| 2016-12-01 09:16:56 | 12/02/16 ENGINEER INSPECTION LETTER WAS DELIVERED TO |
| | ART LANGE (INSPECTOR) FOR INSPECTIONS RESULTS. JG |
| | |
| | |
| | |
| | |
| | RESIDENTIAL (R2) REVISION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- INFORMATION ON THE PLANS SUBMITTED IS EXTREMELY |
| | LIGHT IN SOME AREAS AND IS BARELY LEGIBLE. NEED TO |
| | PROVIDE LEGIBLE PLANS THAT ARE SUITABLE FOR READING AND |
| | ARE ADEQUATE FOR THE RECORDS RETENTION PROGRAM. REVISE |
| | AS REQUIRED. SEC.107.2.1.4 CITY AMENDMENTS. |
| | |
| | 2- PLANS SUBMITTED SHOW CLOUDED AREAS THAT ARE DELETING |
| | INFORMATION THAT WAS ALREADY APPROVED AND IT'S SHOWN ON |
| | THE CITY RECORDS. THAT INFORMATION CAN NOT BE DELETED |
| | BECAUSE IT WAS PART OF THE SCOPE OF WORK. WORK WAS DONE |
| | FOR THOSE ITEMS THAT WERE DELETED. NEED TO |
| | RE-INCORPORATE SUCH INFORMATION. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 3- NEED TO COMPLY WITH PROVISO DATED 01/25/16. BUILDING |
| | REVIEW WAS APPROVED WITH THE CONDITION THAT INFORMATION |
| | WAS GOING TO BE REVISED. SEE BELOW FOR COPY OF PROVISO |
| | THAT WAS PASTED ON THE APPROVED PLANS: |
| | |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | |
| | 1- REVISE SIZE OF HEATING/COOLING UNIT FOR NEW BEDROOM: |
| | SIZE OF HEATING AND COOLING WALL UNIT SHOWN ON PLANS IS |
| | OVERSIZED FOR THE NEW BEDROOM. 8,000 BTU UNIT IS |
| | OVERSIZED FOR A ROOM WITH LESS THAN 100S.F . PROVIDE |
| | EQUIPMENT SIZING CALCULATIONS. SEC. C403.2.1 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). EQUIPMENT |
| | CAN NOT EXCEED THE CALCULATED LOADS. SEC. C403.2.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |