 4] PERMANENT INSTALLED LUMINAIRES SHALL BE 75 % HIGH
 EFFICIENT. FBC-E SECTION R404.1 A NOTE WILL SUFFICE.
  
 5] ELEVATOR SHORT CIRCUIT & GROUND FAULT OVERCURRENT
 PROTECTION SHALL BE SIZED IN ACCORDANCE WITH NEC
 620.61.
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-02-13 Cont ID  
Sent By fmittner Date 2017-02-13 Time 14:15 Rev Time 0.00
Received By fmittner Date 2017-02-13 Time 14:15 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-12-22 Cont ID  
Sent By fmittner Date 2016-12-22 Time 15:22 Rev Time 0.00
Received By fmittner Date 2016-12-22 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-21 Cont ID  
Sent By jgomez Date 2017-02-21 Time 17:42 Rev Time 0.00
Received By jgomez Date 2017-02-09 Time 10:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-22 Cont ID  
Sent By jgomez Date 2016-12-22 Time 15:29 Rev Time 0.00
Received By jgomez Date 2016-11-28 Time 14:37 Sent To  
Notes
2016-11-29 14:37:52R15

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-09 Cont ID  
Sent By gjohnson Date 2017-02-09 Time 10:14 Rev Time 0.00
Received By gjohnson Date 2017-02-09 Time 10:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-14 Cont ID  
Sent By gjohnson Date 2016-12-14 Time 14:40 Rev Time 0.00
Received By gjohnson Date 2016-12-14 Time 13:58 Sent To  
Notes
2016-12-14 14:53:301ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ON THE APPLICATION IT STATES ADDITION OF ELEVATOR
 THE PLAN SHOWS IT AS EXISTING PLEASE CLARIFY IS THE
 MASTER BATHROOM EXISTING AS SHOWN ON PLAN IF NOT
 PROVIDE DRAWING OF EXISTING MASTER BATH . PER WPB AMEND
 TO FBC 107.2.1
  
 2. IT IS UNCLEAR IF THE ISOMETRIC DRAWING FOR THE
 MASTER BATH IS NEW OR EXISTING PIPING PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-02-13 Cont ID  
Sent By fmittner Date 2017-02-13 Time 14:15 Rev Time 0.00
Received By fmittner Date 2017-02-13 Time 14:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-12-22 Cont ID  
Sent By fmittner Date 2016-12-22 Time 15:22 Rev Time 0.00
Received By fmittner Date 2016-12-22 Time 15:22 Sent To  
Notes
***NONE***