Plan Review Details - Permit 16111045
Plan Review Stops For Permit 16111045
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-01 Cont ID  
Sent By jgomez Date 2016-12-01 Time 09:15 Rev Time 0.00
Received By jgomez Date 2016-12-01 Time 07:54 Sent To E
Notes
2016-12-01 09:16:5612/02/16 ENGINEER INSPECTION LETTER WAS DELIVERED TO
 ART LANGE (INSPECTOR) FOR INSPECTIONS RESULTS. JG
  
  
  
  
 RESIDENTIAL (R2) REVISION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- INFORMATION ON THE PLANS SUBMITTED IS EXTREMELY
 LIGHT IN SOME AREAS AND IS BARELY LEGIBLE. NEED TO
 PROVIDE LEGIBLE PLANS THAT ARE SUITABLE FOR READING AND
 ARE ADEQUATE FOR THE RECORDS RETENTION PROGRAM. REVISE
 AS REQUIRED. SEC.107.2.1.4 CITY AMENDMENTS.
  
 2- PLANS SUBMITTED SHOW CLOUDED AREAS THAT ARE DELETING
 INFORMATION THAT WAS ALREADY APPROVED AND IT'S SHOWN ON
 THE CITY RECORDS. THAT INFORMATION CAN NOT BE DELETED
 BECAUSE IT WAS PART OF THE SCOPE OF WORK. WORK WAS DONE
 FOR THOSE ITEMS THAT WERE DELETED. NEED TO
 RE-INCORPORATE SUCH INFORMATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- NEED TO COMPLY WITH PROVISO DATED 01/25/16. BUILDING
 REVIEW WAS APPROVED WITH THE CONDITION THAT INFORMATION
 WAS GOING TO BE REVISED. SEE BELOW FOR COPY OF PROVISO
 THAT WAS PASTED ON THE APPROVED PLANS:
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE SIZE OF HEATING/COOLING UNIT FOR NEW BEDROOM:
 SIZE OF HEATING AND COOLING WALL UNIT SHOWN ON PLANS IS
 OVERSIZED FOR THE NEW BEDROOM. 8,000 BTU UNIT IS
 OVERSIZED FOR A ROOM WITH LESS THAN 100S.F . PROVIDE
 EQUIPMENT SIZING CALCULATIONS. SEC. C403.2.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). EQUIPMENT
 CAN NOT EXCEED THE CALCULATED LOADS. SEC. C403.2.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-07 Cont ID  
Sent By mvaldes Date 2016-12-07 Time 10:32 Rev Time 0.00
Received By mvaldes Date 2016-12-07 Time 10:17 Sent To  
Notes
2016-12-07 10:33:49REVISION 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - COMPLY WITH BUILDING COMMENTS TO PASS ELECTRICAL
 REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-07 Cont ID  
Sent By jgomez Date 2016-12-01 Time 09:16 Rev Time 0.00
Received By mvaldes Date 2016-11-23 Time 11:38 Sent To  
Notes
2016-11-23 11:38:24REVISION ROUTED TO JGOMEZ